Carrier 48EZ-A installation instructions Gas Heating Fan Speed Set-up, Continuous Fan Operation

Page 19

Gas Heating Fan Speed Set-up

To change the gas heating speed:

1.Remove the vinyl cap off of the desired speed tap wire (Refer to Table 6 for color coding). Table 10 shows the temperature rise associated with each fan speed for a given static pressure. Make sure that the speed chosen delivers a temperature rise within the rise range listed on the unit rating plate.

2.Remove the current speed tap wire from the “GAS HEAT” terminal on the interface fan board (IFB) (Fig.14) and place vinyl cap over the connector on the wire.

3.Connect the desired speed tap wire to the “GAS HEAT” terminal on the interface fan board (IFB).

Single Cooling Fan Speed Set-up (Dehumidification feature not used)

To change cooling speed:

1.Remove the vinyl cap off of the desired speed tap wire (Refer to Table 6 for color coding). Add the wet coil pressure drop in Table 8 to the system static to determine the correct cooling airflow speed in Table 10 that will deliver the nominal cooling airflow as listed in Table 1 for each size.

2.Remove the current speed tap wire from the “LOW” terminal on the interface fan board (IFB) (See Fig. 14) and place vinyl cap over the connector on the wire.

3.Connect the desired speed tap wire to the “LOW” terminal on the interface fan board (IFB).

Two Cooling Fan Speeds Set-up (Dehumidification feature used)

IMPORTANT: Dehumidification control must open control circuit on humidity rise above set point.

Use of the dehumidification cooling fan speed requires use of either a 24 VAC dehumidistat or a thermostat which includes control of a 24 VAC dehumidistat connection. In either case, the dehumidification control must open the control circuit on humidity rise above the dehumidification set point. Dehumidification controls are available with the reverse logic; these must not be used.

1.Remove fan speed tap wire from the “LOW” terminal on the interface fan board (IFB) (See Fig. 14).

2.Determine correct normal cooling fan speed for unit and application. Add the wet coil pressure drop in Table 8 to the system static to determine the correct cooling airflow speed in Table 10 that will deliver the nominal cooling airflow as listed in Table 1 for each size.

3.Remove the vinyl cap off of the desired speed tap wire (Refer to Table 6 for color coding) for the normal cooling fan speed and place desired speed tap wire on “HIGH” on the interface board.

4.Refer to airflow tables (Table 10) to determine allowable speeds for the dehumidification cooling fan speed. In Table 10, speeds that are not allowed for dehumidification cooling are shaded.

5.Remove the vinyl cap off of the desired speed tap wire (Refer to Table 6 for color coding) for the dehumidification cooling fan speed and place desired speed tap wire on the “LOW” connection on the interface board (IFB). Verify that static pressure is in the acceptable range for the speed tap to be used for dehumidification cooling.

6.Use any spare vinyl plugs to cap any unused speed tap wires.

Continuous Fan Operation

When the DEHUM feature is not used, the continuous fan speed will be the same as cooling fan speed. When the DEHUM feature is used, the continuous fan will operate on IFB “LOW” speed when the DH control lead is not energized, or IFB “HIGH” speed when the DH lead is energized (see Fig. 14).

NOTE: For heat pump operation, the recommended airflow is 350 to 450 CFM for each 12,000 Btuh of rated cooling capacity.

Table 6 – Color Coding for Indoor Fan Motor Leads

Black = High Speed

Orange = Med---High Speed

Red = Med Speed

Pink = Med---Low Speed

Blue = Low Speed

 

 

 

 

GAS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT

 

HIGH

LOW

 

COM

 

 

 

 

 

 

QC6

 

 

QC7

 

QC4

 

QC3

 

 

 

 

 

 

 

K2

 

 

 

 

 

 

K1

DCR

QCR

CDM/C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RL3

C8

R1L

Q1

 

 

D2

C

 

 

 

 

 

 

 

 

 

 

24VAC/R

 

 

 

 

RI0

 

 

 

 

 

 

 

 

QC1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JM6

 

RI2

 

 

 

 

 

 

 

 

 

 

Q3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C9

 

C4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G1JM5

RI

DL

 

 

 

 

 

 

 

 

 

 

 

 

 

3 AMP

OILL C2

D6

D4

 

 

 

 

 

 

G2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A7

R9

 

AB

A15

 

 

 

 

 

F1

 

 

 

 

 

 

 

 

 

 

 

 

 

C0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C3

 

 

R4

RL4

D5

D3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JW3

 

 

 

P3

 

 

R2

 

R3

 

R5

R6

 

 

 

 

 

 

 

 

 

JW7

QCB

 

 

P2

 

 

 

 

 

 

 

SDL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JW2

 

 

 

 

 

 

Y

Y

R

U

C

24VAC

 

 

 

JW4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JW1

 

P1

 

 

 

 

 

 

 

SSTZ-8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W2

Y2/

G

Y1/

C

R

 

 

 

 

 

 

 

 

 

 

DH

Y

 

 

 

A09058

Fig. 14 - Interface Fan Board (IFB)

48EZ -- A

19

Image 19
Contents Safety Considerations Table of ContentsProvide Unit Support Receiving and InstallationIntroduction Check Equipment48EZ-A24-36 Unit Dimensions 48EZ-A42-60 Unit Dimensions Small Curb Hazard Rig and Place UnitProvide Clearances Personal Injury or Property DamageInspection Install Flue HoodInstall Gas Piping Connect Condensate DrainSediment Trap Fire or Explosion HazardUnit Size 48EZ Physical Data Unit 48EZ-AMaximum Gas Flow Capacity Physical Data Unit 48EZ-A Cont’dHeating Inputs Unit Component Damage Hazard Install Duct ConnectionsConfiguring Units for Downflow Vertical Discharge Alternate MethodSupply Duct Panels Control Voltage Connections Install Electrical ConnectionsSpecial Procedures for 208-V Operation High-Voltage ConnectionsFIRE, EXPLOSION, Electrical Shock Hazard Balance Point Setting-Thermidistat or Hybrid ThermostatPRE-START-UP Transformer ProtectionUnit Sequence of Operation Start-up Heating and Make Adjust- mentsSTART-UP Check for Refrigerant LeaksUnit Damage Hazard Adjust Gas InputCheck Heating Control Check Gas InputCheck Burner Flame Airflow and Temperature RiseLimit Switches Rollout SwitchChecking Cooling Control Operation Start-up Cooling and Make Adjust- mentsChecking and Adjusting Refrigerant Charge Indoor Airflow and Airflow AdjustmentsColor Coding for Indoor Fan Motor Leads Two Cooling Fan Speeds Set-up Dehumidification feature usedGas Heating Fan Speed Set-up Continuous Fan Operation48EZ-A Wet Coil Pressure Drop IN. W.C Filter Pressure Drop Table IN. W.C741 638 547 415 Heating Low Blue 1234 1168 1093 1021 961 894 825 759 687 Heating Low Blue 1736 1695 1642 1601 1553 1512 1465 1427 1381 65oF Heating 1927 1893 1858 1824 1791 1759 1720 1689 1640 65oF Heating 48EZ a 208/230-3-60 Wiring Diagram, Unit 48EZ-A Cooling Charging Table-Subcooling Indoor Blower and Motor MaintenanceCleaning the Blower Motor and Wheel Air FilterMain Burners Limit SwitchInduced Draft combustion air Blower Assembly Burner IgnitionOutdoor Fan Electrical Controls and WiringRefrigerant Circuit Indoor Airflow Pressure SwitchesLoss of Charge Switch Gas InputCopeland Scroll Compressor Puron Refrigerant High-Pressure SwitchExplosion Hazard Refrigerant System Unit Operation and Safety HazardCompressor Oil START-UP Checklist TroubleshootingPuronr R-410A Quick Reference Guide Symptom Cause Remedy Troubleshooting Guide Cooling or Heat Pump Heating ModeTroubleshooting Guide-LED Error Codes Troubleshooting Guide-HeatingIII. START-UP Electrical Supply Voltage Compressor Amps TemperaturesRemove and Store in Job Files Preliminary Information Model noCatalog No 48EZ---06SI
Related manuals
Manual 10 pages 39.3 Kb

48EZ-A specifications

The Carrier 48EZ-A and 48VT-A are two advanced rooftop unit air conditioners that exemplify innovation and efficiency in HVAC technology. Designed for commercial applications, these units provide optimal comfort while ensuring energy conservation and reliability.

One of the standout features of the Carrier 48EZ-A is its high-efficiency cooling system. With SEER ratings reaching up to 16, this model uses advanced compressor technology to ensure that energy consumption stays low while maximizing cooling output. The 48EZ-A incorporates a two-stage scroll compressor that enhances performance during partial load conditions, making it ideal for varying temperature demands throughout the day.

Meanwhile, the Carrier 48VT-A is designed with variable speed technology that allows for precise modulation of airflow and cooling capacity, adapting seamlessly to real-time building conditions. This technology not only improves comfort but also significantly reduces energy usage by optimizing operational efficiency.

Both units are equipped with advanced microprocessor controls that facilitate superior management of the HVAC system. The controls offer programmable options allowing for enhanced control over system operation, scheduling, and diagnostics. This promotes easy maintenance and ensures long-term reliability.

In terms of construction, the Carrier 48EZ-A and 48VT-A units are built with corrosion-resistant materials, ensuring durability and longevity even in challenging environments. The cabinet is designed with insulated panels to minimize sound levels, making them suitable for installation in noise-sensitive locations.

Moreover, both models are equipped for easy installation and serviceability. The logical wiring design and access ports streamline maintenance, reducing downtime and optimizing overall performance. Additionally, they feature an energy-efficient fan design that maximizes airflow while minimizing energy use.

In summary, the Carrier 48EZ-A and 48VT-A rooftop units stand out in the HVAC market for their energy efficiency, advanced technology, and durable construction. These features make them ideal choices for various commercial applications where comfort, efficiency, and reliability are paramount. The combination of high-performance components and user-friendly features positions these models as leaders in modern HVAC solutions.