Carrier 48EZ-A Limit Switch, Burner Ignition, Main Burners, Flue Gas Passageways

Page 29

f.Connect 5 pin plug and 4 pin plug to indoor blower motor.

g.Reinstall blower access panel (see Fig. 19).

3.Restore electrical power to unit. Start unit and check for proper blower rotation and motor speeds during heating and cooling cycles.

1.Remove the induced draft blower assembly according to directions in the Induced Draft Blower Assembly section.

2.Remove the 11 screws holding the flue collector box cover (See Fig. 18) to the heat exchanger assembly. Inspect the heat exchangers.

3.Clean all surfaces, as required, using a wire brush.

Limit Switch

Fan Partition

Flue

 

Mounting

Collector

Inducer

Bracket

Box

Blower

 

 

 

 

Housing

Integrated Gas Unit Controller (IGC)

Auto Transformer

fuses used on 460

volt units only.

(Hidden)

Interface Fan

Board (IFB)

Induced Draft

Motor

Rollout

Burner Mounting Switch

Rack Screw

Remove blower access panel (see Fig. 19). Limit switch is located on the fan partition.

Burner Ignition

Unit is equipped with a direct spark ignition 100 percent lockout system. Ignition module (IGC) is located in the control box (See Fig. 18). Module contains a self-diagnostic LED. During servicing, refer to label diagram or Table 5 in these instructions for LED interpretation.

If lockout occurs, unit may be reset by either momentarily interrupting power supply to unit or by turning selector switch to OFF position at the thermostat.

Main Burners

A

A09193

Fig. 18 - Blower Housing and Flue Collector Box

At the beginning of each heating season, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames and adjust, if necessary.

Removal of Gas Train

To remove the gas train for servicing:

48EZ --

COMPRESSOR

CONTROL

BLOWER ACCESS

ACCESS PANEL PANEL

1.

Shut off main gas valve.

2.

Shut off power to unit and install lockout tag.

3.

Remove control access panel (See Fig. 19).

4.

Disconnect gas piping at unit gas valve.

5.

Remove fan partition mounting bracket (2 screws located

 

on the left side of the control compartment on the fan parti-

 

tion panel). Slide bracket forward, bottom first, to remove

 

(See Fig. 18).

6.

Remove wires connected to gas valve. Mark each wire.

7.

Remove the mounting screw that attaches the burner rack to

 

the unit base (See Fig. 18).

8.

Partially slide the burner rack out of the unit (see Fig. 18

 

and 21). Remove ignitor and sensor wires at the burner as-

ACCESS PANEL

A09207

Fig. 19 - Unit Access Panels

Induced Draft (combustion air) Blower Assembly

The induced-draft blower assembly consists of the inducer motor, the blower housing, and the induced-draft blower wheel.

Clean periodically to assure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during the heating season. For the first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.

To inspect blower wheel, remove draft hood assembly. Shine a flashlight into opening to inspect wheel. If cleaning is required, remove induced-draft blower assembly as follows:

1.Remove control access panel (See Fig. 19).

2.Remove the 5 screws that attach induced-draft blower as- sembly to the flue collector box cover.

3.Slide the assembly out of the unit. (See 20). Clean the blower wheel. If additional cleaning is required, continue with Steps 4 and 5.

4.To remove blower wheel, remove 2 setscrews.

5.To remove inducer motor, remove screws that hold the inducer motor to the blower housing.

6.To reinstall, reverse the procedure outlined above.

Flue Gas Passageways

To inspect the flue collector box and upper areas of the heat exchanger:

 

sembly. Remove rollout switch wires.

9.

Slide the burner rack out of the unit (See Fig. 18 and 21).

10.

To reinstall, reverse the procedure outlined above.

Outdoor Coil, Indoor Coil, and Condensate Drain Pan

Inspect the outdoor coil, indoor coil, and condensate drain pan at least once each year. The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling season. Remove all obstructions, including weeds and shrubs, that interfere with the airflow through the condenser coil.

Straighten bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using the soft brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent-and-water solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring, or air filter(s). For best results, spray outdoor coil fins from inside to outside the unit. On units with an outer and inner condenser coil, be sure to clean between the coils. Be sure to flush all dirt and debris from the unit base.

Inspect the drain pan and condensate drain line when inspecting the coils. Clean the drain pan and condensate drain by removing all foreign matter from the pan. Flush the pan and drain tube with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain tube is restricted, clear it with a “plumbers snake” or similar probe device. Ensure that the auxiliary drain port above the drain tube is also clear.

29

Image 29
Contents Safety Considerations Table of ContentsIntroduction Receiving and InstallationCheck Equipment Provide Unit Support48EZ-A24-36 Unit Dimensions 48EZ-A42-60 Unit Dimensions Small Curb Provide Clearances Rig and Place UnitPersonal Injury or Property Damage HazardInstall Gas Piping Install Flue HoodConnect Condensate Drain InspectionSediment Trap Fire or Explosion HazardUnit Size 48EZ Physical Data Unit 48EZ-AHeating Inputs Physical Data Unit 48EZ-A Cont’dMaximum Gas Flow Capacity Configuring Units for Downflow Vertical Discharge Install Duct ConnectionsAlternate Method Unit Component Damage HazardSupply Duct Panels Special Procedures for 208-V Operation Install Electrical ConnectionsHigh-Voltage Connections Control Voltage ConnectionsPRE-START-UP Balance Point Setting-Thermidistat or Hybrid ThermostatTransformer Protection FIRE, EXPLOSION, Electrical Shock HazardSTART-UP Start-up Heating and Make Adjust- mentsCheck for Refrigerant Leaks Unit Sequence of OperationCheck Heating Control Adjust Gas InputCheck Gas Input Unit Damage HazardLimit Switches Airflow and Temperature RiseRollout Switch Check Burner FlameChecking and Adjusting Refrigerant Charge Start-up Cooling and Make Adjust- mentsIndoor Airflow and Airflow Adjustments Checking Cooling Control OperationGas Heating Fan Speed Set-up Two Cooling Fan Speeds Set-up Dehumidification feature usedContinuous Fan Operation Color Coding for Indoor Fan Motor Leads48EZ-A Wet Coil Pressure Drop IN. W.C Filter Pressure Drop Table IN. W.C741 638 547 415 Heating Low Blue 1234 1168 1093 1021 961 894 825 759 687 Heating Low Blue 1736 1695 1642 1601 1553 1512 1465 1427 1381 65oF Heating 1927 1893 1858 1824 1791 1759 1720 1689 1640 65oF Heating 48EZ a 208/230-3-60 Wiring Diagram, Unit 48EZ-A Cooling Charging Table-Subcooling Cleaning the Blower Motor and Wheel MaintenanceAir Filter Indoor Blower and MotorInduced Draft combustion air Blower Assembly Limit SwitchBurner Ignition Main BurnersRefrigerant Circuit Electrical Controls and WiringOutdoor Fan Loss of Charge Switch Pressure SwitchesGas Input Indoor AirflowExplosion Hazard High-Pressure SwitchCopeland Scroll Compressor Puron Refrigerant Compressor Oil Unit Operation and Safety HazardRefrigerant System Puronr R-410A Quick Reference Guide TroubleshootingSTART-UP Checklist Symptom Cause Remedy Troubleshooting Guide Cooling or Heat Pump Heating ModeTroubleshooting Guide-LED Error Codes Troubleshooting Guide-HeatingRemove and Store in Job Files TemperaturesPreliminary Information Model no III. START-UP Electrical Supply Voltage Compressor AmpsCatalog No 48EZ---06SI
Related manuals
Manual 10 pages 39.3 Kb

48EZ-A specifications

The Carrier 48EZ-A and 48VT-A are two advanced rooftop unit air conditioners that exemplify innovation and efficiency in HVAC technology. Designed for commercial applications, these units provide optimal comfort while ensuring energy conservation and reliability.

One of the standout features of the Carrier 48EZ-A is its high-efficiency cooling system. With SEER ratings reaching up to 16, this model uses advanced compressor technology to ensure that energy consumption stays low while maximizing cooling output. The 48EZ-A incorporates a two-stage scroll compressor that enhances performance during partial load conditions, making it ideal for varying temperature demands throughout the day.

Meanwhile, the Carrier 48VT-A is designed with variable speed technology that allows for precise modulation of airflow and cooling capacity, adapting seamlessly to real-time building conditions. This technology not only improves comfort but also significantly reduces energy usage by optimizing operational efficiency.

Both units are equipped with advanced microprocessor controls that facilitate superior management of the HVAC system. The controls offer programmable options allowing for enhanced control over system operation, scheduling, and diagnostics. This promotes easy maintenance and ensures long-term reliability.

In terms of construction, the Carrier 48EZ-A and 48VT-A units are built with corrosion-resistant materials, ensuring durability and longevity even in challenging environments. The cabinet is designed with insulated panels to minimize sound levels, making them suitable for installation in noise-sensitive locations.

Moreover, both models are equipped for easy installation and serviceability. The logical wiring design and access ports streamline maintenance, reducing downtime and optimizing overall performance. Additionally, they feature an energy-efficient fan design that maximizes airflow while minimizing energy use.

In summary, the Carrier 48EZ-A and 48VT-A rooftop units stand out in the HVAC market for their energy efficiency, advanced technology, and durable construction. These features make them ideal choices for various commercial applications where comfort, efficiency, and reliability are paramount. The combination of high-performance components and user-friendly features positions these models as leaders in modern HVAC solutions.