Carrier 48TC**16 Unit without Thru-Base Connection Kit, Typical Low-Voltage Control Connections

Page 19

Typical

Thermostat

Connections

C

G

W2

W1

O/B/Y2

(see Note)

Y1

R

Central

Terminal

Board

X

C

T

GH E

W2

R

M

 

 

 

O

W1

S

 

 

T

Y2

A

 

 

T

Y1

 

 

 

 

 

R

 

 

 

Unit without Thru-Base Connection Kit —

Pass the thermostat control wires through the bushing on the unit end panel. Route the wire through the snap-in wire tie and up to the web bushing near the control box.. Route the wire through the bushing and into the bottom left side of the control box after removing one of the two knockouts in the corner of the box. Use a connector at the control box to protect the wire as it passes into the control box. Pull the wires over to the terminal strip at the upper left corner of the Central Terminal Board (CTB). Use the connector at the control box and the wire tie to take up any slack in the thermostat wire to ensure that it will not be damaged by contact with the condenser coil. See Fig. 39.

NOTE: If thru-the-bottom connections accessory is used, refer to the accessory installation instructions for information on routing power and control wiring.

48TC**16

Note: Typical multi-function marking. Follow manufacturer’s configuration instructions to select Y2. Do not configure for O output.

Field Wiring

C10903

Fig. 38 - Typical Low-Voltage Control Connections

Thermostat Wire

C10886

Fig. 39 - Thermostat Wire Routing

Heat Anticipator Settings —

Set heat anticipator settings at 0.14 amp for the first stage and 0.14 amp for second-stage heating, when available.

19

Image 19
Contents Installation Instructions Personal Injury and Environmental Hazard Unit Operation and Safety HazardFIRE, Explosion Hazard Electrical Shock HazardUnit Dimensional Drawing 16 Size Unit Plan for Unit Location Service Clearance Dimensional DrawingInspect Unit Plan for Sequence of Unit InstallationProvide Unit Support Roof Curb Details Unit Damage Hazard Field Fabricate DuctworkRig and Place Unit Property Damage HazardPositioning on Curb Convert to Horizontal and Connect Ductwork when requiredEconomizer Hood Removal and Setup Factory Option Install Outside Air HoodTwo Position Damper Hood Removal and Setup Factory Option Economizer Hood and Two-Position Hood Install Flue HoodNatural Gas Supply Line Pressure Ranges Install Gas PipingEquipment Damage Hazard Completing Installation of Thru-the-Base Option Fire or Explosion Hazard Install External Condensate Trap and LineMake Electrical Connections Field Power SupplyUnits with Factory-Installed Disconnect Units Without Factory-Installed Disconnect Electrical Operation Hazard Power Wiring Connections Convenience OutletsUnit Powered Convenience Outlet Wiring Thermostat Field Control WiringFactory-Option Thru-Base Connections Electrical Connections Units without Thru-Base ConnectionsTypical Low-Voltage Control Connections Unit without Thru-Base Connection KitTo connect the Thermidistat device 33CS2PPRH-01 Humidi-MiZerRControl ConnectionsHumidi-MiZer Space RH Controller To connect the Carrier humidistat HL38MG029OAT RRS Srtn PremierLink Controller PremierLinkt Factory OptionPremierLink Wiring Schematic PremierLink Wiring Schematic with Humidi-MiZerR PremierLink Sensor Usage Supply Air Temperature SAT SensorField Connections EconoMi$er2Thermostat Mode Space Sensor ModeSpace Sensors Configure the unit for Thermostat ModeIndoor Air Quality CO2 sensor Economizer ControlsUnit Performance Hazard To wire the sensorSmoke Detector/Fire Shutdown FSD Filter Status SwitchSupply Fan Status Switch Power Exhaust outputCCN Communication Bus Connecting CCN Bus Color Code RecommendationsRecommended Cables RTU Open Multi-Protocol Control Board RTU Open Control SystemRTU Open System Control Wiring Diagram RTU Open System Control Wiring Diagram with Humidi-MiZerR Type of I/O Connection PIN Name Numbers Dedicated Inputs RTU Open Controller Inputs and OutputsRTU Open T-55 Sensor Connections Space Temperature SPT SensorsRelative Humidity Sensors Space or Duct Mounted Space Relative Humidity Sensor Typical WiringConnecting Discrete Inputs Duct Relative Humidity Sensor Typical WiringGeneral Communication Wiring ProtocolsRTU Open Troubleshooting Local AccessReturn Air Enthalpy Sensor Outdoor Air Enthalpy Control PNO 33CSENTHSWLEDs Differential Enthalpy ControlSensor Module Smoke DetectorsSystem ControllerReturn Air with Economizer See Completing Installation of Return Air SmokeSmoke Detector Locations Supply AirReturn Air Detector Shipping Position Completing Installation of Return Air Smoke SensorBrkr Unit Wire/Fuse or Hacr Breaker Sizing DataPre-Start and Start-Up Adjust Factory-Installed OptionsInstall Accessories EconoMi$er IV Occupancy Switch48TC**16 14SI