Carrier 48TC**16 installation instructions Space Sensors, Configure the unit for Thermostat Mode

Page 27

Space Sensors —

The PremierLink controller is factory-shipped configured for Space Sensor Mode. A Carrier T-55 or T-56 space sensor must be used. T-55 space temperature sensor provides a signal of space temperature to the PremierLink control. T-56 provides same space temperature signal plus it allows for adjustment of space temperature setpoints from the face of the sensor by the occupants.

 

TB3

PL

SEN

1

J6-7

 

TB3

PL

SEN

3

J6-6

Jumper

SET

SET 5 J6-5

Fig. 52 - PremierLink T-56 Sensor

Connect Thermostat —

C10022

1

2

3

4

5

6

RED(+)

 

 

 

 

 

 

WHT(GND)

CCN COM

 

 

 

 

 

 

BLK(-)

 

 

 

 

 

 

 

 

 

 

SEN

 

 

 

 

 

SW1

 

 

 

 

 

 

 

 

 

 

 

BRN (GND)

SENSOR WIRING

 

 

 

 

 

BLU (SPT)

 

C08201

Fig. 49 - T-55 Space Temperature Sensor Wiring

Connect T-55:See Fig. 49 for typical T-55 internal connections. Connect the T-55 SEN terminals to TB3 terminals 1 and 3 (see Fig. 50).

TB3PL

SEN 1 J6-7

SEN 3 J6-6

A7-wire thermostat connection requires a 24-v power source and a common connection. Use the R and C terminals on the CTB’s THERMOSTAT connection strip for these. Connect the thermostat’s Y1, Y2, W1, W2 and G terminals to PremierLink TB3 as shown in Fig. 53.

If the 48TC**16 unit is equipped with factory-installed smoke detector(s), disconnect the factory BLU lead at TB3-6 (Y2) before connecting the thermostat. Identify the BLU lead originating at CTB-DDC-1; disconnect at TB3-6 and tape off. Confirm that the second BLU lead at TB3-6 remains connected to PremierLink J4-8.

SPACECTB

THERMOSTAT THERMOSTAT

R R

TB3PL

G 2 J4-12

Y1 4 J4-10

Y2 6 J4-8

W1 8 J4-6

48TC**16

Fig. 50 - PremierLink T-55 Sensor

C10023

W2 10 J4-4

C

C

CTB

THERMOSTAT

Connect T-56:See Fig. 51 for T-56 internal connections. Install a jumper between SEN and SET terminals as illustrated. Connect T-56 terminals to TB3 terminals 1, 3 and 5 (see Fig. 52).

1

2

3

4

5

6

RED(+)

 

 

 

 

 

 

WHT(GND)

CCN COM

 

 

 

 

 

 

BLK(-)

 

 

 

 

 

 

 

 

 

 

SEN

 

SET

 

 

 

SW1

 

 

 

 

BLK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(T56)

 

 

 

 

 

 

BRN (GND)

SENSOR WIRING

 

 

 

 

 

BLU (SPT)

 

 

 

 

 

 

 

 

JUMPER

 

 

 

 

 

 

 

TERMINALS

 

 

 

 

 

 

 

AS SHOWN

C10283

Fig. 53 - Space Thermostat Connections

If the 48TC**16 unit has an economizer system and free-cooling operation is required, a sensor representing Return Air Temperature must also be connected (field-supplied and installed). This sensor may be a T-55 Space Sensor (see Fig. 49) installed in the space or in the return duct, or it may be sensor PNO 33ZCSENSAT, installed in the return duct. Connect this sensor to TB3-1 and TB3-3 per Fig. 50.

Configure the unit for Thermostat Mode —

Connect to the CCN bus using a CCN service tool and navigate to PremierLink Configuration screen for Operating Mode. Default setting is Sensor Mode (value 1). Change the value to 0 to reconfigure the controller for Thermostat Mode.

Cool Warm

Fig. 51 - T-56 Internal Connections

C08202

When the PremierLink is configured for Thermostat Mode, these functions are not available: Fire Shutdown (FSD), Remote Occupied (RMTOCC), Compressor Safety (CMPSAFE), Supply Fan Status (SFS), and Filter Pressure Switch (FILTER).

27

Image 27
Contents Installation Instructions Personal Injury and Environmental Hazard Unit Operation and Safety HazardFIRE, Explosion Hazard Electrical Shock HazardUnit Dimensional Drawing 16 Size Unit Plan for Unit Location Service Clearance Dimensional DrawingPlan for Sequence of Unit Installation Inspect UnitProvide Unit Support Roof Curb Details Unit Damage Hazard Field Fabricate DuctworkRig and Place Unit Property Damage HazardPositioning on Curb Convert to Horizontal and Connect Ductwork when requiredInstall Outside Air Hood Economizer Hood Removal and Setup Factory OptionTwo Position Damper Hood Removal and Setup Factory Option Economizer Hood and Two-Position Hood Install Flue HoodInstall Gas Piping Natural Gas Supply Line Pressure RangesEquipment Damage Hazard Completing Installation of Thru-the-Base Option Fire or Explosion Hazard Install External Condensate Trap and LineMake Electrical Connections Field Power SupplyUnits with Factory-Installed Disconnect Units Without Factory-Installed DisconnectElectrical Operation Hazard Power Wiring Connections Convenience OutletsUnit Powered Convenience Outlet Wiring Thermostat Field Control WiringFactory-Option Thru-Base Connections Electrical Connections Units without Thru-Base ConnectionsTypical Low-Voltage Control Connections Unit without Thru-Base Connection KitTo connect the Thermidistat device 33CS2PPRH-01 Humidi-MiZerRControl ConnectionsHumidi-MiZer Space RH Controller To connect the Carrier humidistat HL38MG029OAT RRS Srtn PremierLink Controller PremierLinkt Factory OptionPremierLink Wiring Schematic PremierLink Wiring Schematic with Humidi-MiZerR PremierLink Sensor Usage Supply Air Temperature SAT SensorField Connections EconoMi$er2Thermostat Mode Space Sensor ModeSpace Sensors Configure the unit for Thermostat ModeIndoor Air Quality CO2 sensor Economizer ControlsUnit Performance Hazard To wire the sensorSmoke Detector/Fire Shutdown FSD Filter Status SwitchSupply Fan Status Switch Power Exhaust outputConnecting CCN Bus Color Code Recommendations CCN Communication BusRecommended Cables RTU Open Multi-Protocol Control Board RTU Open Control SystemRTU Open System Control Wiring Diagram RTU Open System Control Wiring Diagram with Humidi-MiZerR Type of I/O Connection PIN Name Numbers Dedicated Inputs RTU Open Controller Inputs and OutputsRTU Open T-55 Sensor Connections Space Temperature SPT SensorsRelative Humidity Sensors Space or Duct Mounted Space Relative Humidity Sensor Typical WiringConnecting Discrete Inputs Duct Relative Humidity Sensor Typical WiringGeneral Communication Wiring ProtocolsRTU Open Troubleshooting Local AccessReturn Air Enthalpy Sensor Outdoor Air Enthalpy Control PNO 33CSENTHSWLEDs Differential Enthalpy ControlSensor Module Smoke DetectorsSystem ControllerReturn Air with Economizer See Completing Installation of Return Air SmokeSmoke Detector Locations Supply AirReturn Air Detector Shipping Position Completing Installation of Return Air Smoke SensorBrkr Unit Wire/Fuse or Hacr Breaker Sizing DataPre-Start and Start-Up Adjust Factory-Installed OptionsInstall Accessories EconoMi$er IV Occupancy Switch48TC**16 14SI