Space Sensors —
The PremierLink controller is
| TB3 | PL |
SEN | 1 | |
| TB3 | PL |
SEN | 3 |
Jumper
SET
SET 5
Fig. 52 - PremierLink T-56 Sensor
Connect Thermostat —
C10022
1 | 2 | 3 | 4 | 5 | 6 | RED(+) |
|
|
|
|
|
| WHT(GND) | CCN COM | |
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
|
| SEN |
|
|
|
|
| SW1 |
|
|
|
|
|
|
|
|
|
|
| BRN (GND) | SENSOR WIRING | |
|
|
|
|
| BLU (SPT) |
|
C08201
Fig. 49 - T-55 Space Temperature Sensor Wiring
Connect
TB3PL
SEN 1
SEN 3
A
If the 48TC**16 unit is equipped with
SPACECTB
THERMOSTAT THERMOSTAT
R R
TB3PL
G 2
Y1 4
Y2 6
W1 8
48TC**16
Fig. 50 - PremierLink T-55 Sensor
C10023
W2 10
C | C | CTB |
THERMOSTAT
Connect
1 | 2 | 3 | 4 | 5 | 6 | RED(+) |
|
|
|
|
|
| WHT(GND) | CCN COM | |
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
|
| SEN |
| SET |
|
|
| SW1 |
|
|
|
| BLK |
|
|
|
|
|
|
|
| |
|
|
|
|
|
| (T56) |
|
|
|
|
|
| BRN (GND) | SENSOR WIRING | |
|
|
|
|
| BLU (SPT) |
| |
|
|
|
|
|
|
| JUMPER |
|
|
|
|
|
|
| TERMINALS |
|
|
|
|
|
|
| AS SHOWN |
C10283
Fig. 53 - Space Thermostat Connections
If the 48TC**16 unit has an economizer system and
Configure the unit for Thermostat Mode —
Connect to the CCN bus using a CCN service tool and navigate to PremierLink Configuration screen for Operating Mode. Default setting is Sensor Mode (value 1). Change the value to 0 to reconfigure the controller for Thermostat Mode.
Cool Warm
Fig. 51 - T-56 Internal Connections
C08202
When the PremierLink is configured for Thermostat Mode, these functions are not available: Fire Shutdown (FSD), Remote Occupied (RMTOCC), Compressor Safety (CMPSAFE), Supply Fan Status (SFS), and Filter Pressure Switch (FILTER).
27