Carrier 48TC**16 Space Temperature SPT Sensors, RTU Open T-55 Sensor Connections

Page 36

Space Temperature (SPT) Sensors —

There are two types of SPT sensors available from Carrier, resistive input non-communicating (T55, T56, and T59) and Rnet communicating (SPS, SPPL, SPP, and SPPF) sensors. Each type has a variety of options consisting of: timed override button, set point adjustment, a LCD screen, and communication tie in. Space temperature can

Connect T-59:The T-59 space sensor requires a separate, isolated power supply of 24 VAC. See Fig. 71 for internal connections at the T-59. Connect the SEN terminal (BLU) to RTU Open J20-1. Connect the COM terminal (BRN) to J20-2. Connect the SET terminal (STO or BLK) to J20-3.

48TC**16

be also be written to from a building network or zoning system. However, it is still recommended that return air duct sensor be installed to allow stand-alone operation for back-up. Refer to the configuration section for details on controller configurations associated with space sensors.

Field connections to T-55, T-56 and T-59 are provided as examples.

S 33ZCT55SPT, space temperature sensor with override button (T-55)

S 33ZCT56SPT, space temperature sensor with override button and setpoint adjustment (T-56)

S 33ZCT59SPT, space temperature sensor with LCD (liquid crystal display) screen, override button, and setpoint adjustment (T-59)

BLK (STO)

BRN (COM)

BLU (SPT)

OR SET SEN

OPB COM- PWR+

24 VAC

J20-3

J20-2SENSOR WIRING

J20-1

POWER

WIRING

Use 20 gauge wire to connect the sensor to the controller. The wire is suitable for distances of up to 500 ft. Use a three-conductor shielded cable for the sensor and setpoint adjustment connections. If the setpoint adjustment (slidebar) is not required, then an unshielded, 18 or 20 gauge, two-conductor, twisted pair cable may be used.

Connect T-55:See Fig. 49 for typical T-55 internal connections. Connect the T-55 SEN terminals to RTU Open J20-1 and J20-2. See Fig. 69.

SEN J20-1

SEN J20-2

C08460

Fig. 69 - RTU Open T-55 Sensor Connections

Connect T-56:See Fig. 51 for T-56 internal connections. Install a jumper between SEN and SET terminals as illustrated. Connect T-56 terminals to RTU Open J20-1, J20-2 and J20-3 per Fig. 70.

SEN J20-1

SEN J20-2

Jumper

SET

SET J20-3

C08461

Fig. 70 - RTU Open T-56 Sensor Connections

NOTE: Must use a separate isolated transformer.

C10291

Fig. 71 - Space Temperature Sensor Typical Wiring

(33ZCT59SPT)

Indoor Air Quality (CO2 sensor) —

The indoor air quality sensor accessory monitors space carbon dioxide (CO2) levels. This information is used to monitor IAQ levels. Several types of sensors are available, for wall mounting in the space or in return duct, with and without LCD display, and in combination with space temperature sensors. Sensors use infrared technology to measure the levels of CO2 present in the space air.

The CO2 sensors are all factory set for a range of 0 to 2000 ppm and a linear mA output of 4 to 20. Refer to the instructions supplied with the CO2 sensor for electrical requirements and terminal locations. See Fig. 54 for typical CO2 sensor wiring schematic.

To accurately monitor the quality of the air in the conditioned air space, locate the sensor near a return-air grille (if present) so it senses the concentration of CO2 leaving the space. The sensor should be mounted in a location to avoid direct breath contact.

Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft (0.9 m) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream.

36

Image 36
Contents Installation Instructions Unit Operation and Safety Hazard FIRE, Explosion HazardElectrical Shock Hazard Personal Injury and Environmental HazardUnit Dimensional Drawing 16 Size Unit Service Clearance Dimensional Drawing Plan for Unit LocationPlan for Sequence of Unit Installation Inspect UnitProvide Unit Support Roof Curb Details Field Fabricate Ductwork Rig and Place UnitProperty Damage Hazard Unit Damage HazardConvert to Horizontal and Connect Ductwork when required Positioning on CurbInstall Outside Air Hood Economizer Hood Removal and Setup Factory OptionTwo Position Damper Hood Removal and Setup Factory Option Install Flue Hood Economizer Hood and Two-Position HoodInstall Gas Piping Natural Gas Supply Line Pressure RangesEquipment Damage Hazard Completing Installation of Thru-the-Base Option Install External Condensate Trap and Line Fire or Explosion HazardField Power Supply Make Electrical ConnectionsUnits Without Factory-Installed Disconnect Units with Factory-Installed DisconnectPower Wiring Connections Convenience Outlets Electrical Operation HazardUnit Powered Convenience Outlet Wiring Field Control Wiring Factory-Option Thru-Base Connections Electrical ConnectionsUnits without Thru-Base Connections ThermostatUnit without Thru-Base Connection Kit Typical Low-Voltage Control ConnectionsHumidi-MiZerRControl Connections Humidi-MiZer Space RH ControllerTo connect the Carrier humidistat HL38MG029 To connect the Thermidistat device 33CS2PPRH-01OAT RRS Srtn PremierLinkt Factory Option PremierLink ControllerPremierLink Wiring Schematic PremierLink Wiring Schematic with Humidi-MiZerR Supply Air Temperature SAT Sensor Field ConnectionsEconoMi$er2 PremierLink Sensor UsageSpace Sensor Mode Thermostat ModeConfigure the unit for Thermostat Mode Space SensorsEconomizer Controls Indoor Air Quality CO2 sensorTo wire the sensor Unit Performance HazardFilter Status Switch Supply Fan Status SwitchPower Exhaust output Smoke Detector/Fire Shutdown FSDConnecting CCN Bus Color Code Recommendations CCN Communication BusRecommended Cables RTU Open Control System RTU Open Multi-Protocol Control BoardRTU Open System Control Wiring Diagram RTU Open System Control Wiring Diagram with Humidi-MiZerR RTU Open Controller Inputs and Outputs Type of I/O Connection PIN Name Numbers Dedicated InputsSpace Temperature SPT Sensors RTU Open T-55 Sensor ConnectionsSpace Relative Humidity Sensor Typical Wiring Relative Humidity Sensors Space or Duct MountedDuct Relative Humidity Sensor Typical Wiring Connecting Discrete InputsCommunication Wiring Protocols GeneralLocal Access RTU Open TroubleshootingOutdoor Air Enthalpy Control PNO 33CSENTHSW LEDsDifferential Enthalpy Control Return Air Enthalpy SensorSmoke Detectors SystemController Sensor ModuleSee Completing Installation of Return Air Smoke Smoke Detector LocationsSupply Air Return Air with EconomizerCompleting Installation of Return Air Smoke Sensor Return Air Detector Shipping PositionUnit Wire/Fuse or Hacr Breaker Sizing Data BrkrAdjust Factory-Installed Options Install AccessoriesEconoMi$er IV Occupancy Switch Pre-Start and Start-Up48TC**16 14SI

48TC**16 specifications

The Carrier 48TC**16 is a high-efficiency rooftop packaged unit, designed for commercial heating and cooling applications. This model exemplifies Carrier's commitment to delivering reliable and innovative solutions to the HVAC industry. With cutting-edge technology and robust performance characteristics, the 48TC**16 is ideally suited for a variety of building types.

One of the main features of the Carrier 48TC**16 is its impressive energy efficiency. The unit achieves high SEER (Seasonal Energy Efficiency Ratio) ratings, which translates to lower energy bills and reduced environmental impact. The unit is equipped with a scroll compressor, known for its quiet operation and reliability, ensuring a comfortable indoor environment without disruptive noise.

The 48TC**16 utilizes advanced microprocessor controls that enhance system performance by enabling precise temperature control and various operational modes. This allows users to optimize the system's performance based on specific heating and cooling needs. Additionally, the unit includes enhanced diagnostics, allowing for faster troubleshooting and easier maintenance, thus minimizing downtime and repair costs.

Another notable characteristic of the 48TC**16 is its robust construction. Built to withstand harsh weather conditions, the unit features a galvanized steel cabinet coated with a corrosion-resistant finish, ensuring longevity and durability. It also comes equipped with a variety of factory-installed options, such as economizers and filtration systems, which can further enhance its performance and flexibility.

The Carrier 48TC**16 is designed with sustainability in mind, using environmentally friendly refrigerants. The unit supports the latest refrigerant regulations, helping to reduce the overall carbon footprint of the building it serves.

Installation and service are simplified by the unit's modular design, which allows for easy access to all major components. This design not only streamlines maintenance procedures but also facilitates quick installation, making it an ideal choice for contractors and facility managers alike.

In summary, the Carrier 48TC**16 rooftop packaged unit combines high energy efficiency, advanced controls, robust construction, and eco-friendly features, making it a top choice for commercial heating and cooling needs. Its user-friendly design and reliability ensure optimal performance and comfort for various applications, underscoring Carrier's reputation as a leader in the HVAC industry. Whether for new construction or retrofitting, the 48TC**16 meets the demands of modern buildings while adhering to sustainability practices.