Carrier 48TC**16 installation instructions Relative Humidity Sensors Space or Duct Mounted

Page 37

Wiring the Indoor Air Quality Sensor: For each sensor, use two 2-conductor 18 AWG (American Wire Gage) twisted-pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the control board terminals.

To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 54. Connect the 4-20 mA terminal to RTU Open J4-2 and connect the SIG COM terminal to RTU Open J4-3. See Fig. 72.

IAQ Sensor

4-20mA J4-2

SIG COM J4-3 24 VAC

C10738

Fig. 72 - RTU Open / Indoor CO2 Sensor

(33ZCSENCO2) Connections

Outdoor Air Quality Sensor

(PNO 33ZCSENCO2 plus weatherproof enclosure) —

The outdoor air CO2 sensor is designed to monitor carbon dioxide (CO2) levels in the outside ventilation air and interface with the ventilation damper in an HVAC system. The OAQ sensor is packaged with an outdoor cover. See Fig. 56. The outdoor air CO2 sensor must be located in the economizer outside air hood.

Wiring the Outdoor Air CO2 Sensor: A dedicated power supply is required for this sensor. A two-wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2.

To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the OAQ sensor. See Fig. 54. Connect the 4 to 20 mA terminal to RTU Open J4-5. Connect the SIG COM terminal to RTU Open J4-6. See Fig. 73.

OAQ Sensor/RH Sensor

4-20mA J4-5

SIG COM J4-6 24 VAC

C10739

Fig. 73 - RTU Open / Outdoor CO2 Sensor

(33ZCSENCO2) Connections

Space Relative Humidity Sensor or Humidistat —

 

Humidi-MiZerRControl Wiring: In units equipped

 

with the Humidi-MiZer option there are two pink (PNK)

 

wires loose in the control box used to control the

 

dehumidification function of the unit. These pink wires

 

are meant to be tied to a space humidistat or thermidistat

 

on an electromechanical unit. On RTU Open equipped

 

units these pink wires must be connected to J11-7 & 8 to

 

allow the Open board to operate the dehumidification

 

function for the unit. Disconnect the J11 Phoenix style

 

connector from the board and use the plug screws to

 

secure the pink wires in pins 7 and 8, reconnect the plug

 

to the board at J11.

 

Relative Humidity Sensors (Space or Duct Mounted):

 

The accessory space humidity sensor (33ZCSENSRH-01)

 

 

or duct humidity sensor (33ZCSENDRH-01) is used to

 

measure the relative humidity of air within the space or

48TC**16

return air duct. The RH reading is used to control the

 

Humidi-MiZer option of the rooftop unit. For wiring

 

distances up to 500 ft (152 m), use a 3-conductor, 18 or

 

20 AWG shielded cable. The shield must be removed

 

from the sensor end of the cable and grounded at the unit

 

end. The current loop power for sensor is provided by the

 

RTU Open controller as 24vdc. Refer to the instructions

 

supplied with the RH sensor for the electrical

 

requirements and terminal locations. RTU Open

 

configurations must be changed after adding an RH

 

sensor. See Fig. 74 and 75 for typical RH sensor wiring.

 

S J4-1 or J4-4 = 24vdc loop power

 

S J4-2 or J4-5 = 4-20mA signal input

 

NOTE: The factory default for dehumidification control

 

is normally open humidistat.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MOUNTING

HOLES

 

WIRING

Io Vin Gnd Vo

OPENING

SW2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

5

4

3

2

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vin -

J4-1 or J4-4

24Vdc

Io -

J4-2 or J4-5

-20mA output

C11087

Fig. 74 - Space Relative Humidity Sensor Typical Wiring

37

Image 37
Contents Installation Instructions FIRE, Explosion Hazard Unit Operation and Safety HazardElectrical Shock Hazard Personal Injury and Environmental HazardUnit Dimensional Drawing 16 Size Unit Plan for Unit Location Service Clearance Dimensional DrawingInspect Unit Plan for Sequence of Unit InstallationProvide Unit Support Roof Curb Details Rig and Place Unit Field Fabricate DuctworkProperty Damage Hazard Unit Damage HazardPositioning on Curb Convert to Horizontal and Connect Ductwork when requiredEconomizer Hood Removal and Setup Factory Option Install Outside Air HoodTwo Position Damper Hood Removal and Setup Factory Option Economizer Hood and Two-Position Hood Install Flue HoodNatural Gas Supply Line Pressure Ranges Install Gas PipingEquipment Damage Hazard Completing Installation of Thru-the-Base Option Fire or Explosion Hazard Install External Condensate Trap and LineMake Electrical Connections Field Power SupplyUnits with Factory-Installed Disconnect Units Without Factory-Installed DisconnectElectrical Operation Hazard Power Wiring Connections Convenience OutletsUnit Powered Convenience Outlet Wiring Factory-Option Thru-Base Connections Electrical Connections Field Control WiringUnits without Thru-Base Connections ThermostatTypical Low-Voltage Control Connections Unit without Thru-Base Connection KitHumidi-MiZer Space RH Controller Humidi-MiZerRControl ConnectionsTo connect the Carrier humidistat HL38MG029 To connect the Thermidistat device 33CS2PPRH-01OAT RRS Srtn PremierLink Controller PremierLinkt Factory OptionPremierLink Wiring Schematic PremierLink Wiring Schematic with Humidi-MiZerR Field Connections Supply Air Temperature SAT SensorEconoMi$er2 PremierLink Sensor UsageThermostat Mode Space Sensor ModeSpace Sensors Configure the unit for Thermostat ModeIndoor Air Quality CO2 sensor Economizer ControlsUnit Performance Hazard To wire the sensorSupply Fan Status Switch Filter Status SwitchPower Exhaust output Smoke Detector/Fire Shutdown FSDCCN Communication Bus Connecting CCN Bus Color Code RecommendationsRecommended Cables RTU Open Multi-Protocol Control Board RTU Open Control SystemRTU Open System Control Wiring Diagram RTU Open System Control Wiring Diagram with Humidi-MiZerR Type of I/O Connection PIN Name Numbers Dedicated Inputs RTU Open Controller Inputs and OutputsRTU Open T-55 Sensor Connections Space Temperature SPT SensorsRelative Humidity Sensors Space or Duct Mounted Space Relative Humidity Sensor Typical WiringConnecting Discrete Inputs Duct Relative Humidity Sensor Typical WiringGeneral Communication Wiring ProtocolsRTU Open Troubleshooting Local AccessLEDs Outdoor Air Enthalpy Control PNO 33CSENTHSWDifferential Enthalpy Control Return Air Enthalpy SensorSystem Smoke DetectorsController Sensor ModuleSmoke Detector Locations See Completing Installation of Return Air SmokeSupply Air Return Air with EconomizerReturn Air Detector Shipping Position Completing Installation of Return Air Smoke SensorBrkr Unit Wire/Fuse or Hacr Breaker Sizing DataInstall Accessories Adjust Factory-Installed OptionsEconoMi$er IV Occupancy Switch Pre-Start and Start-Up48TC**16 14SI

48TC**16 specifications

The Carrier 48TC**16 is a high-efficiency rooftop packaged unit, designed for commercial heating and cooling applications. This model exemplifies Carrier's commitment to delivering reliable and innovative solutions to the HVAC industry. With cutting-edge technology and robust performance characteristics, the 48TC**16 is ideally suited for a variety of building types.

One of the main features of the Carrier 48TC**16 is its impressive energy efficiency. The unit achieves high SEER (Seasonal Energy Efficiency Ratio) ratings, which translates to lower energy bills and reduced environmental impact. The unit is equipped with a scroll compressor, known for its quiet operation and reliability, ensuring a comfortable indoor environment without disruptive noise.

The 48TC**16 utilizes advanced microprocessor controls that enhance system performance by enabling precise temperature control and various operational modes. This allows users to optimize the system's performance based on specific heating and cooling needs. Additionally, the unit includes enhanced diagnostics, allowing for faster troubleshooting and easier maintenance, thus minimizing downtime and repair costs.

Another notable characteristic of the 48TC**16 is its robust construction. Built to withstand harsh weather conditions, the unit features a galvanized steel cabinet coated with a corrosion-resistant finish, ensuring longevity and durability. It also comes equipped with a variety of factory-installed options, such as economizers and filtration systems, which can further enhance its performance and flexibility.

The Carrier 48TC**16 is designed with sustainability in mind, using environmentally friendly refrigerants. The unit supports the latest refrigerant regulations, helping to reduce the overall carbon footprint of the building it serves.

Installation and service are simplified by the unit's modular design, which allows for easy access to all major components. This design not only streamlines maintenance procedures but also facilitates quick installation, making it an ideal choice for contractors and facility managers alike.

In summary, the Carrier 48TC**16 rooftop packaged unit combines high energy efficiency, advanced controls, robust construction, and eco-friendly features, making it a top choice for commercial heating and cooling needs. Its user-friendly design and reliability ensure optimal performance and comfort for various applications, underscoring Carrier's reputation as a leader in the HVAC industry. Whether for new construction or retrofitting, the 48TC**16 meets the demands of modern buildings while adhering to sustainability practices.