Carrier 48TC**16 installation instructions RTU Open Controller Inputs and Outputs

Page 35

Table 8 – RTU Open Controller Inputs and Outputs

 

 

POINT NAME

BACnet OBJECT

 

TYPE OF I/O

CONNECTION PIN

 

 

NAME

 

NUMBER(S)

 

 

 

 

 

 

 

 

DEDICATED INPUTS

 

Space Temp / Zone Temp

zone_temp

 

AI (10K Thermistor)

J20--- 1, 2

Supply Air Temperature

sa_temp

 

AI (10K Thermistor)

J2--- 1, 2

Outdoor Air Temperature

oa_temp

 

AI (10K Thermistor)

J2--- 3, 4

Space Temperature Offset Pot

stpt_adj_offset

 

AI (100K Potentiometer)

J20--- 3

Safety Chain Feedback

safety_status

 

DI (24 VAC)

J1--- 9

Compressor Safety Status

comp_status

 

DI (24 VAC)

J1--- 2

Fire Shutdown Status

firedown_status

 

DI (24 VAC)

J1--- 10

Enthalpy Status

enthalpy_status

 

DI (24 VAC)

J2--- 6

Humidistat Input Status

humstat_status

 

DI (24 VAC)

J5--- 7

 

 

 

CONFIGURABLE INPUTS

 

Indoor Air CO2

iaq

 

AI (4--- 20 ma)

 

Outdoor Air CO2

oaq

 

AI (4--- 20 ma)

J4--- 2 or J4--- 5

Space Relative Humidity

space_rh

 

AI (4--- 20 ma)

 

Supply Fan Status*

sfan_status

 

DI (24 VAC)

 

Filter Status*

filter_status

 

DI (24 VAC)

J5--- 1 or J5---3 or

Door Contact Input*

door_contact_status

 

DI (24 VAC)

J5 5 or J5--- 7

Occupancy Contact*

occ_contact_status

 

DI (24 VAC)

 

 

 

 

OUTPUTS

 

 

Economizer Output

econ_output

 

AO (4--- 20ma)

J2--- 5

Supply Fan Relay State

sfan

 

DO Relay (24VAC , 1A)

J1--- 4

Compressor 1 Relay State

comp_1

 

DO Relay (24VAC , 1A)

J1--- 8

Compressor 2 Relay State

comp_2

 

DO Relay (24VAC , 1A)

J1--- 7

Heat Stage 1 Relay State

heat_1

 

DO Relay (24VAC , 1A)

J1--- 6

Heat Stage 2 Relay State

heat_2

 

DO Relay (24VAC , 1A)

J1--- 5

Power Exhaust Relay State

pexh

 

DO Relay (24VAC , 1A)

J11--- 3

Dehumidification Relay State

dehum

 

DO Relay (24VAC, 1A)

J11--- 7, 8

LEGEND

 

 

 

 

 

AI

---

Analog Input

 

 

 

 

AO

---

Analog Output

 

 

 

 

DI

---

Discrete Input

 

 

 

 

DO

---

Discrete Output

 

 

 

 

*These inputs (if installed) take the place of the default input on the specific channel according to schematic. Parallel pins J5---1 = J2---6, J5---3 = J1---10, J5---5 = J1---2 are used for field---installation.

48TC**16

The RTU Open controller requires the use of a Carrier space sensor. A standard thermostat cannot be used with the RTU Open system.

Supply Air Temperature (SAT) Sensor —

On FIOP-equipped 48TC**16 unit, the unit is supplied with

asupply-air temperature (SAT) sensor (33ZCSENSAT). This sensor is a tubular probe type, approx 6-inches (12.7 mm) in length. It is a nominal 10-k ohm thermistor.

The SAT is factory-wired. The SAT probe is wire-tied to the supply-air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-position the sensor in the flange of the supply-air opening or in the supply air duct (as required by local codes). Drill or punch a 1/2-in. hole in the flange or duct. Use two field-supplied, self-drilling screws to secure the sensor probe in a horizontal orientation. See Fig. 48.

Outdoor Air Temperature (OAT) Sensor —

The OAT is factory-mounted in the EconoMi$er2 (FIOP or accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring.

EconoMi$er2 —

The RTU Open control is used with EconoMi$er2 (option or accessory) for outdoor air management. The damper position is controlled directly by the RTU Open control; EconoMi$er2 has no internal logic device.

Outdoor air management functions can be enhanced with field-installation of these accessory control devices:

Enthalpy control (outdoor air or differential sensors) Space CO2 sensor

Outdoor air CO2 sensor

Field Connections

Field connections for accessory sensors and input devices are made the RTU Open, at plugs J1, J2, J4, J5, J11 and J20. All field control wiring that connects to the RTU Open must be routed as shown in Fig. 39. This routing provides the UL required clearance between high- and low-voltage wiring. Connect to the wires to the removable Phoenix connectors and then reconnect the connectors to the board.

35

Image 35
Contents Installation Instructions Personal Injury and Environmental Hazard Unit Operation and Safety HazardFIRE, Explosion Hazard Electrical Shock HazardUnit Dimensional Drawing 16 Size Unit Plan for Unit Location Service Clearance Dimensional DrawingProvide Unit Support Plan for Sequence of Unit InstallationInspect Unit Roof Curb Details Unit Damage Hazard Field Fabricate DuctworkRig and Place Unit Property Damage HazardPositioning on Curb Convert to Horizontal and Connect Ductwork when requiredTwo Position Damper Hood Removal and Setup Factory Option Install Outside Air HoodEconomizer Hood Removal and Setup Factory Option Economizer Hood and Two-Position Hood Install Flue HoodEquipment Damage Hazard Install Gas PipingNatural Gas Supply Line Pressure Ranges Completing Installation of Thru-the-Base Option Fire or Explosion Hazard Install External Condensate Trap and LineMake Electrical Connections Field Power SupplyUnits with Factory-Installed Disconnect Units Without Factory-Installed DisconnectElectrical Operation Hazard Power Wiring Connections Convenience OutletsUnit Powered Convenience Outlet Wiring Thermostat Field Control WiringFactory-Option Thru-Base Connections Electrical Connections Units without Thru-Base ConnectionsTypical Low-Voltage Control Connections Unit without Thru-Base Connection KitTo connect the Thermidistat device 33CS2PPRH-01 Humidi-MiZerRControl ConnectionsHumidi-MiZer Space RH Controller To connect the Carrier humidistat HL38MG029OAT RRS Srtn PremierLink Controller PremierLinkt Factory OptionPremierLink Wiring Schematic PremierLink Wiring Schematic with Humidi-MiZerR PremierLink Sensor Usage Supply Air Temperature SAT SensorField Connections EconoMi$er2Thermostat Mode Space Sensor ModeSpace Sensors Configure the unit for Thermostat ModeIndoor Air Quality CO2 sensor Economizer ControlsUnit Performance Hazard To wire the sensorSmoke Detector/Fire Shutdown FSD Filter Status SwitchSupply Fan Status Switch Power Exhaust outputRecommended Cables Connecting CCN Bus Color Code RecommendationsCCN Communication Bus RTU Open Multi-Protocol Control Board RTU Open Control SystemRTU Open System Control Wiring Diagram RTU Open System Control Wiring Diagram with Humidi-MiZerR Type of I/O Connection PIN Name Numbers Dedicated Inputs RTU Open Controller Inputs and OutputsRTU Open T-55 Sensor Connections Space Temperature SPT SensorsRelative Humidity Sensors Space or Duct Mounted Space Relative Humidity Sensor Typical WiringConnecting Discrete Inputs Duct Relative Humidity Sensor Typical WiringGeneral Communication Wiring ProtocolsRTU Open Troubleshooting Local AccessReturn Air Enthalpy Sensor Outdoor Air Enthalpy Control PNO 33CSENTHSWLEDs Differential Enthalpy ControlSensor Module Smoke DetectorsSystem ControllerReturn Air with Economizer See Completing Installation of Return Air SmokeSmoke Detector Locations Supply AirReturn Air Detector Shipping Position Completing Installation of Return Air Smoke SensorBrkr Unit Wire/Fuse or Hacr Breaker Sizing DataPre-Start and Start-Up Adjust Factory-Installed OptionsInstall Accessories EconoMi$er IV Occupancy Switch48TC**16 14SI

48TC**16 specifications

The Carrier 48TC**16 is a high-efficiency rooftop packaged unit, designed for commercial heating and cooling applications. This model exemplifies Carrier's commitment to delivering reliable and innovative solutions to the HVAC industry. With cutting-edge technology and robust performance characteristics, the 48TC**16 is ideally suited for a variety of building types.

One of the main features of the Carrier 48TC**16 is its impressive energy efficiency. The unit achieves high SEER (Seasonal Energy Efficiency Ratio) ratings, which translates to lower energy bills and reduced environmental impact. The unit is equipped with a scroll compressor, known for its quiet operation and reliability, ensuring a comfortable indoor environment without disruptive noise.

The 48TC**16 utilizes advanced microprocessor controls that enhance system performance by enabling precise temperature control and various operational modes. This allows users to optimize the system's performance based on specific heating and cooling needs. Additionally, the unit includes enhanced diagnostics, allowing for faster troubleshooting and easier maintenance, thus minimizing downtime and repair costs.

Another notable characteristic of the 48TC**16 is its robust construction. Built to withstand harsh weather conditions, the unit features a galvanized steel cabinet coated with a corrosion-resistant finish, ensuring longevity and durability. It also comes equipped with a variety of factory-installed options, such as economizers and filtration systems, which can further enhance its performance and flexibility.

The Carrier 48TC**16 is designed with sustainability in mind, using environmentally friendly refrigerants. The unit supports the latest refrigerant regulations, helping to reduce the overall carbon footprint of the building it serves.

Installation and service are simplified by the unit's modular design, which allows for easy access to all major components. This design not only streamlines maintenance procedures but also facilitates quick installation, making it an ideal choice for contractors and facility managers alike.

In summary, the Carrier 48TC**16 rooftop packaged unit combines high energy efficiency, advanced controls, robust construction, and eco-friendly features, making it a top choice for commercial heating and cooling needs. Its user-friendly design and reliability ensure optimal performance and comfort for various applications, underscoring Carrier's reputation as a leader in the HVAC industry. Whether for new construction or retrofitting, the 48TC**16 meets the demands of modern buildings while adhering to sustainability practices.