Carrier 48TC**16 Duct Relative Humidity Sensor Typical Wiring, Connecting Discrete Inputs

Page 38

J4-1 or J4-4 + 24 VDC Supply Voltage

 

 

J4-2 or J4-5 (-) 4 to 20 mA Current Loop Output

 

 

to RTU-OPEN

 

 

 

 

SPAN

 

 

ZERO

4-20 VAC GND 0-5V

mA

or

or

 

VDC

0-10V

Relative Humidity Sensor (Polarized Male Connector)

48TC**16

C10839

Fig. 75 - Duct Relative Humidity Sensor Typical Wiring

Humidistat: The accessory humidistat provides the RTU Open insight to the relative humidity in the space. The humidistat reads the RH level in the space and compares it to its setpoint to operate a dry contact. The humidistat is a dedicated input on the configurable input 9 and tells the RTU Open when the RH level is HIGH or LOW. The normal condition for humidity is LOW. A normally open humidistat is the factory default control for the Humidi-MiZerRoption.

To wire in the field:

SJ5-8 = 24 VAC source for dry contact S J5-7 = Signal input

Smoke Detector/Fire Shutdown (FSD) —

On 48TC**16 units equipped with factory-installed Smoke Detector(s), the smoke detector controller implements the unit shutdown through its NC contact set connected to the unit’s CTB input. The FSD function is initiated via the smoke detector’s Alarm NO contact set. The RTU Open controller communicates the smoke detector’s tripped status to the BAS building control. See Fig. 67, the RTU Open System Control Wiring Diagram.

The Fire Shutdown Switch configuration, MENUConfigInputsinput 5, identifies the normally open status of this input when there is no fire alarm.

Connecting Discrete Inputs —

Filter Status: The filter status accessory is a field-installed accessory. This accessory detects plugged filters. When installing this accessory, the unit must be configured for filter status by setting MENUConfigInputsinput 3, 5, 8, or 9 to Filter Status and normally open (N/O) or normally closed (N/C). Input 8 or 9 is recommended for easy of installation. Refer to Fig. 65 and Fig. 67 or Fig. 68 for wire terminations at J5.

Fan Status: The fan status accessory is a field-installed accessory. This accessory detects when the indoor fan is blowing air. When installing this accessory, the unit must be configured for fan status by setting MENUConfigInputsinput 3, 5, 8, or 9 to Fan Status and normally open (N/O) or normally closed (N/C). Input 8 or 9 is recommended for easy of installation. Refer to Fig. 65 and Fig. 67 or Fig. 68 for wire terminations at J5.

Remote Occupancy: The remote occupancy accessory is

afield-installed accessory. This accessory overrides the unoccupied mode and puts the unit in occupied mode. When installing this accessory, the unit must be configured for remote occupancy by setting MENUConfigInputsinput 3, 5, 8, or 9 to Remote Occupancy and normally open (N/O) or normally closed (N/C).

Also set MENUSchedulesoccupancy source to DI on/off. Input 8 or 9 is recommended for easy of installation. Refer to Fig. 65 and Table 8 for wire terminations at J5.

Power Exhaust (output): The relay used by the RTU Open board to control power exhaust is a dry contact which means it does not have 24vac. This 24vac must be connected to the relay to allow it to operate the power exhaust relay in the PE accessory. A 24vac source must be provided to J11-2 on the RTU Open control board. This can be provided by the unit’s transformer from various sources. The “R” terminal on the unit’s low voltage terminal board (LVTB) is a logical source. Refer to Fig. 65 and Fig. 67 or Fig. 68 for wire terminations at J11.

38

Image 38
Contents Installation Instructions Electrical Shock Hazard Unit Operation and Safety HazardFIRE, Explosion Hazard Personal Injury and Environmental HazardUnit Dimensional Drawing 16 Size Unit Service Clearance Dimensional Drawing Plan for Unit LocationProvide Unit Support Plan for Sequence of Unit InstallationInspect Unit Roof Curb Details Property Damage Hazard Field Fabricate DuctworkRig and Place Unit Unit Damage HazardConvert to Horizontal and Connect Ductwork when required Positioning on CurbTwo Position Damper Hood Removal and Setup Factory Option Install Outside Air HoodEconomizer Hood Removal and Setup Factory Option Install Flue Hood Economizer Hood and Two-Position HoodEquipment Damage Hazard Install Gas PipingNatural Gas Supply Line Pressure Ranges Completing Installation of Thru-the-Base Option Install External Condensate Trap and Line Fire or Explosion HazardField Power Supply Make Electrical ConnectionsUnits Without Factory-Installed Disconnect Units with Factory-Installed DisconnectPower Wiring Connections Convenience Outlets Electrical Operation HazardUnit Powered Convenience Outlet Wiring Units without Thru-Base Connections Field Control WiringFactory-Option Thru-Base Connections Electrical Connections ThermostatUnit without Thru-Base Connection Kit Typical Low-Voltage Control ConnectionsTo connect the Carrier humidistat HL38MG029 Humidi-MiZerRControl ConnectionsHumidi-MiZer Space RH Controller To connect the Thermidistat device 33CS2PPRH-01OAT RRS Srtn PremierLinkt Factory Option PremierLink ControllerPremierLink Wiring Schematic PremierLink Wiring Schematic with Humidi-MiZerR EconoMi$er2 Supply Air Temperature SAT SensorField Connections PremierLink Sensor UsageSpace Sensor Mode Thermostat ModeConfigure the unit for Thermostat Mode Space SensorsEconomizer Controls Indoor Air Quality CO2 sensorTo wire the sensor Unit Performance HazardPower Exhaust output Filter Status SwitchSupply Fan Status Switch Smoke Detector/Fire Shutdown FSDRecommended Cables Connecting CCN Bus Color Code RecommendationsCCN Communication Bus RTU Open Control System RTU Open Multi-Protocol Control BoardRTU Open System Control Wiring Diagram RTU Open System Control Wiring Diagram with Humidi-MiZerR RTU Open Controller Inputs and Outputs Type of I/O Connection PIN Name Numbers Dedicated InputsSpace Temperature SPT Sensors RTU Open T-55 Sensor ConnectionsSpace Relative Humidity Sensor Typical Wiring Relative Humidity Sensors Space or Duct MountedDuct Relative Humidity Sensor Typical Wiring Connecting Discrete InputsCommunication Wiring Protocols GeneralLocal Access RTU Open TroubleshootingDifferential Enthalpy Control Outdoor Air Enthalpy Control PNO 33CSENTHSWLEDs Return Air Enthalpy SensorController Smoke DetectorsSystem Sensor ModuleSupply Air See Completing Installation of Return Air SmokeSmoke Detector Locations Return Air with EconomizerCompleting Installation of Return Air Smoke Sensor Return Air Detector Shipping PositionUnit Wire/Fuse or Hacr Breaker Sizing Data BrkrEconoMi$er IV Occupancy Switch Adjust Factory-Installed OptionsInstall Accessories Pre-Start and Start-Up48TC**16 14SI

48TC**16 specifications

The Carrier 48TC**16 is a high-efficiency rooftop packaged unit, designed for commercial heating and cooling applications. This model exemplifies Carrier's commitment to delivering reliable and innovative solutions to the HVAC industry. With cutting-edge technology and robust performance characteristics, the 48TC**16 is ideally suited for a variety of building types.

One of the main features of the Carrier 48TC**16 is its impressive energy efficiency. The unit achieves high SEER (Seasonal Energy Efficiency Ratio) ratings, which translates to lower energy bills and reduced environmental impact. The unit is equipped with a scroll compressor, known for its quiet operation and reliability, ensuring a comfortable indoor environment without disruptive noise.

The 48TC**16 utilizes advanced microprocessor controls that enhance system performance by enabling precise temperature control and various operational modes. This allows users to optimize the system's performance based on specific heating and cooling needs. Additionally, the unit includes enhanced diagnostics, allowing for faster troubleshooting and easier maintenance, thus minimizing downtime and repair costs.

Another notable characteristic of the 48TC**16 is its robust construction. Built to withstand harsh weather conditions, the unit features a galvanized steel cabinet coated with a corrosion-resistant finish, ensuring longevity and durability. It also comes equipped with a variety of factory-installed options, such as economizers and filtration systems, which can further enhance its performance and flexibility.

The Carrier 48TC**16 is designed with sustainability in mind, using environmentally friendly refrigerants. The unit supports the latest refrigerant regulations, helping to reduce the overall carbon footprint of the building it serves.

Installation and service are simplified by the unit's modular design, which allows for easy access to all major components. This design not only streamlines maintenance procedures but also facilitates quick installation, making it an ideal choice for contractors and facility managers alike.

In summary, the Carrier 48TC**16 rooftop packaged unit combines high energy efficiency, advanced controls, robust construction, and eco-friendly features, making it a top choice for commercial heating and cooling needs. Its user-friendly design and reliability ensure optimal performance and comfort for various applications, underscoring Carrier's reputation as a leader in the HVAC industry. Whether for new construction or retrofitting, the 48TC**16 meets the demands of modern buildings while adhering to sustainability practices.