Carrier 30RA/RH Description of the configuration menu General, Password, Test Fault Description

Page 22

The table below describes the faults that can be displayed during the automatic test.

TEST FAULT

DESCRIPTION

 

 

1

Outdoor air thermistor outside range

2

Outdoor air value read not validated by operator

 

 

3

Low pressure transducer, circuit A, outside range

4

High pressure transducer, circuit A, outside range

5

Low pressure transducer, circuit B, outside range

6

High pressure transducer, circuit B, outside range

 

 

7

Defrost thermistor, circuit A, outside range

8

Defrost thermistor, circuit B, outside range

 

 

9

Water flow switch not open

 

 

10

Primary pump not started or water flow switch not

 

closed

11, 12, 13; 14, 15

Water entering temperature sensor outside range

16, 17, 18, 19, 20

Water leaving temperature sensor outside range

21

Temperature difference between entering and leaving

 

water sensors too high

 

 

22, 23; 24, 25, 26

Water system leaving temperature sensor outside

 

range

 

 

27

Temperature difference between the system entering

 

and leaving water sensors too high

 

 

28

Water flow switch not closed or primary pump not

 

stopped

 

 

29

Secondary pump not started or water flow switch not

 

closed

 

 

30

Water flow switch not closed or secondary pump not

 

stopped

 

 

31

Command fault; compressor A1

32

Command fault; compressor A2

33

Command fault; compressor A3

34

Command fault, 4-way reversing valve, circuit A

 

 

35

Command fault; compressor B1

36

Command fault; compressor B2

37

Command fault; compressor B3

 

 

38

Command fault, 4-way reversing valve, circuit B

 

 

39

Low-speed test, fan A1 not validated by the operator

40

High-speed test, fan A1 not validated by the operator

41

Low-speed test, fan B1 not validated by the operator

42

High-speed test, fan B1 not validated by the operator

43

Test fan A2 not validated by the operator

44

Test fan B2 not validated by the operator

45

Water heat exchanger heater and air heat exchanger

 

condensate heater test, circuit A not validated by the

46

operator

 

Air heat exchanger condensate heater, circuit B, not

 

validated by the operator

 

 

47

Boiler activation test not validated by the operator

 

 

48

Electric heating stage 1 activation test not validated

 

by the operator

49

Electric heating stage 2 activation test not validated

 

by the operator

50

Electric heating stage 3 activation test not validated

 

by the operator

51

Electric heating stage 4 activation test not validated

 

by the operator

 

 

52

Alarm relay output activation test, circuit A not

 

validated by the operator

53

Alarm relay output activation test, circuit B not

 

validated by the operator

 

 

4.3.11- Description of the configuration menu

4.3.11.1- General

This menu can be used to display and modify all configura- tions: Factory, Service and User. Only the User Configuration can be modified by the end-user. The Factory, Service and master/ slave configurations are not described in this document. A configuration can only be modified if the unit is fully stopped (LOFF).

The menus User 1 [USEr 1] and User 2 [USEr 2] are pass- word-protected. The other menus are directly accessible, except if item 11 of the User 2 menu (password for all con- figurations) has been validated.

4.3.11.2 - Password

A password must be entered in order to access the test function or to modify a configuration. It is automatically requested, if necessary: 'EntEr PASS' is displayed on the 4-digit display and the configuration menu LED flashes, indicating that the modification mode is active. Press the arrow keys until the value '11' is displayed on the 4-digit display. Press Enter to validate this. The configuration menu LED stops flashing. If the password is correct, 'Good' is displayed. If the password is incorrect, 'PASS incorrEct' is displayed. The User password has a default value of 11.

This value can be modified through the Service configuration. The password can be entered if the unit is fully stopped, otherwise 'ACCES dEniEd' (access denied) will be displayed on the 4-digit display. The controller automatically deactivates the password after 5 minutes without activity (i.e. no buttons pressed) or after powering up.

22

Image 22
Contents Operation and maintenance instructions 30RA/RH B 30RY/RYH B PRO-DIALOG ControlTable of Contents Safety Considerations PRO-DIALOG Control Operation Abbreviations used GeneralAvoid electrocution Following abbreviations are used frequentlySensors Electrical supply to boardsLight emitting diodes on boards Pressure sensorsControls Connections at the users terminal blockBase DUAL-CIRCUIT UnitsNRCP-BASE CCN Volt-free contact on/off/cooling/heating with multiplexing OFFMain Interface Button Name Description Local interface general featuresMain interface Not available on the PRO-DIALOG Junior interfaceDescription Stopping the unit in local modeUnit start/stop control Starting unit and selecting an operating typeSelecting a menu Modifying the value of a parameter/access to a sub- menuMenus Selecting a menu itemExpand display Menu Menu tree structure Active alarm code Historic alarm codeActive alarm code Historic alarm SUB-MENUDescription of the Information menu Information Menu Format Units DescriptionInformation Menu Format Units DescriptionPressures Menu Format Units Comments Temperatures Menu Format Units CommentsDescription of the Setpoints menu Setpoints Menu Format Units Range CommentsReset Thresholds in Cooling or Heating Mode Leaving Water Temperature Control Setpoint CEntering Water Temperature Control Description of the Inputs menuMenu description Description of the Outputs/Tests menu GeneralOutputs Status & Tests Menu 2 Format Units Description Outputs Status & Tests Menu 2 Manual testsAutomatic tests Additional heating stage statusTest Number Description Confirmation Password Description of the configuration menu GeneralTest Fault Description SUB-MENU Period Configuration SUB-MENU Holiday ConfigurationDescription of the User 1 Configuration sub-menu User 1 Configuration SUB-MENU Format Units Default CommentsDescription of Date and Time configuration sub Menu Description of the User 2 Configuration sub-menuDate & Time Configuration SUB-MENU Format Comments Typical timer program Description of the Holidays sub-menusDescription of the Broadcast sub-menu Broadcast Configuration SUB-MENUItem # Format Comments Runtime menu description Description of the Alarms menuDescription of the Alarms History menu Description of the Runtimes 1 menuStart/stop control Maintenance menu descriptionDescription of Runtimes 2 menu Item # Format Units DescriptionHeating/cooling/auto selection Heating/cooling/standby operationCCN Evaporator antifreeze protection Evaporator water pump controlControl interlock contact Control pointCooling setpoint Heating setpointDemand limit ResetNight mode Reset example in cooling mode Capacity controlAdditional electric heater stage control Master/slave assemblyDefrost function Control of a boilerAlarm codes Displaying alarmsResetting alarms Then, 2 ALArM Then, no ALArMAlarm Code Descriptions

30RY/RYH, 30RA/RH specifications

The Carrier 30RY/RYH and 30RA/RH chiller models are leading solutions in commercial and industrial cooling applications. Renowned for their reliability, efficiency, and advanced technologies, these chillers cater to a wide variety of settings, from office buildings to manufacturing facilities.

The 30RY/RYH series features a distinctive design optimized for performance, utilizing a centrifugal compressor that ensures smooth operation under varying loads. One of the standout features of these chillers is their high-efficiency capabilities, which contribute to lower energy consumption. The models are engineered to deliver substantial energy savings, meeting or exceeding the latest ASHRAE and DOE efficiency standards.

A significant aspect of the 30RY and 30RA models is their use of environmentally friendly refrigerants. The 30RYH, for instance, employs R-134a refrigerant, which is designed to minimize ozone depletion while maximizing efficiency. This commitment to sustainability aligns with modern environmental regulations and practices, making these chillers a wise choice for eco-conscious projects.

In terms of control technology, the chiller models come equipped with advanced microprocessor-based controls, providing users with optimal system management and diagnostics. This integrated control system enhances the overall performance and reliability of the chillers, allowing for real-time monitoring and adjustment to ensure peak operational efficiency.

Another key feature is the quiet operation of the 30RY/RYH and 30RA/RH series. Designed with sound attenuation in mind, these units minimize noise pollution, making them suitable for installations in noise-sensitive environments. Additionally, the modular design allows for easy installation and maintenance, reducing downtime and providing flexibility in system design.

Both series also offer robust thermal performance, with the capability to handle a wide range of operating conditions. The chillers excel in terms of cooling capacity, providing solutions for varying thermal loads while maintaining energy efficiency. This adaptability is invaluable for facilities managing seasonal changes in cooling demands.

In summary, the Carrier 30RY/RYH and 30RA/RH chillers represent an ideal blend of efficiency, advanced technology, and eco-friendliness. Their high-performance capabilities, user-friendly controls, and sustainable design make them a top choice for commercial and industrial applications, ensuring dependable cooling solutions for diverse environments.