Carrier 30RY/RYH, 30RA/RH manual Description of the User 2 Configuration sub-menu

Page 25

4.3.11.4 - Description of the User 2 Configuration sub-menu

USER 1 CONFIGURATION SUB-MENU

ITEM

FORMAT

UNITS

DEFAULT

COMMENTS

0

USEr 2 Menu

 

 

When selected this item authorises return to the previous menu.

1

«YES/no»

-

no

Periodic pump quick-start of the water pump(s)

 

 

 

 

Yes = the pump is started periodically when the unit is manually stopped.

 

 

 

 

No = periodic pump start is disabled

 

 

 

 

When the unit is manually stopped (e.g. during the winter season) the pump is started each day at 14.00 hours

 

 

 

 

for 2 seconds. If two pumps are available, pump #1 is started on odd days and pump #2 on even days.

2

n1n2n3 n4

-

00:00

Night control mode - start time*

 

00:00 to 23:59

Authorises entering the time of day at which the night control mode starts. During this period the fan runs at

 

 

 

 

low speed (to reduce fan noise) if permitted by operating conditions, and unit capacity is limited to the

 

 

 

 

maximum night values.

 

 

 

 

 

3 [1]

n1n2n3 n4

-

00:00

Night control mode - end time*

 

00:00 to 23:59

Authorises entering the time of day at which the night control mode ends.

4

«YES/no»

-

no

Night mode demand limit value. This item permits demand limitation in the night control mode. In this case, if

 

 

 

 

the unit fans cannot be kept at low speed due to the operating conditions, the unit capacity is reduced to

 

 

 

 

prevent fan operation at high speed.

 

 

 

 

 

5

0 to 100

%

0

Night mode demand limit. The unit capacity is never reduced below this capacity in night control mode.

6

0/1/2

-

0

Alarm relay selection

 

 

 

 

0 = alarms/alerts, one alarm/alert output per circuit.

 

 

 

 

1 = alarms only, one alarm output per circuit.

 

 

 

 

2 = mixed mode, one alarm relay and one alert relay, dual-circuit units only.

7

0 or 65 to 99

-

0

Schedule 1 clock number (for unit on/off schedule, see section 4.3.11.6).

 

 

 

 

0 = schedule in local operating mode

 

 

 

 

65 to 99 = schedule in CCN operating mode

8

0 or 65 to 99

-

0

Schedule 2 clock number (schedule for setpoint selection, see section 4.3.11.6).

 

 

 

 

0 = schedule in local operating mode

 

 

 

 

65 to 99 = schedule in CCN operating mode

 

 

 

 

 

9

1 to 239

-

1

CCN element address.

 

 

 

 

No two network elements can have the same element number and bus number at the same time.

10

0 to 239

-

0

CCN bus number.

 

 

 

 

No two network elements can have the same element number and bus number at the same time.

11

«YES/no»

-

no

Password for all User Configurations

 

 

 

 

Yes = password required for all User Configurations (Date, Time Schedule, Broadcast)

 

 

 

 

No = password require for User menu only

 

 

 

 

When this item is validated, the User Password will be required for all configurations accessible by the User.

 

 

 

 

 

12

nn.n

-

-

Software version number

 

 

 

 

This item shows the number of the software version used by this controller. Access is read only.

*n1n2: hours (00 to 23). The first time the Enter button is continuously pressed, the first two characters in the 4-digit display flash so that hours can be adjusted.

n3n4: minutes (00 to 59). Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be adjusted.

4.3.11.5- Description of Date and Time configuration sub-

menu

DATE & TIME CONFIGURATION SUB-MENU

ITEM

FORMAT

COMMENTS

0

dAtE MEnu

When selected this item authorises return to the

 

 

previous menu.

1

n1n2n3n4

Current time setting.

 

00:00 to 23:59

n1n2: hours (00 to 23). The first time the Enter button is

 

 

continuously pressed, the first two characters in the 4-

 

 

digit display flash so that hours can be adjusted.

 

 

n3n4: minutes (00 to 59). Continuous pressing of the

 

 

Enter key again causes the last two characters to flash

 

 

and minutes can be adjusted.

 

 

 

2

 

Current day of week setting.

 

«Mon»

Monday

 

«tUe»

Tuesday

 

«uEd»

Wednesday

 

«tHu»

Thursday

 

«FrI»

Friday

 

«SAt»

Saturday

 

«Sun»

Sunday

 

 

 

3

n1n2n3n4

Current day and month setting.

 

01:01 to 31:12

n1n2:day (01 to 31). The first time the Enter button is

 

 

continuously pressed, the first two characters in the 4-

 

 

digit display flash so that day can be adjusted.

 

 

n3n4:month (01 to 12). Continuous pressing of the Enter

 

 

key again causes the last two characters to flash so

 

 

that month can be adjusted.

4

nnnn

Current year setting.

4.3.11.6- Description of the Time Schedules sub-menus The control provides two timer programs: schedule 1 and schedule 2 that can be activated if the unit is equipped with an optional CCN/clock board (if the CCN/clock board is not installed, the two schedules are permanently in occupied mode).

The first timer program (schedule #1) provides a means to automatically switch the unit from an occupied mode to an unoccupied mode: the unit is started during occupied periods.

The second timer program (schedule #2) provides a means to automatically switch the active setpoint from an occupied setpoint to an unoccupied setpoint: cooling setpoint 1 is used during occupied periods, cooling or heating setpoint 2 during unoccupied periods. Heating setpoint 3 is activated during holiday periods. For additional information on set-point activation see section 5.6.1.

Each schedule consists of eight time periods set by the operator. These time periods can be flagged to be in effect or not in effect on each day of the week plus a holiday period (see section

4.3.11.7on public holidays). The day begins at 00.00 hours and ends at 24.00 hours.

25

Image 25
Contents 30RA/RH B 30RY/RYH B PRO-DIALOG Control Operation and maintenance instructionsTable of Contents Safety Considerations PRO-DIALOG Control Operation Avoid electrocution GeneralAbbreviations used Following abbreviations are used frequentlyLight emitting diodes on boards Electrical supply to boardsSensors Pressure sensorsConnections at the users terminal block ControlsBase DUAL-CIRCUIT UnitsNRCP-BASE CCN OFF Volt-free contact on/off/cooling/heating with multiplexingMain interface Local interface general featuresMain Interface Button Name Description Not available on the PRO-DIALOG Junior interfaceUnit start/stop control Stopping the unit in local modeDescription Starting unit and selecting an operating typeMenus Modifying the value of a parameter/access to a sub- menuSelecting a menu Selecting a menu itemExpand display Menu Active alarm code Historic alarm Active alarm code Historic alarm codeMenu tree structure SUB-MENUInformation Menu Format Units Description Description of the Information menuFormat Units Description Information MenuDescription of the Setpoints menu Temperatures Menu Format Units CommentsPressures Menu Format Units Comments Setpoints Menu Format Units Range CommentsEntering Water Temperature Control Leaving Water Temperature Control Setpoint CReset Thresholds in Cooling or Heating Mode Description of the Inputs menuMenu description Description of the Outputs/Tests menu GeneralOutputs Status & Tests Menu 2 Format Units Description Automatic tests Manual testsOutputs Status & Tests Menu 2 Additional heating stage statusTest Number Description Confirmation Password Description of the configuration menu GeneralTest Fault Description SUB-MENU Holiday Configuration SUB-MENU Period ConfigurationUser 1 Configuration SUB-MENU Format Units Default Comments Description of the User 1 Configuration sub-menuDescription of Date and Time configuration sub Menu Description of the User 2 Configuration sub-menuDate & Time Configuration SUB-MENU Format Comments Description of the Holidays sub-menus Typical timer programDescription of the Broadcast sub-menu Broadcast Configuration SUB-MENUItem # Format Comments Description of the Alarms History menu Description of the Alarms menuRuntime menu description Description of the Runtimes 1 menuDescription of Runtimes 2 menu Maintenance menu descriptionStart/stop control Item # Format Units DescriptionHeating/cooling/auto selection Heating/cooling/standby operationCCN Control interlock contact Evaporator water pump controlEvaporator antifreeze protection Control pointHeating setpoint Cooling setpointNight mode Reset example in cooling mode ResetDemand limit Capacity controlDefrost function Master/slave assemblyAdditional electric heater stage control Control of a boilerResetting alarms Displaying alarmsAlarm codes Then, 2 ALArM Then, no ALArMAlarm Code Descriptions

30RY/RYH, 30RA/RH specifications

The Carrier 30RY/RYH and 30RA/RH chiller models are leading solutions in commercial and industrial cooling applications. Renowned for their reliability, efficiency, and advanced technologies, these chillers cater to a wide variety of settings, from office buildings to manufacturing facilities.

The 30RY/RYH series features a distinctive design optimized for performance, utilizing a centrifugal compressor that ensures smooth operation under varying loads. One of the standout features of these chillers is their high-efficiency capabilities, which contribute to lower energy consumption. The models are engineered to deliver substantial energy savings, meeting or exceeding the latest ASHRAE and DOE efficiency standards.

A significant aspect of the 30RY and 30RA models is their use of environmentally friendly refrigerants. The 30RYH, for instance, employs R-134a refrigerant, which is designed to minimize ozone depletion while maximizing efficiency. This commitment to sustainability aligns with modern environmental regulations and practices, making these chillers a wise choice for eco-conscious projects.

In terms of control technology, the chiller models come equipped with advanced microprocessor-based controls, providing users with optimal system management and diagnostics. This integrated control system enhances the overall performance and reliability of the chillers, allowing for real-time monitoring and adjustment to ensure peak operational efficiency.

Another key feature is the quiet operation of the 30RY/RYH and 30RA/RH series. Designed with sound attenuation in mind, these units minimize noise pollution, making them suitable for installations in noise-sensitive environments. Additionally, the modular design allows for easy installation and maintenance, reducing downtime and providing flexibility in system design.

Both series also offer robust thermal performance, with the capability to handle a wide range of operating conditions. The chillers excel in terms of cooling capacity, providing solutions for varying thermal loads while maintaining energy efficiency. This adaptability is invaluable for facilities managing seasonal changes in cooling demands.

In summary, the Carrier 30RY/RYH and 30RA/RH chillers represent an ideal blend of efficiency, advanced technology, and eco-friendliness. Their high-performance capabilities, user-friendly controls, and sustainable design make them a top choice for commercial and industrial applications, ensuring dependable cooling solutions for diverse environments.