5.6.2 - Reset

Reset means that the active setpoint is modified so that less machine capacity is required (in cooling mode, the setpoint is increased, in heating mode it is decreased). This modification is in general a reaction to a drop in the load. For the Pro-Dialog control system, the source of the reset can be configured in the User 1 configuration: it can be provided either by the outdoor temperature (that gives a measure of the load trends for the building) or by the return water temperature (delta T that gives an average building load). In response to a drop in the outdoor temperature or to a drop in delta T, the cooling setpoint is normally reset upwards in order to optimise unit performance:

In both cases the reset parameters, i.e. slope, source and maximum value, are configurable in the Setpoints menu (see section 4.3.8). Reset is a linear function based on three parameters.

A reference at which reset is zero (outdoor temperature or delta T - no reset value).

A reference at which reset is maximum (outdoor temperature or delta T - full reset value).

The maximum reset value.

5.7 - Demand limit

Generally, demand limit is used by an energy management system to restrict the unit electricity consumption. The PRO- DIALOG control system enables the capacity of the unit to be limited by means of user-controlled volt-free contacts. Single- circuit units only have one contact (control contact 3), available in the User Configuration function for demand limiting or setpoint selection. Dual-circuit units have two volt-free contacts that permit several limit levels. The capacity of the unit cannot exceed the demand limit setpoint activated by the position of the contacts (see section 3.6.4 and 3.6.5 for the contact description). The demand limit setpoints are adjustable via the setpoint menu.

The demand limit is active in all operating types: Local, Remote or CCN. However in CCN operating type, demand limit can be controlled directly with the aid of CCN commands.

A limitation value of 100% means that the unit may call upon the full array of its capacity stages.

5.8 - Night mode

Reset example in cooling mode

Reset value

% Building load

 

Outdoor temperature (OAT)

 

Evaporator Delta T

Legend

AMaximum reset value

BOAT or delta T for no reset

COAT or delta T for full reset

DBuilding Load

The night period is defined (see User configuration) by a start time and an end time that are the same for each day of the week. During the night period, the fan runs at low speed, if permitted by the current operating conditions. In addition, the user can reduce the unit capacity (but a minimum capacity value can be configured).

5.9 - Capacity control

This function adjusts the number of active compressors to keep the heat exchanger water temperature at its setpoint. The precision with which this is achieved depends on the capacity of the water loop, the flow rate, the load, and the number of stages available on the unit. The control system continuously takes account of the temperature error with respect to the setpoint, as well as the rate of change in this error and the difference between entering and leaving water temperatures, in order to determine the optimum moment at which to add or withdraw a capacity stage. If the same compressor undergoes too many starts (per hour) or runs below one minute each time it is started this automatically brings about reduction of compressor starts, which makes leaving water temperature control less precise. In addition, the high pressure, low pressure or defrost unloading functions can also affect the temperature control accuracy. Compressors are started and stopped in a sequence designed to equalise the number of start-ups (value weighted by their operating time).

NOTE: Circuits with 3 compressors (reversible heat pump units) only provide 2 capacity stages (2 compressors are started/stopped together).

5.10 - Head pressure control

Condensing pressure control is automatically ensured by a two- speed fan and can also be ensured by an additional fan on each circuit (no adjustment).

Fanstart-up:

ATTENTION: In accordance with the operating conditions the fans can be cleaned periodically. A fan can start at any time, even if the unit has been shut down.

33

Image 33
Contents 30RA/RH B 30RY/RYH B PRO-DIALOG Control Operation and maintenance instructionsTable of Contents Safety Considerations PRO-DIALOG Control Operation Avoid electrocution GeneralAbbreviations used Following abbreviations are used frequentlyLight emitting diodes on boards Electrical supply to boardsSensors Pressure sensorsConnections at the users terminal block ControlsDUAL-CIRCUIT Units BaseNRCP-BASE CCN OFF Volt-free contact on/off/cooling/heating with multiplexingMain interface Local interface general featuresMain Interface Button Name Description Not available on the PRO-DIALOG Junior interfaceUnit start/stop control Stopping the unit in local modeDescription Starting unit and selecting an operating typeMenus Modifying the value of a parameter/access to a sub- menuSelecting a menu Selecting a menu itemExpand display Menu Active alarm code Historic alarm Active alarm code Historic alarm codeMenu tree structure SUB-MENUInformation Menu Format Units Description Description of the Information menuFormat Units Description Information MenuDescription of the Setpoints menu Temperatures Menu Format Units CommentsPressures Menu Format Units Comments Setpoints Menu Format Units Range CommentsEntering Water Temperature Control Leaving Water Temperature Control Setpoint CReset Thresholds in Cooling or Heating Mode Description of the Inputs menuDescription of the Outputs/Tests menu General Menu descriptionOutputs Status & Tests Menu 2 Format Units Description Automatic tests Manual testsOutputs Status & Tests Menu 2 Additional heating stage statusTest Number Description Confirmation Description of the configuration menu General PasswordTest Fault Description SUB-MENU Holiday Configuration SUB-MENU Period ConfigurationUser 1 Configuration SUB-MENU Format Units Default Comments Description of the User 1 Configuration sub-menuDescription of the User 2 Configuration sub-menu Description of Date and Time configuration sub MenuDate & Time Configuration SUB-MENU Format Comments Description of the Holidays sub-menus Typical timer programBroadcast Configuration SUB-MENU Description of the Broadcast sub-menuItem # Format Comments Description of the Alarms History menu Description of the Alarms menuRuntime menu description Description of the Runtimes 1 menuDescription of Runtimes 2 menu Maintenance menu descriptionStart/stop control Item # Format Units DescriptionHeating/cooling/standby operation Heating/cooling/auto selectionCCN Control interlock contact Evaporator water pump controlEvaporator antifreeze protection Control pointHeating setpoint Cooling setpointNight mode Reset example in cooling mode ResetDemand limit Capacity controlDefrost function Master/slave assemblyAdditional electric heater stage control Control of a boilerResetting alarms Displaying alarmsAlarm codes Then, 2 ALArM Then, no ALArMAlarm Code Descriptions

30RY/RYH, 30RA/RH specifications

The Carrier 30RY/RYH and 30RA/RH chiller models are leading solutions in commercial and industrial cooling applications. Renowned for their reliability, efficiency, and advanced technologies, these chillers cater to a wide variety of settings, from office buildings to manufacturing facilities.

The 30RY/RYH series features a distinctive design optimized for performance, utilizing a centrifugal compressor that ensures smooth operation under varying loads. One of the standout features of these chillers is their high-efficiency capabilities, which contribute to lower energy consumption. The models are engineered to deliver substantial energy savings, meeting or exceeding the latest ASHRAE and DOE efficiency standards.

A significant aspect of the 30RY and 30RA models is their use of environmentally friendly refrigerants. The 30RYH, for instance, employs R-134a refrigerant, which is designed to minimize ozone depletion while maximizing efficiency. This commitment to sustainability aligns with modern environmental regulations and practices, making these chillers a wise choice for eco-conscious projects.

In terms of control technology, the chiller models come equipped with advanced microprocessor-based controls, providing users with optimal system management and diagnostics. This integrated control system enhances the overall performance and reliability of the chillers, allowing for real-time monitoring and adjustment to ensure peak operational efficiency.

Another key feature is the quiet operation of the 30RY/RYH and 30RA/RH series. Designed with sound attenuation in mind, these units minimize noise pollution, making them suitable for installations in noise-sensitive environments. Additionally, the modular design allows for easy installation and maintenance, reducing downtime and providing flexibility in system design.

Both series also offer robust thermal performance, with the capability to handle a wide range of operating conditions. The chillers excel in terms of cooling capacity, providing solutions for varying thermal loads while maintaining energy efficiency. This adaptability is invaluable for facilities managing seasonal changes in cooling demands.

In summary, the Carrier 30RY/RYH and 30RA/RH chillers represent an ideal blend of efficiency, advanced technology, and eco-friendliness. Their high-performance capabilities, user-friendly controls, and sustainable design make them a top choice for commercial and industrial applications, ensuring dependable cooling solutions for diverse environments.