Carrier 30RY/RYH Description of Runtimes 2 menu, Maintenance menu description, Start/stop control

Page 29

4.3.14.2 - Description of Runtimes 2 menu

ITEM #

FORMAT

UNITS

DESCRIPTION

0

-

-

When selected this item

 

 

 

authorises return to the

 

 

 

previous menu

 

 

 

 

1

nn

-

Compressor starts for

 

 

 

compressor with most starts

 

 

 

during the last hour

2

nn

-

24 hours average number of

 

 

 

starts/hour, compressor

 

 

 

 

3

nn

minutes

Minimum compressor

 

 

 

operating time during last

 

 

 

hour

4

nn

minutes

24 hours average minimum

 

 

 

operating time above

 

 

 

 

5 [1]

nnnn M 10 M100

hrs/10 or 100

Boiler operating hours

 

 

 

 

6 [1]

nnnn M 10

hrs/10 or 100

Electric heating stage

 

 

 

operating hours

 

 

 

 

7 [1]

nnnn M 10 M100

-/10 or 100

No. of defrost cycles, circuit

 

 

 

A

8 [1]

nnnn M 10 M100

-/10 or 100

No. of defrost cycles, circuit

 

 

 

B

 

 

 

 

4.3.14.3 - Maintenance menu description

To be active, the maintenance function must be preset in the Service configuration

ITEM #

FORMAT

DESCRIPTION

0

MAintEnAnCE MEnu

When selected this item authorises return to

 

 

the previous menu.

 

 

 

1 [1]

 

Accessible with the Service password.

2 [1]

 

For future use

3 [1]

 

For future use

4 [1]

ALErt

Water loop rate to low

 

 

 

5 [1]

nnn/ALErt

Next primary pump maintenance operation in

 

 

nnn days. 'ALErt' is displayed, when the delay

 

 

before maintenance has elapsed.

 

 

 

6 [1]

nnn/ALErt

Next secondary pump maintenance operation

 

 

in nnn days. 'ALErt' is displayed, when the

 

 

delay before maintenance has elapsed.

7 [1]

nnn/ALErt

Next water filter maintenance operation in nnn

 

 

days. 'ALErt' is displayed, when the delay

 

 

before maintenance has elapsed.

 

 

 

1 This item is masked when not used.

5 - PRO-DIALOG CONTROL OPERATION

5.1 - Start/stop control

The table below summarises the unit control type and stop or go status with regard to the following parameters.

-Operating type: this is selected using the start/stop button on the front of the user interface.

-Remote start/stop contacts: these contacts are used when the unit is in remote operating type (rEM). See sections 3.6.2 and 3.6.3.

-CHIL_S_S: this network command relates to the chiller start/stop when the unit is in CCN control (CCn). Vari- able forced to disable: the unit is halted. Variable forced to Enable: the unit runs in accordance with schedule 1.

-Start/Stop schedule: occupied or unoccupied status of the unit as determined by the chiller start/stop program (Schedule #1). Used when the unit is equipped with an optional CCN/clock board, otherwise the chiller occupied mode is forced to occupied all the time.

-Master control type. This parameter is used when the unit is the master unit in a two chiller lead/lag arrange- ment. The master control type determines whether the unit is to be controlled locally, remotely or through CCN (this parameter is a Service configuration).

-CCN emergency shutdown: if this CCN command is activated, it shuts the unit down whatever the active operating type.

-General alarm: the unit is totally stopped due to failure.

29

Image 29
Contents 30RA/RH B 30RY/RYH B PRO-DIALOG Control Operation and maintenance instructionsTable of Contents Safety Considerations PRO-DIALOG Control Operation Avoid electrocution GeneralAbbreviations used Following abbreviations are used frequentlyLight emitting diodes on boards Electrical supply to boardsSensors Pressure sensorsConnections at the users terminal block ControlsNRCP-BASE CCN DUAL-CIRCUIT UnitsBase OFF Volt-free contact on/off/cooling/heating with multiplexingMain interface Local interface general featuresMain Interface Button Name Description Not available on the PRO-DIALOG Junior interfaceUnit start/stop control Stopping the unit in local modeDescription Starting unit and selecting an operating typeMenus Modifying the value of a parameter/access to a sub- menuSelecting a menu Selecting a menu itemExpand display Menu Active alarm code Historic alarm Active alarm code Historic alarm codeMenu tree structure SUB-MENUInformation Menu Format Units Description Description of the Information menuFormat Units Description Information MenuDescription of the Setpoints menu Temperatures Menu Format Units CommentsPressures Menu Format Units Comments Setpoints Menu Format Units Range CommentsEntering Water Temperature Control Leaving Water Temperature Control Setpoint CReset Thresholds in Cooling or Heating Mode Description of the Inputs menuOutputs Status & Tests Menu 2 Format Units Description Description of the Outputs/Tests menu GeneralMenu description Automatic tests Manual testsOutputs Status & Tests Menu 2 Additional heating stage statusTest Number Description Confirmation Test Fault Description Description of the configuration menu GeneralPassword SUB-MENU Holiday Configuration SUB-MENU Period ConfigurationUser 1 Configuration SUB-MENU Format Units Default Comments Description of the User 1 Configuration sub-menuDate & Time Configuration SUB-MENU Format Comments Description of the User 2 Configuration sub-menuDescription of Date and Time configuration sub Menu Description of the Holidays sub-menus Typical timer programItem # Format Comments Broadcast Configuration SUB-MENUDescription of the Broadcast sub-menu Description of the Alarms History menu Description of the Alarms menuRuntime menu description Description of the Runtimes 1 menuDescription of Runtimes 2 menu Maintenance menu descriptionStart/stop control Item # Format Units DescriptionCCN Heating/cooling/standby operationHeating/cooling/auto selection Control interlock contact Evaporator water pump controlEvaporator antifreeze protection Control pointHeating setpoint Cooling setpointNight mode Reset example in cooling mode ResetDemand limit Capacity controlDefrost function Master/slave assemblyAdditional electric heater stage control Control of a boilerResetting alarms Displaying alarmsAlarm codes Then, 2 ALArM Then, no ALArMAlarm Code Descriptions

30RY/RYH, 30RA/RH specifications

The Carrier 30RY/RYH and 30RA/RH chiller models are leading solutions in commercial and industrial cooling applications. Renowned for their reliability, efficiency, and advanced technologies, these chillers cater to a wide variety of settings, from office buildings to manufacturing facilities.

The 30RY/RYH series features a distinctive design optimized for performance, utilizing a centrifugal compressor that ensures smooth operation under varying loads. One of the standout features of these chillers is their high-efficiency capabilities, which contribute to lower energy consumption. The models are engineered to deliver substantial energy savings, meeting or exceeding the latest ASHRAE and DOE efficiency standards.

A significant aspect of the 30RY and 30RA models is their use of environmentally friendly refrigerants. The 30RYH, for instance, employs R-134a refrigerant, which is designed to minimize ozone depletion while maximizing efficiency. This commitment to sustainability aligns with modern environmental regulations and practices, making these chillers a wise choice for eco-conscious projects.

In terms of control technology, the chiller models come equipped with advanced microprocessor-based controls, providing users with optimal system management and diagnostics. This integrated control system enhances the overall performance and reliability of the chillers, allowing for real-time monitoring and adjustment to ensure peak operational efficiency.

Another key feature is the quiet operation of the 30RY/RYH and 30RA/RH series. Designed with sound attenuation in mind, these units minimize noise pollution, making them suitable for installations in noise-sensitive environments. Additionally, the modular design allows for easy installation and maintenance, reducing downtime and providing flexibility in system design.

Both series also offer robust thermal performance, with the capability to handle a wide range of operating conditions. The chillers excel in terms of cooling capacity, providing solutions for varying thermal loads while maintaining energy efficiency. This adaptability is invaluable for facilities managing seasonal changes in cooling demands.

In summary, the Carrier 30RY/RYH and 30RA/RH chillers represent an ideal blend of efficiency, advanced technology, and eco-friendliness. Their high-performance capabilities, user-friendly controls, and sustainable design make them a top choice for commercial and industrial applications, ensuring dependable cooling solutions for diverse environments.