COMMUNICATIONS GUIDE | FIELDBUS INTERFACE |
DeviceNet protocol
To enable the DeviceNet physical interface, ensure that switches 1 and 2 of the DIP switch communications card (on the CPU module) are on. The external connections through the fieldbus interface are as follows.
Table 13: Fieldbus interface external connections (DeviceNet)
Path | Connection (external) | Wire color |
|
|
|
V– | Pin 3, CAN_GND | Black |
L | Pin 2, CAN_L | Blue |
|
|
|
C | Pin 5, CAN_SHLD | Bare |
|
|
|
H | Pin 7, CAN_H | White |
|
|
|
V+ | Pin 9, CAN_V | Red |
|
|
|
The Modbus status (MS) and network status (NS) LEDs indicate the status of the Fieldbus interface.
Table 14: DeviceNet LED indications
LED | LED operation | Description |
|
|
|
MS | Green on, red on, green on | Device |
|
|
|
| Flashing green | Device in standby state |
|
|
|
| Green on | Device operational |
|
|
|
| Flashing red | Recoverable fault |
|
|
|
| Red on | Unrecoverable fault |
|
|
|
NS | Flashing green | Online, not connected |
|
|
|
| Green on | Online, connected |
|
|
|
| Flashing red | Connection timeout |
|
|
|
| Red on | Critical link failure |
|
|
|
| Red and green | Network access detected |
|
|
|
When used for DeviceNet, the fieldbus port has the following characteristics.
•Baud rate: 125, 250, and 500 kbps
•MAC ID: 0 to 63
•Vendor ID: 928
•Product Code: 0x4D39
•Message types: poll, and explicit messaging
DeviceNet Communications
The device profile is an extension of the Communications Adapter Device Profile (0xC0). It is a group 2 only server. The MAC ID and baud rate are programmable through the EnerVista MM300 Setup software and the Graphical Control Panel. The MM300 supports the following DeviceNet object classes.
CLASS | OBJECT |
|
|
01H | Identify |
|
|
02H | Message Router |
|
|
03H | DeviceNet |
|
|
05H | Connection |
|
|
A0H | Generic Data - Polling/Explicit |
|
|
B1H | Explicit Control Writes |
|
|
B0H | Analog Data - Explicit |
|
|
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE | 57 |