GE MM300 manual Maintenance, Start Inhibit, Restart Block, Calibration, Flexlogic Timers

Page 30

RS485 INTERFACE (MODBUS RTU)

 

 

 

 

 

COMMUNICATIONS GUIDE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Modbus

 

Hex

Description

Min

Max

Step

Units

Format

Default

Size in

 

 

 

 

 

 

 

 

 

 

 

 

Words

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40911

 

038E

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAINTENANCE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40912

 

038F

Drive Greasing Interval

100

50100

100

hrs

F1*

50100

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40913

 

0390

Contactor Inspection Interval

100

65000

100

ops

F1*

65000

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40914

 

0391

Max Motor Stopped Time

10

10010

10

hrs

F1*

10010

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40915

 

0392

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40916

 

0393

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

START INHIBIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40917

 

0394

Start Inhibit Margin

0

11

1

%

F1*

11

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40918

 

0395

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40919

 

0396

Starts/Hour Limit

1

6

1

---

F1*

6

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40920

 

0397

Time Between Starts

1

3601

1

s

F1*

3601

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40921

 

0398

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHANGE MODE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40922

 

0399

Change Mode on Comm Alarm

0

1

1

---

FC126

0

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40923

 

039A

Change Mode when running

0

1

1

---

FC126

0

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40924

 

039B

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40925

 

039C

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

RESTART BLOCK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40926

 

039D

Restart Block Time

1

50001

1

s

F1*

50001

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40927

 

039E

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41039

 

040E

Reserved

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CALIBRATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41040

 

040F

Calibration Date

0

203360302

1

---

F18

0

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41042

 

0411

Calibration Time

0

389757795

1

---

F19

0

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41044

 

0413

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41105

 

0450

Reserved

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SECURITY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41106

 

0451

Passcode Level 1

11111

55556

1

---

F1*

11111

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41107

 

0452

Passcode Level 2

11111

55556

1

---

F1*

22222

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41108

 

0453

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41109

 

0454

Access Switch Level

1

3

1

---

F1

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41110

 

0455

Comms Security

0

1

1

---

FC126

0

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41111

 

0456

MCC Setpoint Access

0

1

1

---

FC126

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41112

 

0457

Passcode Entry

0

55555

1

---

F1

0

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41113

 

0458

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41114

 

0459

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41115

 

045A

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41116

 

045B

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

FLEXLOGIC TIMERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41117

 

045C

Timer 1 Type

0

2

1

---

FC141

0

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41118

 

045D

Timer 1 Pickup Delay

0

1000

1

---

F1

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41119

 

045E

Timer 1 Dropout Delay

0

1000

1

---

F1

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41120

 

045F

Reserved

---

---

---

---

---

---

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26

MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE

Image 30
Contents MM300 Page Table of Contents MM300 Motor Management System Communications Guide MM300 Motor Management System Communications Guide Electrical Interface Data Frame Format and Data RateData Packet Format Error Checking CRC-16 AlgorithmTiming MM300 supported functionsFunction Code 03H Master Transmission Bytes Example Description Function Code 04HMaster/slave packet format for function code 03H Slave Response Bytes Example DescriptionFunction Code 05H Master/slave packet format for function code 04HMaster/slave packet format for function code 05H Data Function Code 06HMaster/slave packet format for function code 06H CRC CB B9Function Code 07H Function code 7 bitmaskMaster/slave packet format for function code 07H Master/slave packet format for function code 08H Function Code 08HFunction Code 10H Diag CodeError Responses Master/slave packet format for function code 10HModbus memory map Actual ValuesGeneral Timers REAL-TIME ClockTrip Counters Status Motor CONTACT/VIRTUAL INPUTS/OUTPUTS StatusSecurity Current MeteringPower Metering GCP Factory Test FLA RTD Maximium TemperatureMotor Starting Learned Data User MAP ValuesEvent Recorder Status BufferFlexlogic Setpoints CommandsCommunication Settings CommunicationREAL-TIME CLOCK/DAYLIGHT Savings Current SensingMotor Data Setup Voltage SensingProcess Interlock RS485 Interface Modbus RTU Communication Setup Open Control CircuitUser MAP Addresses Reset Setup Mechanical JAMRTD OPEN/SHORT Circuit REQUIRED=IOG Thermistor CPUUndercurrent REQUIRED=IOA Underpower IOA + IOC or IOA + IOBGround Fault FLAPhase Reversal REQUIRED=IOB Phase Undervoltage REQUIRED=IOBPhase Overvoltage REQUIRED=IOB Load IncreaseStart Inhibit MaintenanceFlexlogic Timers Restart BlockCommunications Guide RS485 Interface Modbus RTU Communications Guide RS485 Interface Modbus RTU Contact Input Assignment Contact Outputs Auto / Manual ControlFlexlogic Equation Unsigned VALUE, 2 Decimal Places Unsigned ValueUnsigned VALUE, 1 Decimal Place Unsigned Long ValueMSB Unsigned Long VALUE, 3 Decimal PlacesDate MM/DD/YYYY LSBOFF / no On / YESOFF USER1 USER2USER3 No Event/Trip To Date RS485 Interface Modbus RTU RS485 Interface Modbus RTU Not XOR Latch NOR Nand Timer Assign RS485 Interface Modbus RTU Definition RS485 Interface Modbus RTU TUE SUNMON WEDVbn Direct Bit FC180 FC181 FC182 FC183 RS485 Interface Modbus RTU Performing Commands Using Function Code 10H Using the User Definable Memory Map Master/slave packet format for performing commandsCRC 7E CE RS485 Interface Modbus RTU Ethernet interface Profibus LED indications Profibus Output DataFieldbus interface external connections Profibus LEDProfibus Input Data Profibus DP-DiagnosticsSystem Standard Diagnostics Bytes 1 through F1BCommunications Guide Fieldbus Interface DeviceNet LED indications DeviceNet CommunicationsFieldbus interface external connections DeviceNet Class ObjectIdentity Object Class Code 01H Message Router Class Code 02HDeviceNet Object Class Code 03H DeviceNet Connection Object Class Code 05H Connection Object, Class Code 05h, ServicesAttribute Access Name Data Type Value Description Identity Object, Class Code 03h, Instance 01h, AttributesMotor Data Object, Class Code A0h, Services DeviceNet Motor Data Poll, Explicit Object Class Code A0HMotor Data Object, Class Code A0h, Attributes Item Description Size in Bytes Format Explicit Motor Analog Data Object, Class Code B0h, Services Attribute Description Size in Bytes0FH Data Formats, Explicit Motor Analog Data Object Attribute Item Description Size Format BytesFieldbus Interface Explicit Motor Control Object, Class Code B1h, Attributes Explicit Motor Control Object, Class Code B1h, ServicesDeviceNet Explicit Motor Object, Class Code B1H Data Value, Class B1hFieldbus Interface

MM300 specifications

The GE MM300 is a robust and versatile controller designed primarily for industrial automation applications. Built to tackle the demands of modern manufacturing environments, this controller offers a range of features that contribute to its popularity among engineers and operators.

One of the standout features of the GE MM300 is its scalability. The device can be easily configured to meet the needs of both small and large systems. Its modular architecture allows users to add or remove components based on the specific requirements of their applications, facilitating a more tailored approach to automation.

The MM300 supports various communication protocols, including Ethernet/IP, Modbus TCP, and more, ensuring seamless integration with a variety of devices and systems. This feature significantly enhances interoperability, allowing users to connect the controller to existing infrastructure without extensive reconfiguration.

In terms of processing power, the MM300 is equipped with a high-performance processor that can handle complex tasks with ease. With advanced data handling capabilities, it supports real-time data processing, enabling faster decision-making and improving overall operational efficiency. This capability is particularly beneficial for applications requiring precise control and monitoring.

Moreover, the GE MM300 boasts a user-friendly interface, featuring an intuitive programming environment that simplifies the development of control applications. This includes an integrated development environment (IDE) and support for popular programming languages, making it accessible for both seasoned programmers and those new to automation technologies.

The device is designed to operate in challenging industrial conditions, featuring a rugged construction that ensures durability and longevity. Its ability to withstand extreme temperatures, vibrations, and other environmental stressors enhances its reliability in demanding applications, which is crucial for minimizing downtime in production processes.

Security is another critical aspect of the GE MM300. The controller incorporates advanced security features to protect against unauthorized access and cyber threats, helping organizations ensure the integrity of their operations.

In summary, the GE MM300 stands out due to its scalability, versatile communication options, high processing capabilities, user-friendly programming environment, rugged design, and security features. These characteristics make it a reliable choice for industries seeking to enhance their automation processes and improve overall efficiency. Whether for small-scale or large-scale applications, the MM300 provides a comprehensive solution to meet the evolving needs of modern manufacturing.