GUIDE SPECIFICATIONS

GENERAL

System Description

Outdoor-mounted, air-cooled, split-system heat pump unit suitable for ground or rooftop installation. Unit consists of a hermetic compressor, an air-cooled coil, propeller-type condenser fan, and a control box. Unit will discharge supply air upward as shown on contract drawings. Unit will be used in a refrigeration circuit to match up to a packaged fan coil or coil unit.

Quality Assurance

Unit will be rated in accordance with the latest edition of ARI Standard 240.

Unit will be certified for capacity and efficiency, and listed in the latest ARI directory.

Unit construction will comply with latest edition of ANSI/ ASHRAE and with NEC.

Unit will be constructed in accordance with UL standards and will carry the UL label of approval. Unit will have C-UL approval.

Unit cabinet will be capable of withstanding Federal Test Method Standard No. 141 (Method 6061) 500-hr salt spray test.

Air-cooled condenser coils will be leak tested at 217 psig and pressure tested at 450 psig.

Unit constructed in ISO9001 approved facility.

Delivery, Storage, and Handling

Unit will be shipped as single package only and is stored and handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

U.S. and Canada only.

PRODUCTS

Equipment

Factory assembled, single piece, air-cooled heat pump unit. Contained within the unit enclosure is all factory wiring, piping, controls, compressor, refrigerant charge (R-22), and special features required prior to field start-up.

Unit Cabinet

Unit cabinet will be constructed of galvanized steel, bonderized, and coated with a powder coat paint.

Fans

Condenser fan will be direct-drive propeller type, discharging air upward.

Condenser fan motors will be totally enclosed, 1-phase type with class B insulation and permanently lubricated bearings.

Shafts will be corrosion resistant.

Fan blades will be statically and dynamically balanced.

Condenser fan openings will be equipped with steel wire safety guards.

Defrost control board which incorporates defrost relay, defrost timer and low voltage terminal board.

AIR-COOLED, SPLIT-SYSTEM HEAT PUMP 25HCR3C 1.5 TO 5 NOMINAL TONS

Compressor

Compressor will be hermetically sealed.

Compressor will be mounted on rubber vibration isolators.

Condenser Coil

Condenser coil will be air cooled.

Coil will be constructed of aluminum finstock with a resin-based epoxy-phenolic thermoset coating, factory applied by precoating and baking on both sides. The fins are mechanically bonded to copper tubes which are then cleaned, dehydrated, and sealed.

Refrigeration Components

Refrigeration circuit components will include liquid-line shutoff valve with sweat connections, vapor-line shutoff valve with sweat connections, system charge of refrigerant, compressor oil, accumulator, loss of charge switch, and reversing valve.

Operating Characteristics

The capacity of the unit will meet or exceed _____ Btuh at a suction temperature of _____ _F/_C. The power consumption at full load will not exceed _____ kW.

Combination of the unit and the evaporator or fan coil unit will have a total net cooling capacity of _____ Btuh or greater at conditions of _____ CFM entering air temperature at the evaporator at _____ _F/_C wet bulb and _____ _F/_C dry bulb, and air entering the unit at

_____ _F/_C.

The system will have a SEER of _____ Btuh/watt or greater at DOE conditions.

Electrical Requirements

Nominal unit electrical characteristics will be _____ v, single phase, 60 hz. The unit will be capable of satisfactory operation within voltage limits of _____ v to

_____ v.

Unit electrical power will be single point connection.

Control circuit will be 24v.

Special Features

Refer to section of this literature identifying accessories and descriptions for specific features and available enhancements.

25HCR3C

31

Image 31
Contents 25HCR3C Industry Leading Features / BenefitsModel Number Nomenclature Standard FeaturesUnit SIZE---SERIES, Voltage Physical DataAccessories Accessory ThermostatsAccessory Usage Guideline MotorMasterr Low-Ambient Controller Charging Subcooling TXV-TYPE Expansion Device Electrical DataDimensions 25HCR3C Balance Point Worksheet Heat LOSS, Unit Integrated Heating CAPACITY, Mbtuh BuildingCombination Ratings 30---30 Indoor Model Capa Voltage Factory StandardTDR&TXV CAR**3614A 28,600 FK4DNF003 FK4DNB006 36---3042---30 48---30 FK4DNF00560---30 25HCR318C Outdoor Section With FA4CNF,C018 Indoor Section Detailed Cooling Capacities800 Capacity MBtuh Total System Sens25HCR324C Outdoor Section With FA4CNF,C024 Indoor Section 7001000 Capacity Power Furnace Model25HCR330C Outdoor Section With FC4DNF030 Indoor Section 8751200 Cooling Indoor Model Capacity Power Furnace Model25HCR336C30 Outdoor Section With FC4DNF,B036 Indoor Section 10501575 25HCR342C Outdoor Section With FC4DNF,B042 Indoor Section1225 14001800 Cooling Indoor Capa Power Furnace Model City25HCR348C30 Outdoor Section With FC4DNF,B048 Indoor Section 16002000 Capacity MBtuh Total Sys System25HCR360C30 Outdoor Section With FC4DNF,B060 Indoor Section 175025HCR318C Outdoor Section With FA4CNF,C018 Indoor Section Heat Pump Heating PerformanceFC4DNF018 FC4DNF024 FF1ENE018 FF1ENE024 FK4DNF001 FK4DNF002 FC4DNF030 25HCR324C Outdoor Section With FA4CNF,C024 Indoor SectionFF1ENE030 FK4DNF001 FK4DNF002 25HCR330C Outdoor Section With FC4DNF030 Indoor SectionFK4DNF002 FK4DNF003 25HCR336C30 Outdoor Section With FC4DNF,B036 Indoor SectionFK4DNB006 25HCR342C Outdoor Section With FC4DNF,B042 Indoor SectionFK4DNB006 FK4DNF005 25HCR348C30 Outdoor Section With FC4DNF,B048 Indoor Section25HCR360C30 Outdoor Section With FC4DNF,B060 Indoor Section Products Guide Specifications GeneralCatalog No 25HCR3C---2PD