Carrier 25HCR3C warranty Electrical Data, Charging Subcooling TXV-TYPE Expansion Device

Page 7

ELECTRICAL DATA

 

 

 

 

 

 

 

 

MIN

MIN

MAX

MAX

MAX

UNIT SIZE

V/PH

OPER VOLTS*

COMPR

FAN

MCA

WIRE

WIRE

LENGTH

LENGTH

FUSE**

 

 

 

 

 

SIZE†

SIZE†

ft.(m)‡

ft.(m)‡

or BRK

 

 

 

 

 

 

 

 

 

 

MAX

MIN

LRA

RLA

FLA

 

60˚ C

75˚ C

60˚ C

75˚ C

AMPS

18

 

 

 

41

9.8

0.5

12.7

14

14

124

118

20

 

 

 

(37.80)

(35.97)

 

 

 

 

 

 

 

 

 

 

 

24

 

 

 

54

15.13

0.7

19.6

14

14

80

76

30

 

 

 

(23.16)

(23.16)

 

 

 

 

 

 

 

 

 

 

 

30

 

 

 

72.5

13.50

1.2

18.6

14

14

85

81

30

 

 

 

(25.91)

(24.69)

 

 

 

 

 

 

 

 

 

 

 

36

208/230/1--- 60

253

197

88

18.68

0.9

24.2

12

12

103

98

40

(31.39)

(29.87)

 

 

 

 

 

 

 

 

 

 

 

42

 

 

 

104

17.90

0.9

24.0

12

12

104

99

40

 

 

 

(31.70)

(30.18)

 

 

 

 

 

 

 

 

 

 

 

48

 

 

 

137

22.22

1.2

29.0

10

10

138

131

50

 

 

 

(42.06)

(39.93)

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

148

28.85

1.2

37.3

8

8

167

159

60

 

 

 

(50.90)

(48.46)

 

 

 

 

 

 

 

 

 

 

 

* Permissible limits of the voltage range at which the unit will operate satisfactorily

 

 

 

 

 

 

{If wire is applied at ambient greater than 30° C, consult table 310---16 of the NEC (ANSI/NFPA 70). The ampacity of non ---metallic---sheathed cable (NM),

trade name ROMEX, shall be that of 60° C conditions, per the NEC (ANSI/NFPA 70) Article 336---26. If other than uncoated (no---plated), 60 or 75° C insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).

}Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%. ** Time---Delay fuse.

FLA --- Full Load Amps LRA --- Locked Rotor Amps MCA --- Minimum Circuit Amps RLA --- Rated Load Amps

NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.

A-WEIGHTED SOUND LEVEL (dBA)

 

STANDARD

TYPICAL OCTAVE BAND SPECTRUM (dB, without tone adjustment)

UNIT SIZE

RATING

 

 

 

 

 

 

 

 

(dB)

125

250

500

1000

2000

4000

8000

 

 

 

 

 

 

 

 

 

18

71

55

58

64.5

65

64.5

63

55.5

24

74

57.0

62.5

68.5

69.5

67.5

63.0

55.0

30

73

58.0

66.0

66.0

67.5

64.5

61.0

54.5

36

74

53.5

65.5

64.5

68.5

66.0

62.0

54.5

42

74

59.0

62.0

66.0

69.0

65.0

60.0

51.5

48

75

54.5

61.0

66.0

71.0

65.5

62.0

56.5

60

75

56.5

66.5

67.5

69.5

67.5

63.5

56.5

CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE)

UNIT SIZE---SERIES

REQUIRED SUBCOOLING _F (_C)

Heating Piston Size

18

10 (5.6)

42

24

10 (5.6)

52

30

10 (5.6)

57

36

10 (5.6)

57

42

10 (5.6)

67

48

9

(5.0)

67

60

10 (5.6)

78

25HCR3C

7

Image 7
Contents 25HCR3C Industry Leading Features / BenefitsModel Number Nomenclature Standard FeaturesUnit SIZE---SERIES, Voltage Physical DataAccessories Accessory ThermostatsAccessory Usage Guideline MotorMasterr Low-Ambient Controller Charging Subcooling TXV-TYPE Expansion Device Electrical DataDimensions 25HCR3C Balance Point Worksheet Heat LOSS, Unit Integrated Heating CAPACITY, Mbtuh BuildingCombination Ratings 30---30 Indoor Model Capa Voltage Factory StandardTDR&TXV CAR**3614A 28,600 FK4DNF003 FK4DNB006 36---3042---30 48---30 FK4DNF00560---30 25HCR318C Outdoor Section With FA4CNF,C018 Indoor Section Detailed Cooling Capacities800 Capacity MBtuh Total System Sens25HCR324C Outdoor Section With FA4CNF,C024 Indoor Section 7001000 Capacity Power Furnace Model25HCR330C Outdoor Section With FC4DNF030 Indoor Section 8751200 Cooling Indoor Model Capacity Power Furnace Model25HCR336C30 Outdoor Section With FC4DNF,B036 Indoor Section 10501575 25HCR342C Outdoor Section With FC4DNF,B042 Indoor Section1225 14001800 Cooling Indoor Capa Power Furnace Model City25HCR348C30 Outdoor Section With FC4DNF,B048 Indoor Section 16002000 Capacity MBtuh Total Sys System25HCR360C30 Outdoor Section With FC4DNF,B060 Indoor Section 175025HCR318C Outdoor Section With FA4CNF,C018 Indoor Section Heat Pump Heating PerformanceFC4DNF018 FC4DNF024 FF1ENE018 FF1ENE024 FK4DNF001 FK4DNF002 FC4DNF030 25HCR324C Outdoor Section With FA4CNF,C024 Indoor SectionFF1ENE030 FK4DNF001 FK4DNF002 25HCR330C Outdoor Section With FC4DNF030 Indoor SectionFK4DNF002 FK4DNF003 25HCR336C30 Outdoor Section With FC4DNF,B036 Indoor SectionFK4DNB006 25HCR342C Outdoor Section With FC4DNF,B042 Indoor SectionFK4DNB006 FK4DNF005 25HCR348C30 Outdoor Section With FC4DNF,B048 Indoor Section25HCR360C30 Outdoor Section With FC4DNF,B060 Indoor Section Products Guide Specifications GeneralCatalog No 25HCR3C---2PD