Carrier 25HCR3C warranty Accessory Usage Guideline

Page 5

ACCESSORY USAGE GUIDELINE

 

REQUIRED FOR

REQUIRED FOR LONG

REQUIRED FOR SEA

Accessory

LOW---AMBIENT APPLICATIONS

LINE APPLICATIONS*

COAST APPLICATIONS

 

(Below 55° F / 12.78° C)

(Over 80 Ft. / 24.38 m)

(Within 2 miles / 3.22 km)

Ball Bearing Fan Motor

Yes{

No

No

Compressor Start Assist

Yes{

Yes

No

Capacitor and Relay

 

 

 

Crankcase Heater

Yes{

Yes

No

Evaporator Freeze Thermostat

Yes{

No

No

Isolation Relay

Yes{

No

No

Liquid Line Solenoid Valve

No

See Long Line Application

No

Guideline

 

 

 

Motor MasterControl

Yes{

No

No

or Low---ambient Pressure Switch

 

 

 

Support Feet

Recommended

No

Recommended

*For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. vertical (6.09 m) differential, refer to Residential Split System Long Line Application Guideline.

{Required for Low---Ambient Controller MotorMasterr Control only.

Accessory Description and Usage (Listed Alphabetically)

1. Ball-Bearing Fan Motor

A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.

Usage Guideline:

Required on all units when MotorMasterr is used.

2. Compressor Start Assist - Capacitor and Relay

Start capacitor and relay gives a ”hard” boost to compressor motor at each start up.

Usage Guideline:

Required for reciprocating compressors in the following applications:

Long line

Low ambient cooling

Hard shut off expansion valve on indoor coil Liquid line solenoid on indoor coil

Required for single-phase scroll compressors in the following applications:

Long line

Low ambient cooling

Suggested for all compressors in areas with a history of low voltage problems.

3. Compressor Start Assist — PTC Type

Solid state electrical device which gives a ”soft” boost to the compressor at each start-up.

Usage Guideline:

Suggested in installations with marginal power supply.

4. Crankcase Heater

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes the chance of liquid slugging.

Usage Guideline:

Required in low ambient cooling applications. Required in long line applications.

Suggested in all commercial applications.

5. Cycle Protector

The cycle protector is designed to prevent compressor short cycling. This control provides an approximate 5-minute delay after power to the compressor has been interrupted for any reason, including power outage, protector control trip, thermostat jiggling, or normal cycling.

6. Evaporator Freeze Thermostat

An SPST temperature-actuated switch that stops unit operation when evaporator reaches freeze-up conditions.

Usage Guideline:

Required when low ambient kit has been added.

7. High Pressure Switch

A high pressure switch that protects unit against excessive pressure. Usage Guideline:

Required in all heat pumps operated in dual fuel applications.

8. Isolation Relay

An SPDT relay which switches the low-ambient controller out of the outdoor fan motor circuit when the heat pump switches to heating mode.

Usage Guideline:

Required in all heat pumps where low ambient kit has been added.

9. Liquid-Line Solenoid Valve (LLS)

An electrically operated shutoff valve which stops and starts refrigerant liquid flow in response to compressor operation. It is to be installed at the outdoor unit to control refrigerant off cycle migration in the heating mode.

Usage Guideline:

An LLS is required in all long line heat pump applications to control refrigerant off cycle migration in the heating mode. See Long Line Guideline.

10. Low-Ambient Pressure Switch Kit

A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure within normal operating limits (approximately 100 psig to 225 psig). The control will maintain working head pressure at low-ambient temperatures down to 0_F/-17.78_C when properly installed.

Usage Guideline:

ALow-Ambient Pressure Switch or MotorMasterr Low-Ambient Controller must be used when cooling operation is used at outdoor temperatures below 55_F (12.8_C).

25HCR3C

5

Image 5
Contents 25HCR3C Industry Leading Features / BenefitsModel Number Nomenclature Standard FeaturesUnit SIZE---SERIES, Voltage Physical DataAccessories Accessory ThermostatsAccessory Usage Guideline MotorMasterr Low-Ambient Controller Charging Subcooling TXV-TYPE Expansion Device Electrical DataDimensions 25HCR3C Balance Point Worksheet Heat LOSS, Unit Integrated Heating CAPACITY, Mbtuh BuildingCombination Ratings TDR&TXV Indoor Model Capa Voltage Factory Standard30---30 CAR**3614A 28,600 FK4DNF003 42---30 36---30FK4DNB006 48---30 FK4DNF00560---30 25HCR318C Outdoor Section With FA4CNF,C018 Indoor Section Detailed Cooling Capacities25HCR324C Outdoor Section With FA4CNF,C024 Indoor Section Capacity MBtuh Total System Sens700 80025HCR330C Outdoor Section With FC4DNF030 Indoor Section Capacity Power Furnace Model875 100025HCR336C30 Outdoor Section With FC4DNF,B036 Indoor Section Cooling Indoor Model Capacity Power Furnace Model1050 12001225 25HCR342C Outdoor Section With FC4DNF,B042 Indoor Section1400 157525HCR348C30 Outdoor Section With FC4DNF,B048 Indoor Section Cooling Indoor Capa Power Furnace Model City1600 180025HCR360C30 Outdoor Section With FC4DNF,B060 Indoor Section Capacity MBtuh Total Sys System1750 2000FC4DNF018 FC4DNF024 FF1ENE018 FF1ENE024 FK4DNF001 FK4DNF002 Heat Pump Heating Performance25HCR318C Outdoor Section With FA4CNF,C018 Indoor Section FF1ENE030 25HCR324C Outdoor Section With FA4CNF,C024 Indoor SectionFC4DNF030 FK4DNF001 FK4DNF002 25HCR330C Outdoor Section With FC4DNF030 Indoor SectionFK4DNF002 FK4DNF003 25HCR336C30 Outdoor Section With FC4DNF,B036 Indoor SectionFK4DNB006 25HCR342C Outdoor Section With FC4DNF,B042 Indoor SectionFK4DNB006 FK4DNF005 25HCR348C30 Outdoor Section With FC4DNF,B048 Indoor Section25HCR360C30 Outdoor Section With FC4DNF,B060 Indoor Section Products Guide Specifications GeneralCatalog No 25HCR3C---2PD