Bryant 286A instruction manual Operating Ambient, Elevate Unit, Make Piping Connections

Page 3

Operating Ambient

The minimum outdoor operating ambient in cooling mode is 55_F/12.78_C without low ambient cooling enabled, and the maximum outdoor operating ambient in cooling mode is 125_F/51.67_C. On Evolution communicating systems only (for both 286A and 288A), low ambient cooling is available to 0_F/-17.78_C.

The maximum outdoor operating ambient in heating mode is 66°F/18.89_C on all models.

Elevate Unit

!CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Do not allow water and/or ice to build up in base pan.

Elevate unit per local climate and code requirements to provide clearance above estimated snowfall level and ensure adequate drainage of unit.

!CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Locate the unit in such a way that it is stable in all circumstances including adverse weather conditions.

In Long-Line Applications, Install Liquid-Line Solenoid Valve (LSV)

For refrigerant piping arrangements with equivalent lengths greater than 80 ft. (24.38 m) and/or when elevation difference between indoor and outdoor unit is greater than ±20 ft. (±6.10 m), follow all requirements of the Residential Piping and Longline Guideline. If required by Long-Line Guideline, install LSV kit, part no. KHALS0401LLS, specifically designed for PuronR refrigerant heat pumps. LSV should be installed within 2 ft. (0.61 m) of outdoor unit with flow arrow pointing toward outdoor unit. Follow the Installation Instructions included with accessory kit.

IMPORTANT: Flow arrow must point toward outdoor unit.

Make Piping Connections

!WARNING

PERSONAL INJURY AND UNIT DAMAGE

HAZARD

Failure to follow this warning could result in personal injury or death.

Relieve pressure and recover all refrigerant before system repair or final unit disposal. Use all service ports and open all flow-control devices, including solenoid valves.

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Do not leave system open to atmosphere any longer than minimum required for installation. POE oil in compressor is extremely susceptible to moisture absorption. Always keep ends of tubing sealed during installation.

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

If ANY refrigerant tubing is buried, provide a 6 in. vertical rise at service valve. Refrigerant tubing lengths up to 36 in. (914.4 mm) may be buried without further special consideration. Do not bury lines longer than 36 in. (914.4 mm).

Outdoor units may be connected to indoor section using accessory tubing package or field-supplied refrigerant grade tubing of correct size and condition. For tubing requirements beyond 80 ft. (24.38 m), substantial capacity and performance losses can occur. Following the recommendations in the Residential Piping and Longline Guideline will reduce these losses. Refer to Table 1 for field tubing diameters. Refer to Table 2 for accessory requirements.

Outdoor Unit Connected to Factory-Approved Indoor

Unit

Outdoor unit contains correct system refrigerant charge for operation with factory-approved, ARI-rated indoor unit with highest sales volume when connected by 15 ft. (4.57 m) of field-supplied or factory-accessory tubing, and factory-supplied filter drier. Check refrigerant charge for maximum efficiency.

286A / 288A

3

Image 3
Contents Electrical Shock Hazard Unit Operation and Safety HazardCUT Hazard Indoor Thermostat Control OptionsUnpack Unit Install on a Solid, Level Mounting PadCheck Equipment and Job Site Clearance RequirementsOutdoor Unit Connected to Factory-Approved Indoor Operating AmbientElevate Unit Make Piping ConnectionsLiquid Rated Vapor Unit Size Accessory UsageMake Electrical Connections Install Accessories Make Airflow SelectionsCompressor Crankcase Heater System Functions and Sequence of Operation Start-UpCrankcase Heater Operation One Minute Stage Change Time Delay on 286A ModelsTime Delays Compressor Operation on 286A ModelsLow Ambient Cooling DefrostEvolution Controlled low ambient cooling Check Charge Field Connections Pressure Switch ProtectionControl Fault Stage Control BoardCompressor Voltage Sensing 230V Line Power Disconnect DetectionUnloader Test Procedure Temperature ThermistorsThermistor Sensor Comparison Failed Thermistor Default OperationStatus Codes TroubleshootingEdge Thermidistat Models T6-PRH-01 or T6-NRH-01 Care and Maintenance Final ChecksPuronr R-410A Refrigerant Quick Reference Guide