Bryant 286A instruction manual Thermistor Sensor Comparison, Failed Thermistor Default Operation

Page 13

THERMISTOR CURVE

 

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(KOHMS)

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RESISTANCE

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

20

40

60

80

100

120

 

 

(-17.77)

(-6.67)

(4.44)

(15.56)

(26.67)

(37.78)

(48.89)

 

 

 

 

 

 

 

 

TEMPERATURE °F (°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A08054

Fig. 7 - Resistance Values Versus Temperature

If the outdoor air or coil thermistor should fail, the control will flash the appropriate fault code. (See Table 6.)

IMPORTANT: The outdoor air thermistor and coil thermistor

should be factory mounted in the final locations. Check to ensure thermistors are mounted properly per Fig. 8 and Fig. 9.

OAT Thermistor must be locked in place with spherical nib end facing to- wards the front of the control box

Fig. 8 - Outdoor Air Thermistor (OAT) Attachment

Thermistor Sensor Comparison

The control continuously monitors and compares the outdoor air temperature sensor and outdoor coil temperature sensor to ensure proper operating conditions. The comparison is:

SIn cooling if the outdoor air sensor indicates 10_F

(5.6_C) warmer than the coil sensor (or) the outdoor air

sensor indicates 20_F (11_C) cooler than the coil sensor, the sensors are out of range.

SIn heating if the outdoor air sensor indicates 35_F (

19.4_C) warmer than the coil sensor (or) the outdoor air sensor indicates 10_F (5.6_C) cooler than the coil sensor, the sensors are out of range.

If the sensors are out of range, the control will flash the appropriate fault code as shown in Table 6.

The thermistor comparison is not performed during low ambient cooling or defrost operation.

Failed Thermistor Default Operation

Factory defaults have been provided in the event of failure of

288A

(OCT).

outdoor air thermistor (OAT) and/or outdoor coil thermistor

 

If the OAT sensor should fail, low ambient cooling will not be

/

allowed and the one-minute outdoor fan off delay will not occur.

286A

Defrost will be initiated based on coil temperature and time.

If the OCT sensor should fail, low ambient cooling will not be

 

allowed. Defrost will occur at each time interval during heating

 

operation, but will terminate after 5 minutes.

 

If there is a thermistor out of range error, defrost will occur at each

 

time interval during heating operation, but will terminate after 5

 

minutes.

 

Count the number of short and long flashes to determine the

 

appropriate flash code. Table 6 gives possible causes and actions

 

related to each error.

 

OCT Thermistor

 

must be secured

 

tight on stub tube.

 

Fig. 9 - Outdoor Coil Thermistor (OCT) Attachment

Table 5 – Two-Stage Compressor Resistances

(Winding Resistance at 70_F±20_F / 21_C±11_C)

Winding

286A024

286A036

286A048

286A060

Start (S-C)

2.74

1.98

1.55

0.74

Run (R-C)

0.80

0.75

0.48

0.36

 

 

 

 

 

Winding

288A024

288A036

288A048

288A060

Start (S-C)

1.40

1.29

1.52

0.60

Run (R-C)

1.32

0.89

0.64

0.49

13

Image 13
Contents CUT Hazard Unit Operation and Safety HazardIndoor Thermostat Control Options Electrical Shock HazardCheck Equipment and Job Site Install on a Solid, Level Mounting PadClearance Requirements Unpack UnitElevate Unit Operating AmbientMake Piping Connections Outdoor Unit Connected to Factory-Approved IndoorLiquid Rated Vapor Unit Size Accessory UsageMake Electrical Connections Make Airflow Selections Install AccessoriesCompressor Crankcase Heater System Functions and Sequence of Operation Start-UpTime Delays One Minute Stage Change Time Delay on 286A ModelsCompressor Operation on 286A Models Crankcase Heater OperationDefrost Low Ambient CoolingEvolution Controlled low ambient cooling Check Charge Control Fault Pressure Switch ProtectionStage Control Board Field ConnectionsUnloader Test Procedure 230V Line Power Disconnect DetectionTemperature Thermistors Compressor Voltage SensingThermistor Sensor Comparison Failed Thermistor Default OperationStatus Codes TroubleshootingEdge Thermidistat Models T6-PRH-01 or T6-NRH-01 Final Checks Care and MaintenancePuronr R-410A Refrigerant Quick Reference Guide