Status Codes

Table 6 shows the status codes flashed by the amber status light. Most system problems can be diagnosed by reading the status code as flashed by the amber status light on the control board.

The codes are flashed by a series of short and long flashes of the status light. The short flashes indicate the first digit in the status code, followed by long flashes indicating the second digit of the error code.

The short flash is 0.25 seconds ON and the long flash is 1.0 second ON. Time between flashes is 0.25 seconds. Time between short flash and first long flash is 1.0 second. Time between code repeating is 2.5 seconds with LED OFF.

EXAMPLE:

3 short flashes followed by 2 long flashes indicates a 32 code. Table 6 shows this to be low pressure switch open.

286A / 288A

Table 6 – TROUBLESHOOTING

OPERATION

 

AMBER LED

 

FAULT

FLASH

POSSIBLE CAUSE AND ACTION

 

 

CODE

 

Standby – no call for unit operation

None

On solid, no

Normal operation

flash

 

 

 

Low Stage Cool/Heat Operation

None

1, pause

Normal operation

High Stage Cool/Heat Operation

None

2, pause

Normal operation

 

System Commu-

16

Communication with User Interface lost. Check wiring to UI, indoor and

 

nications Failure

 

outdoor units

 

Invalid Model Plug

25

Control does not detect a model plug or detects an invalid model plug. Unit

 

will not operate without correct model plug.

 

 

 

 

High Pressure

31*

High ---pressure switch trip. Check refrigerant charge, outdoor fan operation

 

Switch Open

and coils for airflow restrictions.

 

 

 

Low Pressure

32*

Low---pressure switch trip. Check refrigerant charge and indoor air flow.

 

Switch Open

 

 

 

 

Control Fault

45

Outdoor unit control board has failed. Control board needs to be replaced.

 

Brown Out (230 v)

46

Line voltage < 187v for at least 4 seconds. Compressor and fan operation

 

not allowed until voltage>190v. Verify line voltage.

 

 

 

 

 

 

There is no 230v at the contactor when indoor unit is powered and cooling/

 

No 230v at Unit

47

heating demand exists. Verify the disconnect is closed and 230v wiring is

 

 

 

connected to the unit.

 

Outdoor Air Temp

53

Outdoor air sensor not reading or out of range. Ohm out sensor and check

 

Sensor Fault

wiring.

 

 

 

Outdoor Coil

55

Coil sensor not reading or out of range. Ohm out sensor and check wiring.

 

Sensor Fault

 

 

 

 

Thermistors out of

56

Improper relationship between coil sensor and outdoor air sensor. Ohm out

 

range

sensors and check wiring.

 

 

 

Low Stage

 

Compressor operation detected then disappears while low stage demand

 

71*

exists. Possible causes are internal compressor overload trip or start relay

 

Thermal Cutout

 

 

and capacitor held in circuit too long (if installed).

 

 

 

 

High Stage

 

Compressor operation detected then disappears while high stage demand

 

72*

exists. Possible causes are internal compressor overload trip or start relay

 

Thermal Cutout

 

 

and capacitor held in circuit too long (if installed).

 

 

 

 

Contactor Shorted

73

Compressor voltage sensed when no demand for compressor operation

 

exists. Contactor may be stuck closed or there is a wiring error.

 

 

 

 

No 230V at

 

Compressor voltage not sensed when compressor should be starting. Con-

 

Compressor (288A

74

 

tactor may be stuck open or there is a wiring error.

 

Only)

 

 

 

 

 

Low Stage Did Not

 

Specified start voltage at VR terminal was not achieved in low stage. Start

 

Start

75

 

relay was de---energized after 1 second.

 

(286A Only)

 

 

 

 

 

Low Stage Did Not

 

For 3 consecutive low stage starts, the specified start voltage at VR terminal

 

Start 3 times (286A

76

was not achieved & start relay was de---energized. Low stage locked out for

 

Only)

 

30 minutes.

 

High Stage Did Not

 

Specified start voltage at VS terminal was not achieved in high stage. Start

 

Start

77

 

relay was de---energized after 1 second.

 

(286A Only)

 

 

 

 

 

High Stage Did Not

 

For 3 consecutive high stage starts, the specified start voltage at VS terminal

 

Start 3 times (286A

78

was not achieved & start relay was de---energized. High stage locked out for

 

Only)

 

30 minutes.

 

Low Stage

81

Thermal cutout occurs in three consecutive low/high stage cycles. Low

 

Thermal Lockout

stage locked out for 4 hours or until 24v power recycled.

 

 

 

High Stage

82

Thermal cutout occurs in three consecutive high/low stage cycles. High

 

Thermal Lockout

stage locked out for 4 hours or until 24v power recycled.

 

 

 

Low---Pressure

83

Low pressure switch trip has occurred during 3 consecutive cycles. Unit

 

Lockout

operation locked out for 4 hours or until 24v power recycled.

 

 

 

High ---Pressure

84

High pressure switch trip has occurred during 3 consecutive cycles. Unit

 

Lockout

operation locked out for 4 hours or until 24v power recycled.

 

 

 

Low Contactor

 

Compressor voltage not sensed when compressor should be starting. Low

 

Open

85

 

stage contactor may be stuck open or there is a wiring error.

 

(286A Only)

 

 

 

 

 

High Contactor

 

Compressor voltage not sensed when compressor should be starting. High

 

Open

87

 

stage contactor may be stuck open or there is a wiring error.

 

(286A Only)

 

 

 

 

*Sequence: Compressor contactor is de---energized and outdoor fan is energized for up to 15 minutes. If demand still exists, control will energize compressor contactor after 15 minute delay. If fault is cleared, unit will resume operation. If fault still exists, fan shuts off, and error code continues to flash. Control will attempt re---start every 15 minutes. Cycling low voltage defeats the 15 minute delay.

14

Image 14
Contents Indoor Thermostat Control Options Unit Operation and Safety HazardCUT Hazard Electrical Shock HazardClearance Requirements Install on a Solid, Level Mounting PadCheck Equipment and Job Site Unpack UnitMake Piping Connections Operating AmbientElevate Unit Outdoor Unit Connected to Factory-Approved IndoorAccessory Usage Liquid Rated Vapor Unit SizeMake Electrical Connections Compressor Crankcase Heater Install AccessoriesMake Airflow Selections Start-Up System Functions and Sequence of OperationCompressor Operation on 286A Models One Minute Stage Change Time Delay on 286A ModelsTime Delays Crankcase Heater OperationEvolution Controlled low ambient cooling Low Ambient CoolingDefrost Check Charge Stage Control Board Pressure Switch ProtectionControl Fault Field ConnectionsTemperature Thermistors 230V Line Power Disconnect DetectionUnloader Test Procedure Compressor Voltage SensingFailed Thermistor Default Operation Thermistor Sensor ComparisonTroubleshooting Status CodesEdge Thermidistat Models T6-PRH-01 or T6-NRH-01 Puronr R-410A Refrigerant Quick Reference Guide Care and MaintenanceFinal Checks