MAJOR COMPONENTS
2-Stage Control Board
The HP control board controls the following functions:
SHigh and low stage compressor contactor operation S Outdoor fan motor operation
S Reversing valve operation S Defrost operation
S Low ambient cooling
S Crankcase heater operation
S Compressor external protection S Pressure switch monitoring
S Time Delays
S On 286A models, high- and
Field Connections
On models with
On models with communicating system, use the ABCD Evolution connections.
Two Stage Compressor
The two stage compressor contains motor windings that provide
Compressor Internal Relief
The compressor is protected by an internal pressure relief (IPR) which relieves discharge gas into the compressor shell when differential between suction and discharge pressure exceeds
Compressor Control Contactors
The contactor(s) have a 24volt coil. The electronic control board controls the operation of the appropriate contactor.
TROUBLESHOOTING
Systems Communication Failure
If communication with the Evolution control is lost with the User Interface, the control will flash the appropriate fault code. (See Table 6.) Check the wiring to the UI and the indoor and outdoor units.
Model Plug
Each control board contains a model plug. The correct model plug must be installed for or the system to operate properly. (See Table 4.)
Table 4 – Model Plug Information
MODEL | MODEL PLUG | PIN RESISTANCE | ||
NUMBER | NUMBER |
|
| |
Pins | Pins | |||
|
| |||
|
|
|
| |
286A024 | HK70EZ002 | 5.1 | 18 | |
286A036 | HK70EZ004 | 5.1 | 33 | |
286A048 | HK70EZ006 | 5.1 | 51 | |
286A060 | HK70EZ008 | 5.1 | 75 | |
|
|
|
| |
288A024 | HK70EZ010 | 5.1 | 120 | |
288A036 | HK70EZ012 | 5.1 | 180 | |
288A048 | HK70EZ014 | 5.1 | 270 | |
288A060 | HK70EZ016 | 11 | 5.1 |
The model plug is used to identify the type and size of unit to the control. On 286A models, the model plug is also used to determine the start sequence timing for each individual model.
On new units, the model and serial numbers are input into the board’s memory at the factory. If a model plug is lost or missing at initial installation, the unit will operate according to the information input at the factory and the appropriate error code will flash temporarily. An RCD replacement board contains no model and serial information. If the factory control board fails, the model plug must be transferred from the original board to the replacement board for the unit to operate.
NOTE: The model plug takes priority over factory model information input at the factory. If the model plug is removed after initial power up, the unit will operate according to the last valid model plug installed, and flash the appropriate fault code temporarily.
Pressure Switch Protection
The outdoor unit is equipped with high- and
1.
2.Keep the outdoor fan operating for 15 minutes.
3.Display the appropriate fault code (see Table 6).
4.After a 15 minute delay, if there is a call for cooling or heat- ing and LPS or HPS is reset, the appropriate compressor contactor is energized.
5.If LPS or HPS has not closed after a 15 minute delay, the outdoor fan is turned off. If the open switch closes anytime after the 15 minute delay, then resume operation with a call for cooling or heating.
6.If LPS or HPS trips 3 consecutive cycles, the unit operation is locked out for 4 hours.
7.In the event of a
8.In the event of a
Control Fault
If the outdoor unit control board has failed, the control will flash the appropriate fault code (see Table 6). The control board should be replaced.
Brown-Out Protection
If the line voltage is less than 187v for at least 4 seconds, the appropriate compressor contactor and fan relay are
230v Brown-Out Protection Defeated
The brownout feature can be defeated if needed for severe noisy power conditions. This defeat should always be a last resort to solving the problem. Defeat is available on the User Interface setup screen (available with
The brownout toggle is accomplished by shorting the defrost pins from power up with the OAT and OCT sensor connector removed. After 3 seconds, the status of the force defrost short and the OAT/OCT as open will be checked. If correct, then the brownout will be toggled.
SStatus code 6 shows the brownout is disabled. S Status code 5 shows the brownout is active.
After the brownout defeat is set, power down and reinstall the OAT/OCT sensor and remove the short from the forced defrost pins. As long as the short on the forced defrost remains, the OAT
286A / 288A