604D--A Sequence of Operation
a. CONTINUOUS FAN
(1.) Thermostat closes circuit R to G energizing the blower motor for continuous fan.
b. COOLING MODE
(1.) If indoor temperature is above temperature set point, thermostat closes circuits R to G, R to Y and
Rto O-The unit delivers cooling airflow.
c.ELECTRIC HEATING MODE
(1.) Thermostat closes circuit R to W/W1, or W2 and R to G. There are no on or off delays.
d.HEAT PUMP HEATING MODE
(1.) Thermostat closes circuits R to G and R to Y. The compressor, indoor and outdoor fans are energized.
e.HEAT PUMP HEATING WITH AUXILIARY ELECTRIC HEAT
(1.) Thermostat closes circuits R to G, R to Y and R to W/W1 or W2. The compressor, indoor and outdoor fans are energized, as well as the electric heat relays.
f.DEFROST MODE
The defrost mode is automatically energized by the defrost board during heating mode. The defrost board energizes “O” (reversing valve) and “W2” (electric heat). It also de-energizes the outdoor fan. When defrost is complete, unit will return to heating mode. If room thermostat is satisfied during defrost, unit will shut down and restart in defrost on next call for heat.
Checking and Adjusting Refrigerant Charge
The refrigerant system is fully charged with Puron (R-410A) refrigerant and is tested and factory sealed.
NOTE: Adjustment of the refrigerant charge is not required unless the unit is suspected of not having the proper Puron (R-410A) charge.
A subcooling charging chart is attached to the inside of the compressor access panel (see Fig. 20). The chart includes the required liquid line temperature at given discharge line pressures and outdoor ambient temperatures.
An accurate thermocouple- or thermistor-type thermometer, and a gauge manifold are required when using the subcooling charging method for evaluating the unit charge. Do not use mercury or small dial-type thermometers because they are not adequate for this type of measurement.
NOTE: Allow system to operate for a minimum of 15 minutes before checking or adjusting refrigerant charge.
IMPORTANT: When evaluating the refrigerant charge, an indicated adjustment to the specified factory charge must always be very minimal. If a substantial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, such as insufficient airflow across either coil or both coils.
Proceed as follows:
1.Remove caps from low- and high-pressure service fittings.
2.Using hoses with valve core depressors, attach low- and high-pressure gauge hoses to low- and high-pressure service fittings, respectively.
3.Start unit and let run until system pressures stabilize.
4.Measure and record the following:
a.Outdoor ambient-air temperature (°F [°C] db).
b.Liquid line temperature (°F [°C]) at TXV.
c.Discharge (high-side) pressure (psig).
d.Suction (low-side) pressure (psig) (for reference only).
5.Using Cooling Charging Charts compare outdoor-air temperature (°F [°C] db) with the discharge line pressure
(psig) to determine desired system operating liquid line temperature (See Fig. 17).
6.Compare actual liquid line temperature with desired liquid line temperature. Using a tolerance of ±2°F (±1.1°C), add refrigerant if actual temperature is more than 2°F (1.1°C) higher than proper liquid line temperature, or remove refrigerant if actual temperature is more than 2°F (1.1°C) lower than required liquid line temperature.
NOTE: If the problem causing the inaccurate readings is a refrigerant leak, refer to Check for Refrigerant Leaks section.
Indoor Airflow and Airflow Adjustments
!CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in unit damage.
For cooling operation, the recommended airflow is 350 to 450 cfm for each 12,000 Btuh of rated cooling capacity. For heating operation, the airflow must produce a temperature rise that falls within the range stamped on the unit rating plate.
NOTE: Be sure that all supply-and return-air grilles are open, free from obstructions, and adjusted properly.
!WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect electrical power to the unit and install lockout tag before changing blower speed.
This unit has independent fan speeds for gas heating and cooling. In addition, this unit has the field-selectable capability to run two different cooling fan speeds: A normal cooling fan speed (350~400 CFM/Ton) and an enhanced dehumidification fan speed (As low as 320 CFM/Ton) for use with either a dehumidistat or a thermostat that supports dehumidification.
The cooling speed is marked “LOW” on the interface fan board (IFB) (See. Fig. 15) . The factory-shipped settings are noted in Table 4. There are 4 additional speed tap wires available for use in either electric heating or cooling (For color coding on the indoor fan motor leads, see Table 3). The additional 4 speed tap wires are shipped loose with vinyl caps and are located in the control box, near the interface fan board (IFB) (See Fig. 15).
Single Cooling Fan Speed Set-up (Dehumidification feature not used)
To change cooling speed:
1.Remove the vinyl cap off of the desired speed tap wire (Refer to Table 3 for color coding). Add the wet coil pressure drop in Table 5 to the system static to determine the correct cooling airflow speed in Table 4 that will deliver the nominal cooling airflow as listed in Table 1 for each size.
2.Remove the current speed tap wire from the “LOW” terminal on the interface fan board (IFB) (See Fig. 15) and place vinyl cap over the connector on the wire.
3.Connect the desired speed tap wire to the “LOW” terminal on the interface fan board (IFB).
NOTE: If accessory electric heat is installed, and the electric heat fan speed is chosen to be the same as the normal cooling fan speed, the dry airflow must meet or exceed the minimum airflow speed specified in Table 2 for the specific size unit.