Bryant 604D--A Provide for Condensate Disposal, Install Electrical Connections

Page 9

Step 6 — Provide for Condensate Disposal

NOTE: Ensure that condensate-water disposal methods comply with local codes, restrictions, and practices.

The 604D--A units dispose of condensate through a 3/4 in. NPT female fitting that exits on the compressor end of the unit. Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground level installations. Install a field-supplied 2-in. (51 mm) condensate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. (25

mm)lower than the drain-pan condensate connection to prevent the pan from overflowing. Prime the trap with water. When using a gravel apron, make sure it slopes away from the unit.

If the installation requires draining the condensate water away from the unit, install a field-supplied 2 -in. (51mm) trap at the condensate connection to ensure proper drainage. Condensate trap is available as an accessory or is field-supplied. Make sure that the outlet of the trap is at least 1 in. (25 mm) lower than the unit drain-pan condensate connection to prevent the pan from overflowing. Connect a drain trough using a minimum of field-supplied 3/4-in. PVC or field-supplied 3/4-in. copper pipe at outlet end of the 2-in. (51 mm) trap. (See Fig. 10) Do not

High-Voltage Connections

The unit must have a separate electrical service with a field-supplied, waterproof disconnect switch mounted at, or within sight from the unit. Refer to the unit rating plate, NEC and local codes for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing.

The field-supplied disconnect may be mounted on the unit over the high-voltage inlet hole when the standard power and low-voltage entry points are used. See Fig. 2 and 3 for acceptable location. Remove high voltage knockout.

See unit wiring label (Fig. 11-13) and Fig. 9 for reference when making high voltage connections. Proceed as follows to complete the high-voltage connections to the unit.

Single phase units:

1.Run the high-voltage (L1, L2) and ground lead into the control box.

2.Connect ground lead to chassis ground connection.

3.Locate the black and yellow wires connected to the line side of the contactor.

604D-- -- A

undersize the tube. Pitch the drain trough downward at a slope of at least 1 in. (25 mm) every 10 ft (3 m) of horizontal run. Be sure to check the drain trough for leaks. Prime the trap at the beginning of the cooling season start-up.

Step 7 — Install Electrical Connections

HIGH VOLTAGE POWER LEADS (SEE UNIT WIRING LABEL)

3-PHASE SHOWN

1-PHASE USES

TWO POWER

EQUIP GR

LEADS

CONTROL BOX

POWER

SUPPLY

FIELD-SUPPLIED FUSED DISCONNECT

UNIT COMPONENT DAMAGE HAZARD

Failure to follow this caution may result in damage to the unit being installed.

1.

Make all electrical connections in accordance with NEC

 

NFPA 70 (latest edition) and local electrical codes

 

governing such wiring. In Canada, all electrical

 

connections must be in accordance with CSA standard

 

C22.1 Canadian Electrical Code Part 1 and applicable

 

local codes. Refer to unit wiring diagram.

2.

Use only copper conductor for connections between

 

field-supplied electrical disconnect switch and unit. DO

LOW-VOLTAGE POWER LEADS (SEE UNIT)

WIRING LABEL

SPLICE BOX

WHT(W1)

W1

 

VIO (W2)

W2

 

YEL(Y)

Y

 

GRN(G)

G

 

RED(R)

R

 

BRN(C)

C

 

ORN(O)

O

 

BLU(DH)

DH

 

GRA(Y2)

3-Phase

 

 

Only

THERMOSTAT (TYPICAL)

 

NOT USE ALUMINUM WIRE.

3.

Be sure that high-voltage power to unit is within

 

operating voltage range indicated on unit rating plate. On

 

3-phase units, ensure phases are balanced within 2

 

percent. Consult local power company for correction of

 

improper voltage and/or phase imbalance.

4.

Do not damage internal components when drilling

 

through any panel to mount electrical hardware, conduit,

 

etc.

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

The unit cabinet must have an uninterrupted, unbroken electrical ground. This ground may consist of an electrical wire connected to the unit ground screw in the control compartment, or conduit approved for electrical ground when installed in accordance with NEC,NFPA 70 National Fire Protection Association (latest edition) (in Canada, Canadian Electrical Code CSA C22.1) and local electrical codes.

A09071

Fig. 9 - High- and Control-Voltage Connections

4.Connect field L1 to black wire on connection 11 of the compressor contactor.

5.Connect field wire L2 to yellow wire on connection 23 of the compressor contactor.

Three-phase units:

1.Run the high-voltage (L1, L2, L3) and ground lead into the control box.

2.Connect ground lead to chassis ground connection.

3.Locate the black and yellow wires connected to the line side of the contactor.

4.Connect field L1 to black wire on connection 11 of the compressor contactor.

5.Connect field wire L3 to yellow wire on connection 13 of the compressor contactor.

6.Connect field wire L2 to blue wire from compressor.

9

Image 9
Contents Safety Considerations Table of ContentsIntroduction Receiving and InstallationCheck Equipment Provide Unit SupportRig and Place Unit Unit Falling HazardProperty Damage Hazard 604D--A24-36 Unit Dimensions 604D--A42-60 Unit Dimensions CPRFCURB010A00 SizeCPRFCURB012A00 CPRFCURB013A00Select and Install Ductwork Corner Weights Small Cabinet Corner Weights Large CabinetRigging/Lifting of Unit See Fig Personal Injury and Electrical Operation Hazard Supply and Return Duct OpeningsProvide for Condensate Disposal Install Electrical ConnectionsHigh-Voltage Connections Unit Component Damage HazardAccessory Electric Heaters Installation Special Procedures for 208-V OperationControl Voltage Connections Standard ConnectionsMinimum Airflow for Reliable Electric Heater Operation CFM Physical Data Unit 604D--A604D a Cont. Ladder Wiring Schematics 208/230-1-60 Connection Wiring Schematics 208/230-3-60 Cont. Ladder Wiring Schematics 208/230-3-60 Connection Wiring Diagram Cont. Ladder Wiring Diagram START-UP Start-Up AdjustmentsCheck for Refrigerant Leaks Checking Cooling and Heating Control OperationIndoor Airflow and Airflow Adjustments Checking and Adjusting Refrigerant Charge604D--A Sequence of Operation Unit Operation HazardSingle Speed Cooling With Higher Electric Heat Speed Two Cooling Fan Speeds Set-up Dehumidification feature usedContinuous Fan Operation Color Coding for Indoor Fan Motor LeadsTypical Heat Pump Operation, Cooling Mode Maintenance Defrost ControlAir Filter Outdoor Fan Outdoor Coil, Indoor Coil, and Condensate Drain PanA24-60 Series a 604D--A Wet Coil Pressure Drop IN. W.CFilter Pressure Drop Table IN. W.C Cooling Charging Table-Subcooling Refrigerant Circuit Electrical Controls and WiringLoss of Charge Switch Pressure SwitchesHigh-Pressure Switch Copeland Scroll Compressor Puron RefrigerantTroubleshooting START-UP ChecklistSystem Information Puronr R-410A Quick Reference Guide Symptom Cause Remedy Troubleshooting ChartRemove and Store in Job Files TemperaturesPreliminary Information Model no III. START-UP Electrical Supply Voltage Compressor AmpsAccessories Vertical Economizer Factory Installed Option GeneralInstallation Small ChassisPart Number Filter Part NumberHood Divider Removed Economizer Hood Assembly Horizontal Return Duct Cover Panel and Hood Divider Removal Large ChassisLeft Hood Side Hood Assembly Supply AIR Temperature SAT SENSOR-The supply ConfigurationTemperature Economizer Standard Sensors11.7C 12.8C 14.4C 17.2C 20C 22.8C 25.6C Economizer Controller 604D-- -- a Economizer Wiring Diagram A10200 Cont. Ladder Wiring Diagram A10199 604D-- -- a 604D-- -- a CO2 Sensor Standard Settings CO2 Sensor Standard Settings Economizer Input/Output LogicOperation Troubleshooting 604D--A 30-36 3 Phase with Economizer 604D--A 42-60 3 Phase with Economizer

604D--A specifications

The Bryant 604D--A is a remarkable heating and cooling unit designed for both efficiency and performance, making it an ideal choice for homeowners seeking optimal climate control solutions. Its impressive array of features, technologies, and characteristics sets it apart in the HVAC market.

One of the standout features of the Bryant 604D--A is its advanced two-stage cooling system. This design allows the unit to adjust its cooling output based on the current temperature and humidity levels, which ensures a comfortable indoor environment while optimizing energy consumption. This two-stage operation is particularly beneficial during transitional seasons when temperatures fluctuate, providing a quieter operation and increased efficiency.

The Bryant 604D--A incorporates high-efficiency compressor technology that maximizes cooling capability while minimizing energy usage. This energy-efficient operation is further enhanced by its excellent SEER (Seasonal Energy Efficiency Ratio) rating. By achieving a high SEER rating, the 604D--A not only promotes energy savings but also contributes to lower utility bills, making it an economically sound investment for homeowners.

Another key characteristic of the Bryant 604D--A is its durable construction. Built with quality materials, this unit is designed to withstand varying weather conditions, ensuring longevity and reliable performance over the years. Its robust design also minimizes vibrations and noise, making it a quieter option compared to many competing systems.

Smart technology integration is also a significant highlight of the Bryant 604D--A. It features wireless connectivity, allowing users to control their heating and cooling settings remotely through a smartphone app. This modern convenience enables homeowners to adjust their indoor climate on-the-go, enhancing user comfort and convenience.

Additionally, the Bryant 604D--A is equipped with an advanced filtration system that helps to improve indoor air quality. By capturing dust, pollen, and other particles, this filtration system ensures that the air circulating within the home remains clean and healthy.

In conclusion, the Bryant 604D--A is a high-performance HVAC unit that excels in energy efficiency, durability, and convenience. With its advanced technology, quiet operation, and user-friendly features, it stands as a premier choice for those looking to elevate their home comfort while maintaining cost-effectiveness and sustainability. Whether for new installations or as a replacement for an outdated system, the Bryant 604D--A is undoubtedly a leader in modern climate control solutions.