Bryant 604D--A installation instructions Economizer Controller

Page 41

12

CONTROL

CURVE

A

B

C

D

18 16 14

CONTROL POINT

 

 

 

 

 

 

 

 

 

APPROX ˚F (˚C)

 

 

 

 

 

 

 

 

 

 

AT 50% RH

 

 

 

 

 

 

 

 

 

 

 

73 (23)

 

 

 

 

 

 

 

 

 

 

 

70 (21)

 

 

 

 

 

 

 

 

 

 

 

67 (19)

 

 

 

 

 

 

 

 

 

 

 

63 (17)

 

 

 

 

 

 

 

 

DRY

 

 

 

 

 

 

 

POUND

 

 

 

 

 

 

 

34

 

 

 

 

 

 

 

PER

 

 

 

 

 

 

 

 

 

32

 

 

 

 

 

 

 

 

 

BTU

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26

 

 

 

 

 

 

 

 

 

 

 

 

ENTHALPY

 

 

 

 

 

 

 

 

 

 

 

24

 

 

 

 

 

 

 

 

 

 

 

 

22

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

 

 

 

 

 

 

 

 

 

 

 

(13)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

(10)

 

 

C

 

 

 

 

 

45

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

(7)

 

 

 

 

 

 

 

 

 

40

 

 

 

 

 

 

 

 

 

 

 

 

(4)

 

 

 

 

 

 

 

 

 

 

 

35

 

 

 

 

 

 

 

 

 

 

 

 

 

(2)

 

 

 

 

 

 

 

 

 

 

 

 

40

AIR

38

36

 

65

(18)

60

(16)

A

B

 

 

46

 

 

44

 

 

42

 

 

80

 

 

(27)

 

 

75

 

 

 

(24)

 

70

 

 

(21)

 

 

100

90

80

 

 

 

 

 

70

 

 

 

 

 

 

60

D C B

85

90

95

100

105

110

(29)

(32)

(25)

(38)

(41)

(43)

HUMIDITY

(%)

 

RELATIVE

 

50 40

30

20

10

A

N1

 

EXH

TR

N

 

Set

 

2V

10V

 

 

 

P1

EXH

 

24

 

 

Vac

 

 

 

P

 

Min

HOT

T1

 

Pos

 

 

 

 

T

 

Open

 

 

 

 

 

 

DCV

1

 

 

Max

 

 

 

 

2V

10V

 

AQ+

DCV

 

 

 

 

 

AQ

 

DCV

 

SO+

 

Set

3

 

 

 

SO

2V

10V

 

 

 

 

SR+

Free

 

EF

Cool

 

 

 

 

 

SR

B

C

 

 

 

 

 

A

D

 

Fig. 43 - Economizer Controller

TR1

24Vac

COM

2

5

4

EF1

A09712

604D-- -- A

35

40

45

50

55

60

65

70

75

80

85

90

95

100

105

110

(2)(4) (7) (10) (13) (16) (18) (21) (24) (27) (29) (32) (36) (38) (41) (43)

APPROXIMATE DRY BULB TEMPERATURE — ˚F (˚C)

A09711

Fig. 41 - Enthalpy Changeover Setpoints

6000

 

 

 

 

 

 

5000

 

 

 

 

 

 

4000

 

 

 

 

 

800 ppm

 

 

 

 

 

 

3000

 

 

 

 

 

900 ppm

 

 

 

 

 

1000 ppm

 

 

 

 

 

 

2000

 

 

 

 

 

1100 ppm

 

 

 

 

 

 

1000

 

 

 

 

 

 

0

 

 

 

 

 

 

2

3

4

5

6

7

8

 

 

 

 

 

 

A09713

Fig. 42 - CO2 Sensor Maximum Range Setting

OUTDOOR ENTHALPY CHANGEOVER—For enthalpy control, accessory enthalpy sensor (part number HH57AC078) is required. Replace the standard outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location.

When the outdoor air enthalpy rises above the outdoor enthalpy changeover set point, the outdoor-air damper moves to its minimum position. The outdoor enthalpy changeover set point is set with the outdoor enthalpy set point potentiometer on the Economizer controller. The set points are A, B, C, and D. See Fig.

41.The factory-installed 620-ohm jumper must be in place across terminals SR and SR+ on the Economizer controller. See Fig. 43 and Fig. 44.

DIFFERENTIAL ENTHALPY CONTROL — For differential enthalpy control, the Economizer controller uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return airstream. The Economizer controller compares the outdoor air enthalpy to the return air enthalpy to determine Economizer use. The controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when the outdoor air has a lower enthalpy than the return air and is below the set point, the Economizer opens to bring in outdoor air for free cooling. Replace the standard outside air dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. Mount the return air enthalpy sensor in the return air duct. See Fig. 40. When using this mode of changeover control, turn the enthalpy set point poten- tiometer fully clockwise to the D setting.

INDOOR AIR QUALITY (IAQ) SENSOR INPUT The IAQ input can be used for demand control ventilation control based on the level of CO2 measured in the space or return air duct. Mount the accessory IAQ sensor according to manufacturer specifications. The IAQ sensor should be wired to the AQ and AQ1 terminals of the controller. Adjust the DCV potentiometers to correspond to the DCV voltage output of the indoor air quality sensor at the user determined set point. See Fig. 42. If a separate field-supplied transformer is used to power the IAQ sensor, the sensor must not be grounded or the Economizer control board will be damaged.

EXHAUST SET POINT ADJUSTMENT—The exhaust set point will determine when the exhaust fan runs based on damper position (if power exhaust is installed). The set point is modified with the Exhaust Fan Set Point (EXH SET) potentiometer. See Fig. 44 for Wiring Diagram. The set point represents the damper position above which the exhaust fans will be turned on. When there is a call for exhaust, the Economizer controller provides a 45 ±15 second delay before exhaust fan activation to allow the dampers to open. This delay allows the damper to reach the appropriate position to avoid unnecessary fan overload.

MINIMUM POSITION CONTROL — There is a minimum damper position potentiometer on the Economizer controller. See Fig. 38 and 44. The minimum damper position maintains the minimum airflow into the building during the occupied period. When using demand ventilation, the minimum damper position represents the minimum ventilation position for VOC (volatile organic compound) ventilation requirements. The DCV Max potentiometer must be fully closed (CCW) to allow the Minimum Position potentiometer to function correctly.

41

Image 41
Contents Safety Considerations Table of ContentsIntroduction Receiving and InstallationCheck Equipment Provide Unit SupportProperty Damage Hazard Rig and Place UnitUnit Falling Hazard 604D--A24-36 Unit Dimensions 604D--A42-60 Unit Dimensions CPRFCURB010A00 SizeCPRFCURB012A00 CPRFCURB013A00Rigging/Lifting of Unit See Fig Select and Install DuctworkCorner Weights Small Cabinet Corner Weights Large Cabinet Personal Injury and Electrical Operation Hazard Supply and Return Duct OpeningsProvide for Condensate Disposal Install Electrical ConnectionsHigh-Voltage Connections Unit Component Damage HazardAccessory Electric Heaters Installation Special Procedures for 208-V OperationControl Voltage Connections Standard ConnectionsMinimum Airflow for Reliable Electric Heater Operation CFM Physical Data Unit 604D--A604D a Cont. Ladder Wiring Schematics 208/230-1-60 Connection Wiring Schematics 208/230-3-60 Cont. Ladder Wiring Schematics 208/230-3-60 Connection Wiring Diagram Cont. Ladder Wiring Diagram START-UP Start-Up AdjustmentsCheck for Refrigerant Leaks Checking Cooling and Heating Control OperationIndoor Airflow and Airflow Adjustments Checking and Adjusting Refrigerant Charge604D--A Sequence of Operation Unit Operation HazardSingle Speed Cooling With Higher Electric Heat Speed Two Cooling Fan Speeds Set-up Dehumidification feature usedContinuous Fan Operation Color Coding for Indoor Fan Motor LeadsTypical Heat Pump Operation, Cooling Mode Air Filter MaintenanceDefrost Control Outdoor Fan Outdoor Coil, Indoor Coil, and Condensate Drain PanFilter Pressure Drop Table IN. W.C A24-60 Series a604D--A Wet Coil Pressure Drop IN. W.C Cooling Charging Table-Subcooling Refrigerant Circuit Electrical Controls and WiringLoss of Charge Switch Pressure SwitchesHigh-Pressure Switch Copeland Scroll Compressor Puron RefrigerantSystem Information TroubleshootingSTART-UP Checklist Puronr R-410A Quick Reference Guide Symptom Cause Remedy Troubleshooting ChartRemove and Store in Job Files TemperaturesPreliminary Information Model no III. START-UP Electrical Supply Voltage Compressor AmpsAccessories Vertical Economizer Factory Installed Option GeneralInstallation Small ChassisPart Number Filter Part NumberHood Divider Removed Economizer Hood Assembly Horizontal Return Duct Cover Panel and Hood Divider Removal Large ChassisLeft Hood Side Hood Assembly Supply AIR Temperature SAT SENSOR-The supply ConfigurationTemperature Economizer Standard Sensors11.7C 12.8C 14.4C 17.2C 20C 22.8C 25.6C Economizer Controller 604D-- -- a Economizer Wiring Diagram A10200 Cont. Ladder Wiring Diagram A10199 604D-- -- a 604D-- -- a Operation CO2 Sensor Standard SettingsCO2 Sensor Standard Settings Economizer Input/Output Logic Troubleshooting 604D--A 30-36 3 Phase with Economizer 604D--A 42-60 3 Phase with Economizer

604D--A specifications

The Bryant 604D--A is a remarkable heating and cooling unit designed for both efficiency and performance, making it an ideal choice for homeowners seeking optimal climate control solutions. Its impressive array of features, technologies, and characteristics sets it apart in the HVAC market.

One of the standout features of the Bryant 604D--A is its advanced two-stage cooling system. This design allows the unit to adjust its cooling output based on the current temperature and humidity levels, which ensures a comfortable indoor environment while optimizing energy consumption. This two-stage operation is particularly beneficial during transitional seasons when temperatures fluctuate, providing a quieter operation and increased efficiency.

The Bryant 604D--A incorporates high-efficiency compressor technology that maximizes cooling capability while minimizing energy usage. This energy-efficient operation is further enhanced by its excellent SEER (Seasonal Energy Efficiency Ratio) rating. By achieving a high SEER rating, the 604D--A not only promotes energy savings but also contributes to lower utility bills, making it an economically sound investment for homeowners.

Another key characteristic of the Bryant 604D--A is its durable construction. Built with quality materials, this unit is designed to withstand varying weather conditions, ensuring longevity and reliable performance over the years. Its robust design also minimizes vibrations and noise, making it a quieter option compared to many competing systems.

Smart technology integration is also a significant highlight of the Bryant 604D--A. It features wireless connectivity, allowing users to control their heating and cooling settings remotely through a smartphone app. This modern convenience enables homeowners to adjust their indoor climate on-the-go, enhancing user comfort and convenience.

Additionally, the Bryant 604D--A is equipped with an advanced filtration system that helps to improve indoor air quality. By capturing dust, pollen, and other particles, this filtration system ensures that the air circulating within the home remains clean and healthy.

In conclusion, the Bryant 604D--A is a high-performance HVAC unit that excels in energy efficiency, durability, and convenience. With its advanced technology, quiet operation, and user-friendly features, it stands as a premier choice for those looking to elevate their home comfort while maintaining cost-effectiveness and sustainability. Whether for new installations or as a replacement for an outdated system, the Bryant 604D--A is undoubtedly a leader in modern climate control solutions.