Bryant 604D--A installation instructions Check for Refrigerant Leaks, Start-Up Adjustments

Page 18

604D-- -- A

PRE-START-UP

!WARNING

FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury, death or property damage.

1.Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system.

2.Relieve and recover all refrigerant from system before touching or disturbing compressor plug if refrigerant leak is suspected around compressor terminals.

3.Do not remove compressor plug until all electrical sources are disconnected and tagged.

4.Never attempt to repair soldered connection while refrigerant system is under pressure.

5.Do not use torch to remove any component. System contains oil and refrigerant under pressure.

To remove a component, wear protective goggles and proceed as follows:

a.Shut off electrical power to unit and install lockout tag.

b.Relieve and reclaim all refrigerant from system using both high- and low-pressure ports.

c.Cut component connecting tubing with tubing cutter and remove component from unit.

d.Carefully unsweat remaining tubing stubs when necessary. Oil can ignite when exposed to torch flame.

Use the Start-Up Checklist supplied at the end of this book and proceed as follows to inspect and prepare the unit for initial start-up:

1.Remove all access panels (see Fig. 20).

2.Read and follow instructions on all DANGER, WARNING, CAUTION, and INFORMATION labels attached to, or shipped with, unit.

3.Make the following inspections:

a.Inspect for shipping and handling damages such as broken lines, loose parts, disconnected wires, etc.

b.Inspect for oil at all refrigerant tubing connections and on unit base. Detecting oil generally indicates a refrigerant leak. Leak-test all refrigerant tubing connections using electronic leak detector, or liquid-soap solution. If a refrigerant leak is detected, see following Check for Refrigerant Leaks section.

c.Inspect all field and factory-wiring connections. Be sure that connections are completed and tight. Ensure wires do not touch refrigerant tubing or sharp sheet metal edges.

d.Inspect coil fins. If damaged during shipping and handling, carefully straighten fins with a fin comb.

4.Verify the following conditions:

a.Make sure that outdoor-fan blade is correctly positioned in fan orifice.

b.Make sure that air filter(s) is in place.

c.Make sure that condensate drain pan and trap are filled with water to ensure proper drainage.

d.Make sure that all tools and miscellaneous loose parts have been removed.

5.Each unit system has 2 Schrader-type ports, one low-side Schrader fitting located on the suction line, and one high-side Schrader fitting located on the compressor discharge line. Be sure that caps on the ports are tight.

START-UP

Checking Cooling and Heating Control Operation

Start and check the unit for proper control operation as follows:

(1.) Place room thermostat SYSTEM switch or MODE control in OFF position. Observe that blower motor starts when FAN mode is placed in FAN ON position and shuts down when FAN MODE switch is placed in AUTO position.

(2.) Thermostat:

When the room temperature rises to a point that is slightly above the cooling control setting of the thermostat, the thermostat completes the circuit between thermostat terminal R to terminals Y, O and G.These completed circuits through the thermostat connect contactor coil (C) (through unit wire Y) and Indoor Fan board (through unit wire

G)across the 24-v. secondary of transformer (TRAN).

(3.) Place system switch or MODE control in HEAT position. Set control above room temperature. Observe that compressor, outdoor fan, and indoor blower motors start. Observe that heating cycle shuts down when control setting is satisfied.

(4.) When using an automatic changeover room thermostat place both SYSTEM or MODE control and FAN mode switches in AUTO positions. Observe that unit operates in Cooling mode when temperature control is set to “call for Cooling” (below room temperature), and unit operates in Heating mode when temperature control is set to “call for Heating” (above room temperature).

NOTE: Once the compressor has started and then has stopped, it should not be started again until 5 minutes have elapsed. The defrost board has a built-in 5 minute delay between cycles. The 5 minute compressor delay also applies to heat pump heating mode.

Step 1 — Check for Refrigerant Leaks

Proceed as follows to locate and repair a refrigerant leak and to charge the unit:

1.Locate leak and make sure that refrigerant system pressure has been relieved and reclaimed from both high- and low-pressure ports.

2.Repair leak following Refrigerant Service procedures. NOTE: Install a bi-flow filter drier whenever the system has been opened for repair.

3.Add a small charge of R-410A refrigerant vapor to system and leak-test unit.

4.Recover refrigerant from refrigerant system and evacuate to 500 microns if no additional leaks are not found.

5.Charge unit with Puron (R-410A) refrigerant, using an electronic scale. Refer to unit rating plate for required charge.

Step 2 — Start-Up Adjustments

Complete the required procedures given in the Pre-Start-Up section before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the unit in Cooling mode when the outdoor temperature is below 40_F (4_C) (unless accessory low-ambient kit is installed).

IMPORTANT: Three-phase, scroll compressors are direction oriented. Unit must be checked to ensure proper compressor 3-phase power lead orientation. If not corrected within 5 minutes, the internal protector will shut off the compressor. The 3-phase power leads to the unit must be reversed to correct rotation. When turning backwards, the difference between compressor suction and discharge pressures may be near zero.

18

Image 18
Contents Table of Contents Safety ConsiderationsCheck Equipment Receiving and InstallationIntroduction Provide Unit SupportRig and Place Unit Unit Falling HazardProperty Damage Hazard 604D--A24-36 Unit Dimensions 604D--A42-60 Unit Dimensions CPRFCURB012A00 SizeCPRFCURB010A00 CPRFCURB013A00Select and Install Ductwork Corner Weights Small Cabinet Corner Weights Large CabinetRigging/Lifting of Unit See Fig Supply and Return Duct Openings Personal Injury and Electrical Operation HazardHigh-Voltage Connections Install Electrical ConnectionsProvide for Condensate Disposal Unit Component Damage HazardControl Voltage Connections Special Procedures for 208-V OperationAccessory Electric Heaters Installation Standard ConnectionsPhysical Data Unit 604D--A Minimum Airflow for Reliable Electric Heater Operation CFM604D a Cont. Ladder Wiring Schematics 208/230-1-60 Connection Wiring Schematics 208/230-3-60 Cont. Ladder Wiring Schematics 208/230-3-60 Connection Wiring Diagram Cont. Ladder Wiring Diagram Check for Refrigerant Leaks Start-Up AdjustmentsSTART-UP Checking Cooling and Heating Control Operation604D--A Sequence of Operation Checking and Adjusting Refrigerant ChargeIndoor Airflow and Airflow Adjustments Unit Operation HazardContinuous Fan Operation Two Cooling Fan Speeds Set-up Dehumidification feature usedSingle Speed Cooling With Higher Electric Heat Speed Color Coding for Indoor Fan Motor LeadsTypical Heat Pump Operation, Cooling Mode Maintenance Defrost ControlAir Filter Outdoor Coil, Indoor Coil, and Condensate Drain Pan Outdoor FanA24-60 Series a 604D--A Wet Coil Pressure Drop IN. W.CFilter Pressure Drop Table IN. W.C Cooling Charging Table-Subcooling Electrical Controls and Wiring Refrigerant CircuitHigh-Pressure Switch Pressure SwitchesLoss of Charge Switch Copeland Scroll Compressor Puron RefrigerantTroubleshooting START-UP ChecklistSystem Information Puronr R-410A Quick Reference Guide Troubleshooting Chart Symptom Cause RemedyPreliminary Information Model no TemperaturesRemove and Store in Job Files III. START-UP Electrical Supply Voltage Compressor AmpsInstallation Vertical Economizer Factory Installed Option GeneralAccessories Small ChassisFilter Part Number Part NumberHood Divider Removed Economizer Hood Assembly Large Chassis Horizontal Return Duct Cover Panel and Hood Divider RemovalLeft Hood Side Hood Assembly Temperature ConfigurationSupply AIR Temperature SAT SENSOR-The supply Economizer Standard Sensors11.7C 12.8C 14.4C 17.2C 20C 22.8C 25.6C Economizer Controller 604D-- -- a Economizer Wiring Diagram A10200 Cont. Ladder Wiring Diagram A10199 604D-- -- a 604D-- -- a CO2 Sensor Standard Settings CO2 Sensor Standard Settings Economizer Input/Output LogicOperation Troubleshooting 604D--A 30-36 3 Phase with Economizer 604D--A 42-60 3 Phase with Economizer

604D--A specifications

The Bryant 604D--A is a remarkable heating and cooling unit designed for both efficiency and performance, making it an ideal choice for homeowners seeking optimal climate control solutions. Its impressive array of features, technologies, and characteristics sets it apart in the HVAC market.

One of the standout features of the Bryant 604D--A is its advanced two-stage cooling system. This design allows the unit to adjust its cooling output based on the current temperature and humidity levels, which ensures a comfortable indoor environment while optimizing energy consumption. This two-stage operation is particularly beneficial during transitional seasons when temperatures fluctuate, providing a quieter operation and increased efficiency.

The Bryant 604D--A incorporates high-efficiency compressor technology that maximizes cooling capability while minimizing energy usage. This energy-efficient operation is further enhanced by its excellent SEER (Seasonal Energy Efficiency Ratio) rating. By achieving a high SEER rating, the 604D--A not only promotes energy savings but also contributes to lower utility bills, making it an economically sound investment for homeowners.

Another key characteristic of the Bryant 604D--A is its durable construction. Built with quality materials, this unit is designed to withstand varying weather conditions, ensuring longevity and reliable performance over the years. Its robust design also minimizes vibrations and noise, making it a quieter option compared to many competing systems.

Smart technology integration is also a significant highlight of the Bryant 604D--A. It features wireless connectivity, allowing users to control their heating and cooling settings remotely through a smartphone app. This modern convenience enables homeowners to adjust their indoor climate on-the-go, enhancing user comfort and convenience.

Additionally, the Bryant 604D--A is equipped with an advanced filtration system that helps to improve indoor air quality. By capturing dust, pollen, and other particles, this filtration system ensures that the air circulating within the home remains clean and healthy.

In conclusion, the Bryant 604D--A is a high-performance HVAC unit that excels in energy efficiency, durability, and convenience. With its advanced technology, quiet operation, and user-friendly features, it stands as a premier choice for those looking to elevate their home comfort while maintaining cost-effectiveness and sustainability. Whether for new installations or as a replacement for an outdated system, the Bryant 604D--A is undoubtedly a leader in modern climate control solutions.