Envision Peripherals Geothermal Indoor Split Heat Pumps installation manual Refrigeration

Page 22

ENVISION SERIES INSTALLATION MANUAL

Refrigeration

The Envision series comes with a holding charge. The charge must be adjusted in the field based on performance. Refrigeration piping on the split consists of installing a brazed copper line set between the blower coil unit and the unit’s split compressor section. To select the proper tube diameters for the installation, refer to the table on page 9. Line sets over 60 feet long are not recommended because of oil return and pressure drop problems. The suction line must always be insu- lated. Handle and route the line sets carefully to avoid kinking or bending the tubes. If the line set is kinked or distorted and it cannot be formed back into its original shape, the bad portion of the pipe should be replaced. A restricted line set will affect the performance of the system.

Connection to Air Coil

Figures 1 and 2 illustrate typical Envision Split installations. The table on page 9 shows typical lineset diameters and maximum length. As in all R-410A equipment, a reversible liquid line filter drier is required to insure all moisture is removed from the system. This drier should be replaced whenever “breaking into” the system for service. All linesets should be insulated with a minimum of 1/2” closed cell insulation. All insulation should be painted with UV resistant paint or covering to insure long insulation life.

Fasten the copper line set to the blower coil unit as instructed by the coil installation instructions shown in Figure 14. Nitrogen should be bled through the system at 2 to 3 PSI to prevent oxidation inside the refrigerant tubing. Use a low silver phos-copper braze alloy on all brazed connections.

Braze line set to the service valve stubs on the inside front of the split cabinet as shown in Figure

Figure 13: Typical Split System Refrigerant Line Connections

13. Nitrogen should be bled through the system at

2 to 3 PSI to prevent oxidation contamination. Use

a low silver phos-copper braze alloy on all brazed

Service ports for attaching refrigerant gauges

Insulated

connections. Envision split units are shipped with

a factory charge and service valves are not to be

opened until the line set has been leak tested,

purged and evacuated. Schrader cores should be

removed before brazing. A heat sink should be used

on the service valves and TXV to prevent damage

caused by excessive heat.

Figure 14: Attaching the Air Coil

TXV ("IN" toward condensing unit)

Equalizer Bulb

Suction

Liquid

TXV has internal check valve

Suction Line

Replace caps after

ccw

 

opening system

 

ccw

Braze

Connection

Liquid

Line

Position

Description

System

Service

Port

 

 

 

 

 

 

 

CW - Full In

Shipping Position

Closed

Open

 

 

 

 

CCW - Full Out 1/2 turn CW

Service Position

Open

Open

 

 

 

 

CCW - Full Out

Operation Position

Open

Closed

 

 

 

 

22

Image 22
Contents Envision Series Geothermal Indoor Split Heat Pumps 410A Refrigerant Ton Single Speed Ton Dual CapacityPhysical Characteristics Model NomenclatureTable of Contents General Installation Information Equipment Selection Utilizing Existing Coil or Air HandlerAir Handler Installation Connection to Air CoilDual Fuel Systems Water Piping Swivel Connections Residential UnitsEnvision Matching Air Coil Surface Air Handler Coil DataLine Set Sizes Rows TubeOpen Loop Well Water Systems Solenoid ValveSolenoid Wiring Water QualityClosed Loop Ground Source Systems Multiple Units on One Flow CenterDesuperheater Connections Water Tank PreparationPlumbing Installation Desuperheater StartupGeneral Thermostat WiringElectrical Electrical DataWiring Schematics 24V Accessory relay see SW2 3 for description of operationHp Total Microprocessor Control Fan G only Cooling OperationLockout Conditions Operation Logic Data STG1 STG2 STG3 Emerg Single Speed UnitsDIP Switch Settings Freeze Sensing SettingPosition Description System Service RefrigerationInitial System Charge Calculation Leak TestingSystem Evacuation Charging the SystemDetermining Subcooling Pressure/Temperature Coversion Chart for R-410A Unit Operating Parameters Single Speed ModelsDual Capacity Models Unit Startup Before Powering Unit, Check The FollowingStartup Steps Final Evaluation Unit Startup/Troubleshooting Heating Cycle AnalysisSingle Speed Pressure Drop and Recommended Flow RatesDual Capacity Standard Microprocessor Controls TroubleshootingLED Definitions and Diagnostics Refrigerant SystemsPreventive Maintenance Replacement ProceduresPhysical Dimensions Envision NZ Split Dimensional DataInstallation Notes

Geothermal Indoor Split Heat Pumps specifications

Envision Peripherals has established itself as a leader in the energy-efficient heating and cooling market with its advanced geothermal indoor split heat pumps. These systems are designed to utilize the earth's stable underground temperature as a renewable energy source, resulting in remarkable performance and sustainability.

One of the main features of Envision Peripherals geothermal indoor split heat pumps is their exceptional energy efficiency. With the ability to achieve a coefficient of performance (COP) exceeding 4.0, these heat pumps provide four units of heating or cooling for every unit of electricity consumed. This level of efficiency significantly reduces operational costs and lowers environmental impact, making them an ideal choice for eco-conscious consumers.

The technology employed in these systems emphasizes reliability and flexibility. The heat pumps are equipped with variable speed compressors, allowing them to adjust the heating and cooling output based on the current demands of the space. This results in consistent indoor temperatures and enhanced comfort. Moreover, the systems can seamlessly integrate with existing HVAC infrastructures, offering versatile installation options for residential and commercial applications.

Another characteristic that sets Envision Peripherals geothermal systems apart is their dual functionality. These units not only provide heating during the colder months but also excel in cooling during hot weather conditions. The geothermal heat pumps extract heat from the indoor air and transfer it to the ground, ensuring an efficient cooling process without the need for traditional air conditioning systems.

Durability and low maintenance are key aspects of Envision Peripherals heat pumps. Constructed with high-quality materials and advanced engineering, these systems are built to withstand varying environmental conditions. They feature a closed-loop system that minimizes wear and tear, reducing the frequency of repairs and providing homeowners and businesses with peace of mind.

In addition, Envision Peripherals emphasizes eco-friendliness. The use of renewable geothermal energy diminishes dependence on fossil fuels, contributing to a more sustainable living and working environment. Their commitment to sustainability aligns with global efforts to reduce greenhouse gas emissions and combat climate change.

In summary, Envision Peripherals geothermal indoor split heat pumps deliver exemplary energy efficiency, advanced technology, and a range of benefits, including dual functionality and reduced environmental impact. As the demand for sustainable heating and cooling solutions continues to grow, these systems represent a leading choice for consumers seeking comfort and energy savings.