ENVISION SERIES INSTALLATION MANUAL
DIP Switch Settings
DIP SWITCH | DESCRIPTION | OFF POSITION | ON POSITION | ||
NUMBER | |||||
|
|
| |||
|
|
|
|
| |
SW1 | N/A | NOT USED | N/A | N/A | |
|
|
|
|
| |
|
| Service/Test Mode - Allows control of “NORM” or “TEST” opera- |
|
| |
| 1 | tional modes. Test mode accelerates most timing functions 16 | Test | Norm | |
| times to allow faster troubleshooting. Test mode also allows view- | ||||
|
|
|
| ||
|
| ing the “CURRENT” status of the fault inputs on the LED display. |
|
| |
|
|
|
|
| |
|
| Freeze Sensing Setting |
|
| |
| 2 | Allows field selection of freeze thermistor fault sensing tempera- | Loop | Well | |
| tures for well water (30°F) or | (Protection 15° F) | (Protection 30° F) | ||
|
| ||||
|
| loops. |
|
| |
|
|
|
|
| |
|
| Accessory Relay |
|
| |
| 3 | Allows field selection of the accessory relay to operate with the | Fan | Comp | |
|
| compressor or fan. |
|
| |
|
|
|
|
| |
SW2 | 4 | NOT USED | N/A | N/A | |
|
|
|
| ||
5 | NOT USED | N/A | N/A | ||
| |||||
|
|
|
|
| |
|
| Input Diagnostics - Allows viewing the inputs from the thermo- | Diagnostic Inputs | Normal Display | |
| 6 | stat to the control board such as Y1, Y2, O, G, W, | |||
| viewed at LEDs | viewed at LEDs | |||
|
| LED display. | |||
|
|
|
| ||
|
|
|
|
| |
|
| Output Diagnostics - Allows viewing the outputs from the control | Diagnostic | Normal | |
| 7 | board such as the compressor, reversing valve, blower, hot water | Outputs viewed at | Display viewed | |
|
| pump, and loop pump on the LED display. | LEDs | at LEDs | |
|
|
|
|
| |
|
| Thermostat Selection | Pulsed “L” | Continuous “L” | |
| 8 | Configures the control for a pulsed lockout signal (ComforTalk and | |||
| signal | signal | |||
|
| FaultFlash thermostats) or continuous 5 VAC lockout signal. | |||
|
|
|
| ||
|
|
|
|
| |
| 1 | Single or Dual Capacity Operation | Dual Cap | 1 Speed | |
|
|
|
|
| |
|
| Zoned/Finish on Second Stage |
| Finish on 2nd | |
|
| This switch allows the unit to down stage with the thermostat | Normal - | Unzoned Dual | |
| 2 | when off and finish with second stage when on. Finish on second | Capacity | ||
| All other systems | ||||
|
| stage reduces stage changing in reciprocating dual capacity | |||
|
|
| |||
|
| compressors. |
| Premier 2 speed | |
SW3 |
|
|
|
| |
3 | ECM Fan Monitoring - Set for No PRM on split systems | No RPM | RPM | ||
| |||||
|
|
|
|
| |
| 4 | NOT USED | N/A | N/A | |
|
|
|
|
| |
|
| On dual capacity units this switch allows stage change: on the fly |
| ||
| 5 | when off, and 1 minute delay when on. A delay is required on all | Envision | ||
| Premier | ||||
|
| reciprocating dual capacity units. |
| ||
|
|
|
| ||
|
|
|
|
|
21