ENVISION SERIES INSTALLATION MANUAL
Unit Operating Parameters
Single Speed Models
|
|
|
|
| Cooling |
| |||
Entering Water | Water Flow |
|
|
|
|
|
|
| |
Suction | Discharge |
|
|
| Water Temp | Air Temp | |||
Temp °F | GPM/Ton | Pressure | Pressure |
| Superheat | Subcooling | |||
|
| PSIG | PSIG |
|
|
| Rise °F | Drop °F DB | |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| |
50 | 1.5 | 120 | - 142 | 215 - 240 |
| 7 - 15 | 7 - 14 | 18 - 22 | 18 - 22 |
3.0 | 115 - 138 | 190 - 225 |
| 10 - 18 | 4 - 11 | 8 - 10 | 18 - 22 | ||
|
| ||||||||
|
|
|
|
|
|
|
|
| |
70 | 1.5 | 125 | - 148 | 290 - 315 |
| 8 - 14 | 6 | 18 - 22 | 18 - 22 |
3.0 | 123 | - 146 | 255 - 290 |
| 9 - 15 | 5 - 10 | 8 - 10 | 18 - 22 | |
|
| ||||||||
|
|
|
|
|
|
|
|
| |
90 | 1.5 | 134 | - 157 | 340 - 380 |
| 8 - 14 | 6 - 13 | 18 - 22 | 16 - 20 |
3.0 | 130 | - 155 | 310 - 350 |
| 9 - 15 | 5 - 12 | 8 - 10 | 16 - 20 | |
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| Heating |
| |||
Entering Water | Water Flow |
|
|
|
|
|
|
| |
Suction | Discharge |
|
|
| Water Temp | Air Temp | |||
Temp °F | GPM/Ton | Pressure | Pressure |
| Superheat | Subcooling | |||
|
| PSIG | PSIG |
|
|
| Drop °F | Rise °F DB | |
|
|
|
|
|
|
| |||
30 | 1.5 | 69 | - 81 | 254 - 334 |
| 7 - 13 | 5 - 13 | 7 | 18 - 24 |
3.0 | 75 | - 87 | 260 - 340 |
| 7 - 14 | 5 - 13 | 3 - 6 | 20 - 26 | |
|
| ||||||||
50 | 1.5 | 98 - 113 | 293 - 373 |
| 7 - 14 | 7 - 15 | 8 - 11 | 20 - 26 | |
3.0 | 105 | - 120 | 300 - 380 |
| 7 - 15 | 7 - 15 | 4 - 7 | 22 - 28 | |
|
| ||||||||
70 | 1.5 | 133 | - 150 | 315 - 415 |
| 9 - 15 | 9 - 16 | 11 - 14 | 26 - 32 |
3.0 | 139 | - 157 | 325 - 425 |
| 9 - 15 | 9 - 16 | 7 - 10 | 28 - 34 | |
|
|
Note: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB.
Heating performance based on entering air temperature of 70º F DB.
26