. A complete Parts List is available at www.MillerWelds.com
SECTION 7 − OPERATING AUXILIARY EQUIPMENT
7-1. Generator Power Receptacles
! If unit does not have GFCI recep- tacles, use
NOTICE − Disconnect equipment from auxil- iary power receptacles during start−up and shutdown. Some equipment can be dam- aged by changes in frequency as engine rpms change during
. Generator power decreases as weld current increases.
Set Fine Control R1 at 10 for full genera- tor power.
1 240 V 50 A AC Receptacle RC1
RC1 supplies 60 Hz
2 120 V 20 A Duplex Receptacle RC2
3 120 V 20 A Duplex Receptacle RC3
RC2 and RC3 supply 60 Hz
2 3
5 6
1
4 Supplementary Protector CB1
CB1 protects receptacles RC1, RC2, and RC3 from overload. If CB1 opens, the recep- tacles do not work. Place switch in On posi- tion to reset.
5Supplementary Protector CB2
6Supplementary Protector CB3
CB2 protects RC2 and CB3 protects RC3 from overload. If a supplementary protector opens, the receptacle does not work.
.Press button to reset. If supplementary
protector continues to open, contact Factory Authorized Service Agent.
! Power is still present at the 240 volt receptacle if CB2 and/or CB3 trips. Unplug power cord before attempting to service accessories or tools.
7 Optional 120 V 20 A AC GFCI Recep- tacles
GFCI2 and GFCI3 supply 60 Hz single-
4phase power at weld/power speed. Maxi- mum output from
7 |
|
|
|
|
|
| If a ground fault is detected, the GFCI Reset | |
|
|
|
|
|
|
|
| button pops out and the circuit opens to dis- |
|
|
|
|
|
|
|
| connect the faulty equipment. Check for |
|
|
|
|
|
|
|
| damaged tools, cords, plugs, etc. connected |
|
|
|
|
|
|
|
| to the receptacle. Press button to reset re- |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| ceptacle and resume operation. |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| . At least once a month, run engine at |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| weld/power speed and press Test button |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| to verify GFCI is working properly. |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| Combined output of all receptacles limited to |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| 10 kVA/kW rating of the generator. |
|
|
|
|
|
|
|
| EXAMPLE: If 20 A is drawn from each 120 |
|
|
|
|
|
|
|
| V duplex receptacle, only 21 A is available at |
|
|
|
|
|
|
|
| the 240V receptacle: |
|
|
|
|
|
|
|
| 2 x (120 V x 20 A) + (240 V x 21 A) = 10 kVA/ |
|
|
|
|
|
|
|
| kW |
803