2-11. Electrical Service Guide
Input Voltage | 200 | 230 | |
|
|
| |
Input Amperes At Rated Output | 30 | 26 | |
|
|
| |
Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes |
|
| |
Circuit Breaker 1, | 35 | 30 | |
Normal Operating 3 | 45 | 40 | |
Min Input Conductor Size In AWG/Kcmil | 10 | 10 | |
|
|
| |
Max Recommended Input Conductor Length In Feet (Meters) | 97 | 128 | |
(29) | (39) | ||
| |||
|
|
| |
Min Grounding Conductor Size In AWG/Kcmil | 10 | 10 | |
|
|
|
Reference: 1999 National Electrical Code (NEC)
1Choose a circuit breaker with
2
3“Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).
YCaution: Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard.
2-12. Selecting A Location And Connecting Input Power
18 in (457 mm) of space for airflow
Y Do not move or operate unit where it could tip.
Y Always connect grounding conductor first.
= GND/PE
5
L1
L2
1 Rating Label
Supply correct input power.
2Plug
3Receptacle
Connect plug to receptacle.
4Input And Grounding Conductors
Connect directly to line disconnect device if hard wiring is required.
5Line Disconnect Device See Section
YSpecial installation may be required where gasoline or volatile liquids are present – see NEC Article 511 or CEC Section 20.
1
1 | 2 |
4
3
L2L1
230 VAC, 1
801 568 / Ref. 800