2-11. Electrical Service Guide
Input Voltage | 200 | 230 | 460 | 575 | |
|
|
|
|
| |
Input Amperes At Rated Output | 46 | 40 | 20 | 16 | |
|
|
|
|
| |
Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes |
|
|
|
| |
Circuit Breaker 1, | 50 | 50 | 25 | 20 | |
Normal Operating Fuse 3 | 70 | 60 | 30 | 25 | |
Min Input Conductor Size In AWG/Kcmil | 10 | 10 | 14 | 14 | |
|
|
|
|
| |
Max Recommended Input Conductor Length In Feet (Meters) | 59 | 77 | 122 | 190 | |
(18) | (24) | (37) | (58) | ||
| |||||
|
|
|
|
| |
Min Grounding Conductor Size In AWG/Kcmil | 10 | 10 | 14 | 14 | |
|
|
|
|
|
Reference: 1999 National Electrical Code (NEC)
1Choose a circuit breaker with
2
3“Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).
YCaution: Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard.
2-12. Selecting A Location And Connecting Input Power
18 in (457 mm) of space for airflow
YDo not move or operate unit where it could tip.
YAlways connect grounding conductor first.
= GND/PE
4
L1
L2
1 Rating Label
Supply correct input power.
2Plug
3Receptacle
Connect plug to receptacle.
4Line Disconnect Device See Section
YSpecial installation may be required where gasoline or volatile liquids are present – see NEC Article 511 or CEC Section 20.
2
1
3
L2L1
230 VAC, 1