ENVIRONMENTALLY FRIENDLY TECHNOLOGY

Speedy digital PID control

The introduction of new digital PID control to the E-model stabilizes the chilled/hot water temperature with high accuracy than the previous C model. It quickly responds to the load fluctuation and supplies stable

chilled/hot water temperature. It is suitable for air-conditioning intelligent buildings which require sophisticated control.

SUPER ABSORPTION

Optimum dilution cycle period can be shortened substantially according to microprocessor monitoring

This results in the appropriate dilution cycle operating hours.

Graph 6. Dilution cycle (DE)

Control of high temperature generator by solution level control

With the new control system, solution flow rate is precisely controlled so

getic effect of absorbent pump inverter control. This enables the supply

that the solution level of the high temperature generator is maintained at

of a more stable temperature for chilled/hot water compared to conven-

a certain level.

tional models.

Frequency of maneuvering has been substantially reduced with the syner-

 

Graph 4. Operating result by speedy PID control (gas-fired)

 

 

 

Continuous operation of E model absorbent pump

 

 

 

Absorbent

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pump

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

 

 

Conventional pump

 

E model

 

 

 

 

 

ON-OFF(3 times)

 

Conventional

 

 

 

 

 

 

 

 

Temperature

12

 

Chilled water inlet temperature

Load change

 

 

 

 

 

 

 

 

 

 

(° C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E model

 

Temperature

8

 

Chilled water outlet temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setting 7° C

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

Conventional

 

 

 

 

 

 

 

 

 

 

 

 

 

Load factor 80%

 

 

Load factor 40%

 

 

0

 

 

 

 

 

 

 

 

 

0

5

10

15

20

25

30

35

40

 

 

 

 

 

Time(minutes)

 

 

 

Saving energy with the inverter

Balancing the load and flow rate with the absorbent pump’s inverter con- trol enables efficient and energy saving operation. As a result, it saves the input energy and electric power consumption, running cost by 5%

compared to none-inverter control.

Graph 5. Running cost curve

Table 4. Test condition

Operation

ON

signal

OFF

 

 

Chiller /

ON

heater

OFF

 

 

 

 

Cooling water

ON

pump

OFF

 

 

Chilled / hot

ON

water pump

OFF

 

 

1 min

 

 

 

T 1

 

 

 

1 min

 

 

 

T 2

 

 

 

 

 

 

 

 

 

Stop signal

 

 

 

 

 

 

 

 

 

 

 

Chiller stop

T1: Count the time until generator temperature goes down to 120° C (About 4 to 20 minutes)

T2: Decide the time by generator temperature. (About 5 to 10 minutes)

Note :

1)Dilution time in cooling operation is minimum 6 minutes to maximum 15 minutes.

2)Dilution time in heating operation is 5 minutes.

Unit proper and hot water pump stop in 5 minutes after stop signal is lit.

3)Stop the air conditioning system after complete stop of chiller.

Purge system

The high performance purge system maintains the required operating pressure, preserves the chiller performance characteristics, minimizes chiller maintenance as one purge time operation per season in case there are four(4) seasons.

Steam valve opening control

Graph 7. Start up chart (NE)

ex.

 

100

 

 

 

 

 

ratio(%)

80

 

 

 

 

 

 

 

Non-inverter

 

 

 

 

 

control

 

 

 

60

 

 

 

 

 

consumption

 

 

 

 

 

40

 

 

 

 

 

 

 

 

 

E model

 

Fuel

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

0

20

40

60

80

100

Cooling load factor(%)

1.Chilled water outlet temperature 7° C constant

2.Cooling water inlet temperature

Load factor(%)

Temperature(° C)

 

 

100

32

 

 

50

27

30

25

 

 

 

 

 

Variable(5-30minutes)

 

 

 

 

15minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

140

 

 

 

 

 

 

 

 

 

Steam consumption

 

 

 

 

 

120

 

 

Temperature (° C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Consumption ratio (%)

control opening ratio (%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

 

 

 

 

 

 

 

Steam control valve

 

 

 

 

 

 

 

 

 

 

 

 

80

 

 

 

 

 

 

 

 

 

opening ratio

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling water inlet temperature

 

60

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Chilled water inlet temperature

 

40

Steam

Steam

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Chilled water outlet temperature

 

 

 

 

7° C

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

5

7 8

15

 

20

25

 

30

35

40

 

 

 

10

 

 

 

 

Open angle of steam control valve at starting is controlled by means of the three steps, resulting that the excessive amount of steam and also the consumed time to reach the desired level became less than the previous model.

Of course, by means of adjusting the open speed of steam control valve at the second step and the third, it is possible to set up to the most suitable condition met to the site aux- iliary equipment.

Time(minutes)

8

9

Image 6
Contents Making the World a More Comfortable Place Contents Double effect absorption cycle Electrical peak power shavingHeating and cooling operation Many applicationsExpert function by self-diagnosis Graph 2. Tendency of absorbent concentrationGenerator temp 149 C Sanyo control systemDisplay and control board Exhaust gas temp 236 C CH W temp 12.3 7.1 CPurge system Speedy digital PID controlSaving energy with the inverter Steam valve opening controlDouble effect type High temperature generator safety controlExpansion of safety operating zone Crystallization protectionAbsorption cooling cycle Lower shellSchematic cooling cycle Upper shellHeating cycle Low Temperature GeneratorCooling cycle Cooling Water outletDouble effect direct-fired absorption chiller / heaters Scope of supply DE Scope of order DECOW Hole33ø DE-31ThruDE-32 ABC DEF To mount the chiller Foundation dimensional data DEControl panel DE Detail of weld . Washers are supplied with the chillerField wiring DE StartStop Ignition Stop signal Chiller stop36 sec Ignition gasFlue & stack connection Flue flange dimensional dataField supply Steel material Dimensional data Typical steel stackBurner description Gas trainTypical piping diagram DE Cooling cycle schematicGeneral remarks on piping work Double effect steam-fired absorption chillers Scope of supply NE Scope of order NE877 341 329 2311 1896 1003 364 2089 Eitherside CHWin 3289 3104 3400 1078 396 Out 1515 410 684 COWin R700 2930 1971 33hole Wireconnectionø Out Connectionø41 Wire Out 140 Foundation dimensional data NE Control panel NEField wiring NE Typical electrical field connection diagram Steam-fired NETypical piping diagram-laying NE General remarks on piping-laying workHot water-fired absorption chillers Scope of supply LE Scope of order LEMain unit Rust preventive paint Control panel Finish paint BCD 2255 835 926 Side Spaceeither COWinlet Tuberemoval COWoutlet 976 Side 3886 4500 Removalspaceeither Tube Customer.the LEThru52-LE 57.FigureFoundation dimensional data LE Control panel LEGenerator temp 69 C Field wiring LE For emergency stop signalTypical piping diagram-laying LE Work outside the area surrounded by this lineCapacity ratings DE and NE Capacity ratings LEFlowrate Dropcurve Pressure WaterCooling pressure drop LEcurve Field piping instruction Location and space requirementsWater piping Leveling requirementsInsulation DE Insulation NE Insulation dataInsulation LE Rupture disk mountingQuality control of cooling water Water treatmentCooling water blow system

DE specifications

Sanyo DE is an innovative line of home appliances and electronics that showcases Sanyo's commitment to quality, efficiency, and user-centered design. This series includes various products, such as air conditioners, refrigerators, and microwaves, all engineered to enhance the everyday living experience.

One of the standout features of Sanyo DE appliances is their energy efficiency. Many models are equipped with advanced technologies that adhere to stringent energy-saving standards, helping consumers reduce their electricity bills while minimizing their environmental footprint. The use of inverter technology in air conditioners, for instance, allows for precise temperature control and significant reductions in energy consumption.

Sanyo DE also emphasizes smart technology integration. Many products come with Wi-Fi capabilities, enabling users to control their appliances remotely via mobile apps. This connectivity makes it easier to monitor energy usage, adjust settings, and receive alerts about maintenance needs. Users can enjoy added convenience as they can pre-heat their ovens or set their air conditioners to the desired temperature before arriving home.

Another key characteristic of Sanyo DE is its focus on durability and reliability. Each product is built with high-quality materials and undergoes rigorous testing to ensure long-lasting performance. The robust construction not only enhances the lifespan of the appliances but also provides peace of mind to users concerning their safety and functionality.

In terms of design, Sanyo DE products are crafted to blend seamlessly into modern homes with sleek and contemporary aesthetics. The intuitive user interfaces are designed for ease of use, featuring clear displays and simple controls, allowing users of all ages to operate the appliances without any hassle.

Furthermore, Sanyo DE pays attention to noise reduction. Many appliances incorporate sound dampening technologies, making them ideal for use in residential settings, where quiet operation is critical. Whether it’s a refrigerator running seamlessly in the background or an air conditioner cooling the room without disruption, Sanyo DE ensures a pleasant home atmosphere.

Overall, Sanyo DE exemplifies a fusion of advanced technology, energy efficiency, and user-friendly design. With a diverse range of appliances, Sanyo DE is committed to enhancing the lives of its users through thoughtful innovation and reliable performance.