Location and space requirements

 

 

 

The unit is designed for indoor application and must be located in a space

provided on either end to facilitate tube cleaning, or removal and clear-

 

where the surrounding temperature of equipment is between 5° C and

ance on all other sides of the unit for general unit maintenance. See the

 

45° C, and at no more than 90% relative humidity. Clearance must be

dimensional data tables for clearance requirements.

 

Water piping

 

 

 

Water piping should be arranged so that the circulating pumps discharge

and noise transmission, vibration absorbers should be provided. Shutoff

 

directly into the vessels. The water piping should be insulated to reduce

valves should be provided to allow unit isolation during maintenance.

 

heat gain and to prevent condensation. Air vents should be located at all

Chilled water flow switch is provided on the unit and is preset to open at

 

high points in the water piping system, and drains should be located at all

approximately 50% of specified flow rate.

 

low points to facilitate complete system drainage. To reduce vibration

 

 

22

50

 

21

 

40

14

12

13

11

 

30

 

/h)

 

3

 

(m

Field piping instruction

1.In order to prevent freeze-up of chilled water during unit shutdown, the chilled water pump(s) and air handler must be run for 15 minutes after the burner is shut off. This will allow time for the automatic dilu- tion cycle to be completed.

2.The standard unit must not be subjected to water pressures in excess of 981 kPa (10 kg/cm2G).

3.An expansion tank should be provided in the chilled/hot water line.

4.Thermometers and pressure gauges should be field-installed at the inlet and outlet of the chilled/hot water line, and the cooling water

line.

5.During heating operation, the cooling water circuit should not be in operation and should be blown down.

6.All external piping connections are provided with JIS 10K flanges un- less noted.

7.A drain line must be installed from the smoke chamber drain to a floor drain.

8.See Figure 32 (DE), Figure 48 (NE), Figure 61 (LE) for typical sys- tem piping arrangement.

03

20

Flowrate

(LE)

 

 

 

 

02

 

 

 

10

dropcurve

 

 

 

 

01

 

 

 

8 9

pressure

 

 

 

 

 

 

 

 

6 7

water

 

 

 

 

 

 

 

 

5

Hot

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Graph17.

 

 

 

 

 

 

 

 

3

100

90

80

70

60

50

40

30

20

10

 

 

 

 

 

 

(kPa) drop Pressure

 

 

Leveling requirements

Strict leveling tolerances must be adhered to for trouble-free operation.

difference in the water level at the two points. The tolerance that must be

SANYO units are furnished with four leveling reference points, one on

maintained from end-to-end and side-to side is 1mm (1/25'') of difference

each corner of the lower shell or tube sheet. Each reference point is

for each 1m length between points. It is not necessary to check levels

designated by three punch marks. A convenient method to check level-

diagonally. When the unit does not meet this requirement, the unit must

ing tolerances is to fill a clear vinyl hose with water and measure the

be shimmed in order to meet leveling tolerances.

Figure 62. Leveling the chiller

 

B

D

Evaporator side

A

Absorber side

C

88

89

Image 46
Contents Making the World a More Comfortable Place Contents Double effect absorption cycle Electrical peak power shavingHeating and cooling operation Many applicationsExpert function by self-diagnosis Graph 2. Tendency of absorbent concentrationGenerator temp 149 C Sanyo control systemDisplay and control board Exhaust gas temp 236 C CH W temp 12.3 7.1 CPurge system Speedy digital PID controlSaving energy with the inverter Steam valve opening controlDouble effect type High temperature generator safety controlExpansion of safety operating zone Crystallization protectionAbsorption cooling cycle Lower shellSchematic cooling cycle Upper shellHeating cycle Low Temperature GeneratorCooling cycle Cooling Water outletDouble effect direct-fired absorption chiller / heaters Scope of supply DE Scope of order DECOW Hole33ø DE-31ThruDE-32 ABC DEF To mount the chiller Foundation dimensional data DEControl panel DE Detail of weld . Washers are supplied with the chillerStart Field wiring DEStop Ignition Stop signal Chiller stop36 sec Ignition gasFlue & stack connection Flue flange dimensional dataField supply Steel material Dimensional data Typical steel stackBurner description Gas trainCooling cycle schematic Typical piping diagram DEGeneral remarks on piping work Double effect steam-fired absorption chillers Scope of supply NE Scope of order NE877 341 329 2311 1896 1003 364 2089 Eitherside CHWin 3289 3104 3400 1078 396 Out 1515 410 684 COWin R700 2930 1971 33hole Wireconnectionø Out Connectionø41 Wire Out 140 Foundation dimensional data NE Control panel NEField wiring NE Typical electrical field connection diagram Steam-fired NETypical piping diagram-laying NE General remarks on piping-laying workHot water-fired absorption chillers Scope of order LE Scope of supply LEMain unit Rust preventive paint Control panel Finish paint BCD 2255 835 926 Side Spaceeither COWinlet Tuberemoval COWoutlet 976 Side 3886 4500 Removalspaceeither Tube Customer.the LEThru52-LE 57.FigureControl panel LE Foundation dimensional data LEGenerator temp 69 C Field wiring LE For emergency stop signalTypical piping diagram-laying LE Work outside the area surrounded by this lineCapacity ratings DE and NE Capacity ratings LEFlowrate Dropcurve Pressure WaterCooling pressure drop LEcurve Field piping instruction Location and space requirementsWater piping Leveling requirementsInsulation DE Insulation NE Insulation dataInsulation LE Rupture disk mountingQuality control of cooling water Water treatmentCooling water blow system

DE specifications

Sanyo DE is an innovative line of home appliances and electronics that showcases Sanyo's commitment to quality, efficiency, and user-centered design. This series includes various products, such as air conditioners, refrigerators, and microwaves, all engineered to enhance the everyday living experience.

One of the standout features of Sanyo DE appliances is their energy efficiency. Many models are equipped with advanced technologies that adhere to stringent energy-saving standards, helping consumers reduce their electricity bills while minimizing their environmental footprint. The use of inverter technology in air conditioners, for instance, allows for precise temperature control and significant reductions in energy consumption.

Sanyo DE also emphasizes smart technology integration. Many products come with Wi-Fi capabilities, enabling users to control their appliances remotely via mobile apps. This connectivity makes it easier to monitor energy usage, adjust settings, and receive alerts about maintenance needs. Users can enjoy added convenience as they can pre-heat their ovens or set their air conditioners to the desired temperature before arriving home.

Another key characteristic of Sanyo DE is its focus on durability and reliability. Each product is built with high-quality materials and undergoes rigorous testing to ensure long-lasting performance. The robust construction not only enhances the lifespan of the appliances but also provides peace of mind to users concerning their safety and functionality.

In terms of design, Sanyo DE products are crafted to blend seamlessly into modern homes with sleek and contemporary aesthetics. The intuitive user interfaces are designed for ease of use, featuring clear displays and simple controls, allowing users of all ages to operate the appliances without any hassle.

Furthermore, Sanyo DE pays attention to noise reduction. Many appliances incorporate sound dampening technologies, making them ideal for use in residential settings, where quiet operation is critical. Whether it’s a refrigerator running seamlessly in the background or an air conditioner cooling the room without disruption, Sanyo DE ensures a pleasant home atmosphere.

Overall, Sanyo DE exemplifies a fusion of advanced technology, energy efficiency, and user-friendly design. With a diverse range of appliances, Sanyo DE is committed to enhancing the lives of its users through thoughtful innovation and reliable performance.