11. PROCESSES AND FUNCTIONS

(2) Dry Operation (Dehumidification)

Dry operation uses the ability of the cooling cycle to remove moisture from the air, but by running at low level to dehumidify without greatly reducing the room temperature. The air conditioner repeats the cycle of turning ON and OFF automatically as shown in the chart below according to the room temperature.

Room temp.

T + 4 °F

Set temp. T °F T – 2 °F

Room temp. 59 °F

Cooling operation

Dry A zone

Compressor : Continuous operation

FMI (indoor fan) : L (low speed) / LL (very low speed) intermittent ventilation only while the compressor is ON.

Dry B zone

Compressor : Intermittent operation (ON for 3 minutes and OFF for 9 minutes)

FMI (indoor fan) : L (low speed) / LL (very low speed) intermittent ventilation only while the compressor is ON.

Monitor zone

Both the indoor and outdoor units stop.

2213_M_S

Fig. 12

NOTE

Intermittent ventilation occurs by switching the indoor fan speed between L LL.

Dry operation does not occur when the room temperature is under 59°F, which is the monitor zone. When the compressor stops, the indoor fan stops as well.

SM830092

– 36 –

Image 36
Contents Technical Data Indoor Unit Outdoor Unit KS2462R C2462R CL2462RPlease Read Before Starting …In a Room…In Moist or Uneven Locations Table of Contents Operating Range KS2462R / C2462RKS2462R / CL2462R Specifications Unit SpecificationsIndoor Unit KS2462R Outdoor Unit CL2462R Major Component Specifications Indoor Unit Major Component Specifications Outdoor Unit Model No CL2462R Source Controller P.C.B. AssyHeat exchange Other Component Specifications Indoor Unit Model No KS2462R Power TransformerThermistor Coil sensor Lamp AssyOther Component Specifications Outdoor Unit Power RelayModel No C2462R Thermostat Coil sensorModel No CL2462R Solenoid control valve or coilDimensional Data Indoor Unit KS2462ROutdoor Unit C2462R, CL2462R Cooling Capacity Indoor Unit KS2462R Outdoor Unit C2462R208V / 1 phase / 60Hz Performance Charts Operating Current Indoor Unit KS2462R230V 208VOutdoor Unit CL2462R High and Low Pressure Indoor Unit KS2462R High Pressure230V / 208 Low Pressure230 AIR Throw Distance Chart Horizontal distance ftRefrigerant Flow Diagram HgbvInstallation Instructions Tubing LengthC2462R, CL2462R 132 Selecting the Installation Site For stable operationAir conditioner, do Air discharge chamber for top discharge Recommended outer dimensions of wind shield field supply Electrical Wiring General Precautions on Wiring Wiring System Diagram ModelsElectrical Data Electric Wiring Diagram Electrical Wiring DiagramsElectric Wiring Diagram Schematic Diagram CL2462R Outdoor Unit Controller CR-CL2432Schematic Diagram Outdoor Unit CL2462RRoom Temperature Control Processes and FunctionsDry Operation Dehumidification Cooling operation Dry a zoneFreeze Prevention Outdoor Fan Speed Control C2462R Type CL2462R TypeService Procedures 1032XS Check remote control unit There is a possibility of short circuitCheck Operation selector switch in the indoor unit Check compressor motor protectors High pressure switch 63PHTransformer in indoor unit Check. auxiliary relay Y or 2Y Check fuse on the P.C.B. Ass’y in the indoor unitCheck Cool / FAN selector switch in the remote control unit Check set temperatureOutdoor Unit does not Run Check compressor motor magnetic contactor Check indoor unit P.C.BCheck outdoor unit P.C.B. CL2462R Type Indoor Unit does not Run Indoor fan and flap motor do not runSome Part does not Operate. A. Indoor fan does not run Flap motor does not runOutdoor Fan does not Run Outdoor Fan does not Run for CL2462R Compressor does not RunPoor Cooling Excessive CoolingRoom temp. Sensor in the remote control unit is defective Power Supply Wires Measurement of Insulation Re- sistance for Electrical partsChecking the Protective Devices Compressor motor thermal protector . . . . . . Outdoor unitIndoor fan motor FMI Indoor unit Measure the coil resistance Motor capacitor Both in indoor and outdoor unitCheck for continuity using a multim- eter as shown in Fig Continuity of fuse on P.C.B. Ass’yMethod Used to Replace Fuse on PCB Ass’y Refrigerant R410A Special Precautions When Installing Unit No addition of compressor oil for R410A Gauge manifold

C2462R, CL2462R specifications

The Sanyo CL2462R and C2462R are versatile and innovative air conditioning models designed to meet the demands of residential and commercial spaces. Known for their advanced features, energy efficiency, and user-friendly operation, these units have garnered a reputation for reliability and performance.

One of the standout features of the Sanyo CL2462R and C2462R is their energy efficiency. Equipped with inverter technology, these models adjust their cooling output based on the ambient temperature, minimizing energy consumption while maintaining consistent comfort levels. This not only helps in reducing electricity bills but also contributes to environmental sustainability, making them an attractive choice for the eco-conscious consumer.

Both models come with a powerful cooling capacity, ensuring rapid temperature reduction even in the most demanding conditions. The CL2462R features a robust compressor that provides an efficient cooling experience, while the C2462R balances power with refined performance, tailoring its output to the specific needs of the space it serves.

Another significant characteristic is their whisper-quiet operation. The Sanyo CL2462R and C2462R are designed with noise reduction technology, allowing them to operate at lower decibel levels. This feature makes them ideal for use in bedrooms, offices, or any quiet environment where disruption needs to be minimized.

User-centric design is prevalent in these models, with intuitive remote controls and programmable timers that allow users to customize their cooling experience. Both units feature multiple fan speeds, allowing users to choose their desired airflow levels for optimal comfort. Additionally, the units are equipped with air purification technologies, including filters that effectively trap dust, allergens, and pollutants, ensuring that the air circulated is clean and healthy.

The Sanyo CL2462R and C2462R also boast sleek designs that can complement various interior decor styles. Their compact dimensions make them easy to install without occupying too much space, making them a practical choice for modern living.

In summary, the Sanyo CL2462R and C2462R deliver exceptional performance, energy efficiency, and user-friendly features, making them ideal solutions for effective cooling. These models embody Sanyo's commitment to quality and innovation, providing consumers with reliable products that enhance comfort and improve air quality in any environment.