8. INSTALLATION INSTRUCTIONS

Wind Shield for "CL" Model

IMPORTANT

It is recommended to use wind shields for "CL" model (Fig. 5b). "CL" model is designed to use in low outdoor temperature conditions.

General

When the outdoor unit is installed in a position exposed to strong wind (like seasonal winds with low air tempera- ture in winter), a suitable wind shield must be installed on the outdoor unit.

This unit is designed so that the fan of the outdoor unit runs at low speed when the air conditioner is operated at low outdoor air temperatures. When the outdoor unit is exposed to strong wind, the system pressure drops because of the freeze protector.

For outer dimensions of the wind shield, see Fig. 5c.

Wind shield

(air discharge side)

Front

Fig. 5b

Recommended outer dimensions of wind shield (field supply)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

hole

 

 

 

 

 

 

 

 

 

 

-9/16"

 

 

 

 

 

 

 

 

 

 

 

ø1

 

 

 

 

 

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9-27/32"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21-13/16"

 

 

 

hole

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- ø15/64"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21-5/8"

 

22-7/16"

23-15/32"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-1/16"

 

 

9-27/32"

 

 

9-27/32"

 

 

 

15/16"

 

1/2"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21-13/16"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CL2462R

Fig. 5c

5-3/16"

5-5/32"

SM830092

– 26 –

Image 26 Contents
Technical Data Indoor Unit Outdoor Unit KS2462R C2462R CL2462R…In Moist or Uneven Locations Please Read Before Starting…In a Room Table of Contents KS2462R / CL2462R Operating RangeKS2462R / C2462R Specifications Unit SpecificationsIndoor Unit KS2462R Outdoor Unit CL2462R Major Component Specifications Indoor Unit Major Component Specifications Outdoor Unit Heat exchange Model No CL2462R SourceController P.C.B. Assy Thermistor Coil sensor Other Component Specifications Indoor UnitModel No KS2462R Power Transformer Lamp AssyModel No C2462R Other Component Specifications Outdoor UnitPower Relay Thermostat Coil sensorModel No CL2462R Solenoid control valve or coilDimensional Data Indoor Unit KS2462ROutdoor Unit C2462R, CL2462R Cooling Capacity Indoor Unit KS2462R Outdoor Unit C2462R208V / 1 phase / 60Hz 230V Performance ChartsOperating Current Indoor Unit KS2462R 208VOutdoor Unit CL2462R 230V / 208 High and Low Pressure Indoor Unit KS2462RHigh Pressure Low Pressure230 AIR Throw Distance Chart Horizontal distance ft Refrigerant Flow Diagram HgbvC2462R, CL2462R 132 Installation InstructionsTubing Length Air conditioner, do Selecting the Installation SiteFor stable operation Air discharge chamber for top discharge Recommended outer dimensions of wind shield field supply Electrical Wiring General Precautions on Wiring Wiring System Diagram ModelsElectrical Data Electric Wiring Diagram Electrical Wiring DiagramsElectric Wiring Diagram Schematic Diagram CL2462R Outdoor Unit Controller CR-CL2432Schematic Diagram Outdoor Unit CL2462RRoom Temperature Control Processes and FunctionsDry Operation Dehumidification Cooling operation Dry a zoneFreeze Prevention Outdoor Fan Speed Control C2462R Type CL2462R TypeService Procedures 1032XS Check remote control unit There is a possibility of short circuitTransformer in indoor unit Check Operation selector switch in the indoor unitCheck compressor motor protectors High pressure switch 63PH Check. auxiliary relay Y or 2Y Check fuse on the P.C.B. Ass’y in the indoor unitOutdoor Unit does not Run Check Cool / FAN selector switch in the remote control unitCheck set temperature Check outdoor unit P.C.B. CL2462R Type Check compressor motor magnetic contactorCheck indoor unit P.C.B Some Part does not Operate. A. Indoor fan does not run Indoor Unit does not RunIndoor fan and flap motor do not run Flap motor does not runOutdoor Fan does not Run Outdoor Fan does not Run for CL2462R Compressor does not RunPoor Cooling Excessive CoolingRoom temp. Sensor in the remote control unit is defective Power Supply Wires Measurement of Insulation Re- sistance for Electrical partsChecking the Protective Devices Compressor motor thermal protector . . . . . . Outdoor unitIndoor fan motor FMI Indoor unit Measure the coil resistance Motor capacitor Both in indoor and outdoor unitMethod Used to Replace Fuse on PCB Ass’y Check for continuity using a multim- eter as shown in FigContinuity of fuse on P.C.B. Ass’y Refrigerant R410A Special Precautions When Installing Unit No addition of compressor oil for R410A Gauge manifold