12. SERVICE PROCEDURES

(3)Checking the Electrical Components

1)Measurement of Insulation Resistance

The electrical insulation is acceptable when the resistance exceeds 2 MΩ .

1 Power Supply Wires

Clamp the earthed wire of the Power Supply wires with a lead clip of the insulation resistance tester and mea- sure the resistance by placing a probe on either of the power wires. (Fig. 16)

Then measure the resistance between the earthed wire and the other power wires. (Fig. 16)

2 Indoor Unit

Clamp an aluminum plate fin or copper tube with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on the terminal plate (Fig. 17)

3 Outdoor Unit

Measure the resistance by placing a probe on the terminal plate in the same manner as explained above 2 . (Fig. 17)

4Measurement of Insulation Re- sistance for Electrical parts

Disconnect the connector of the desired electric part from terminal plate, P.C.B. Ass’y, etc. (Fig. 18)

Similarly, disconnect the lead wires from compressor, capacitor, etc. (Fig. 19)

Measure the resistance in the same manner as illustrated on the right.

Refer to Electrical Wiring Diagram.

NOTE

If the probe does not enter the hole because the hole is too narrow, use a probe with a thinner pin.

Earthed wire

Clip

Probe

Insulation tester

0638_X_S

Terminal plate

Probe

Clip

 

Copper

Insulation

tube or

tester

metallic part

 

0639_X_S

Probe

Clip

Copper tube or metallic part

Insulation tester

0640_X_S

From fan motor, compressor and other parts.

Metallic

Probe

part

 

Clip

 

Insulation tester

0641_X_S

Fig. 16

Fig. 17

Fig. 18

Fig. 19

SM830092

– 51 –

Image 51 Contents
Indoor Unit Outdoor Unit KS2462R C2462R CL2462R Technical DataPlease Read Before Starting …In a Room…In Moist or Uneven Locations Table of Contents Operating Range KS2462R / C2462RKS2462R / CL2462R Unit Specifications SpecificationsIndoor Unit KS2462R Outdoor Unit CL2462R Major Component Specifications Indoor Unit Major Component Specifications Outdoor Unit Model No CL2462R Source Controller P.C.B. AssyHeat exchange Lamp Assy Other Component Specifications Indoor UnitModel No KS2462R Power Transformer Thermistor Coil sensorThermostat Coil sensor Other Component Specifications Outdoor UnitPower Relay Model No C2462RSolenoid control valve or coil Model No CL2462RIndoor Unit KS2462R Dimensional DataOutdoor Unit C2462R, CL2462R Indoor Unit KS2462R Outdoor Unit C2462R Cooling Capacity208V / 1 phase / 60Hz 208V Performance ChartsOperating Current Indoor Unit KS2462R 230VOutdoor Unit CL2462R Low Pressure High and Low Pressure Indoor Unit KS2462RHigh Pressure 230V / 208230 Horizontal distance ft AIR Throw Distance ChartHgbv Refrigerant Flow DiagramInstallation Instructions Tubing LengthC2462R, CL2462R 132 Selecting the Installation Site For stable operationAir conditioner, do Air discharge chamber for top discharge Recommended outer dimensions of wind shield field supply Electrical Wiring General Precautions on Wiring Models Wiring System DiagramElectrical Data Electrical Wiring Diagrams Electric Wiring DiagramElectric Wiring Diagram Schematic Diagram Controller CR-CL2432 CL2462R Outdoor UnitOutdoor Unit CL2462R Schematic DiagramProcesses and Functions Room Temperature ControlCooling operation Dry a zone Dry Operation DehumidificationFreeze Prevention CL2462R Type Outdoor Fan Speed Control C2462R TypeService Procedures 1032XS There is a possibility of short circuit Check remote control unitCheck Operation selector switch in the indoor unit Check compressor motor protectors High pressure switch 63PHTransformer in indoor unit Check fuse on the P.C.B. Ass’y in the indoor unit Check. auxiliary relay Y or 2YCheck Cool / FAN selector switch in the remote control unit Check set temperatureOutdoor Unit does not Run Check compressor motor magnetic contactor Check indoor unit P.C.BCheck outdoor unit P.C.B. CL2462R Type Flap motor does not run Indoor Unit does not RunIndoor fan and flap motor do not run Some Part does not Operate. A. Indoor fan does not run Outdoor Fan does not Run Compressor does not Run Outdoor Fan does not Run for CL2462RExcessive Cooling Poor CoolingRoom temp. Sensor in the remote control unit is defective Measurement of Insulation Re- sistance for Electrical parts Power Supply WiresCompressor motor thermal protector . . . . . . Outdoor unit Checking the Protective DevicesMotor capacitor Both in indoor and outdoor unit Indoor fan motor FMI Indoor unit Measure the coil resistanceCheck for continuity using a multim- eter as shown in Fig Continuity of fuse on P.C.B. Ass’yMethod Used to Replace Fuse on PCB Ass’y Refrigerant R410A Special Precautions When Installing Unit No addition of compressor oil for R410A Gauge manifold