Termination

The CC-16 zone controller uses a 2-wire RS-485 network to communicate with the ESP-88 sound processor. For optimum performance, the RS-485 network must be “terminated.” The CC-16 includes built-in termination resistors which make it easy to terminate the network. Termination is accomplished by setting DIP switches 1 and 2 to the ON position.

In most cases, only one CC-16 zone controller – the last unit in the daisy chain network (furthest away from the ESP-88) should have the termination set to ON.

In a star topology, with the ESP-88 in the middle of two or more long runs, two units (the two furthest from the ESP-88) should have the termination set to ON.

Note: Switch 3 (2X) should always be in the ON position.

10

Image 10
Contents ControlSpace CC-16 Zone Controller Important Safety Instructions For the intended audienceInformation about products that generate electrical noise Please read this install guide Regulatory informationFeatures and functions IntroductionQuick start Installation CablingInstalling the mounting box Maximum cable distancesDIP Switch Settings DIP switch addressesTermination Wiring Connecting the wiresWiring Power supplyMounting Mounting the CC-16 zone controllerTroubleshooting Specifications Warranty Bose Product Sales ConditionsOther Rights Page