SSI America 9200 user manual Span Output

Page 49

Model 9200 Programmable Dual-loop Controller

Pressing the “Next ->” key displays the following calibration screen:

Span Output 1

Entered measured output current (mA)

Edit

Calibrate

<-- Back

Skip

Next -->

DONE

Pressing the “Edit” button displays a numeric keypad allowing you to change the Span Output 1 value. Measured at terminals 24(-) and 25(+) for this step. After entering the new Span Output value you must press “Calibrate”. Pressing the “Calibrate” key stores the appropriate value. Pressing the “Done” will return you to the “User Calibration” Screen.

Pressing the “Next ->” key displays the following calibration screen:

Zero Output 2

Enter zero output current (mA)

Edit

Calibrate

<-- Back

Skip

Next -->

DONE

Pressing the “Edit” button displays a numeric keypad allowing you to change the Zero Output 2 value. Measured at terminals 26(-) and 25(+) for this step. After entering the new Zero Output value you must press “Calibrate”. Pressing the “Calibrate” key stores the appropriate value. Pressing the “Done” will return you to the “User Calibration” Screen.

SSi Manual SERIES 9200

49

Programmable Dual-loop

Image 49
Contents Model 9200 Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller 24VDC / 1 AMP Ohms Total IP10 hand protected Model 9200 Terminals Connections Model 9200 Programmable Dual-loop Controller SSi requirement Installation Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Configuration Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Adam VC Base Aipc Model 9200 Programmable Dual-loop Controller Step Opcode Temperature Atmosphere Option Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Calibrate Span input 1 range Span input 2 range Zero input 3 range Zero Output Span Output Enter measured output current mA Supervisor Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Programs Parameter Value Series 9200 Opcodes Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller Applications Information Series 9200 Factory defaults August 17 Rev August 6 Model 9200 Programmable Dual-loop Controller Model 9200 Programmable Dual-loop Controller OPT Code Temp SET PT Rev Description Date