Model 9200 Programmable Dual-loop Controller
Pressing the “Next ->” key displays the following calibration screen:
Span Output 2
Enter measured output current (mA)
Edit
Calibrate
Pressing the “Edit” button displays a numeric keypad allowing you to change the Span Output 2 value. Measured at terminals 26(-) and 25(+) for this step. After entering the new Span Output value you must press “Calibrate”. Pressing the “Calibrate” key stores the appropriate value. Pressing the “Done” will return you to the “User Calibration” Screen.
Pressing the “Next ->” displays a screen that indicates that the calibration process is complete. Pressing the “Done” key at the bottom right of the screen takes you back to the configuration menu.
Full Calibration
Used by SSi personnel.
SSi Manual SERIES 9200 | 50 | Programmable Dual-loop |