Model 9200 Programmable Dual-loop Controller
Pressing the “Edit” button displays a numeric keypad allowing you to change the Zero input 1 range value. Normally terminals 31 and 32 are shorted for this step.
After entering the new Zero Input value you must press “Calibrate”. Pressing the “Calibrate” key stores the appropriate value. Pressing the “Done” will return you to the “User Calibration” Screen.
The current value is displayed directly above the bottom row of buttons as Current Input 1 value: XX.X UV.
Pressing the “Next
Span input 1 range 0
Enter span voltage (sugg. 2000 mV)
Edit
Calibrate
Skip
Next
DONE
Pressing the “Edit” button displays a numeric keypad allowing you to change the Span input 1 range value. Normally terminals
After entering the new Span Input value you must press “Calibrate”. Pressing the “Calibrate” key stores the appropriate value. Pressing the “Done” will return you to the “User Calibration” Screen.
The current value is displayed directly above the bottom row of buttons as Current Input 1 value: XX.X UV.
Pressing the “Next
Zero input 2 range 2
Enter zero voltage (mV)
Edit
Calibrate
Skip
Next
DONE
Pressing the “Edit” button displays a numeric keypad allowing you to change the Zero input 2 range value. Normally terminals 29 and 30 are shorted for this step.
After entering the new Zero Input value you must press “Calibrate”. Pressing the “Calibrate” key stores the appropriate value. Pressing the “Done” will return you to the “User Calibration” Screen.
The current value is displayed directly above the bottom row of buttons as Current Input 2 value: XX.X UV.
SSi Manual SERIES 9200 | 45 | Programmable |