Troubleshooting Procedures

Section 8-4

8-4 Troubleshooting Procedures

The following procedures can be used to troubleshoot various problems in system operation.

8-4-1 Startup Problems

Startup Problems occurred.

 

N

 

 

N

 

 

 

Y

Is the node

N

RUN indicator lit?

ERH indicator lit?

ERC indicator lit?

address set between

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01 and FE Hex?

 

 

Y

 

 

Y

 

 

 

 

N

 

 

 

 

 

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace the Ethernet Unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supplied

N

Make sure that sufficient

 

 

 

 

 

 

 

 

 

 

power is supplied to the

 

 

 

 

 

 

 

 

 

 

to CPU Unit?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPU Unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ethernet Unit

Y

 

Make sure that Unit is firmly

 

 

 

 

 

 

 

 

 

 

 

mounted and tighten the

 

 

 

 

 

 

 

 

 

 

loose on Rack?

 

 

 

mounting screws firmly or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lock the sliders into place.

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Do the RUN and ERH

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace the CPU Unit that

 

 

 

 

 

 

 

 

 

 

indicators not light if another

 

 

 

 

 

 

 

 

 

 

 

 

 

didn't work.

 

 

 

 

 

 

 

 

 

 

CPU Unit is mounted

 

 

 

 

 

 

 

 

 

 

 

 

 

to the Rack?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace the Ethernet Unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the same node

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Create the I/O tables in

 

 

 

 

 

 

 

 

 

 

 

number used by another

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the CPU Unit.

 

 

 

 

 

 

 

 

 

 

 

Unit?

 

 

 

 

 

 

 

 

 

 

 

Y

Set the node numbers so that each one is used only once.

Set the node address to between 01 and FE Hex.

ERH indicator not lit?

Y

Is the same unit

Y

Set the unit numbers correctly.

number used by another

 

 

 

 

 

 

 

CPU Bus Unit?

 

 

 

N

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Has a CPU Unit error

Y

 

 

 

 

Restart the CPU Unit. If the error persists, replace the CPU

 

 

 

occurred in the CPU Unit?

 

 

Unit.

 

 

 

 

 

 

 

 

 

N

Set the Unit Setup and routing tables correctly.

ERH indicator not

Y

Is the IP address correct? N

flashing?

 

 

 

Correct the IP address in the System Setup, and read out the controller status using the READ CONTROLLER STATUS command in FINS communications and correct any problems indicated.

N

Y

Make sure that the node number and the last byte of the IP address are the same and set other host IDs to 0, or change the address conversion method to use and IP address table or combined methods.

Go to Network Connection Problems

209