Omron CS1W-ETN21 operation manual 206

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 231
Image 231

Error Log

 

 

Section 8-3

 

 

 

 

 

 

Error

Meaning

Detailed error code

Correction

EE-

code

 

 

 

 

PROM

 

1st byte

2nd byte

 

 

 

 

 

 

 

 

 

 

 

03C2

FINS/TCP packet discarded

01 to 10:

02:

Have the FINS/TCP connection

---

 

 

Connection

Reopened

status checked when a

 

 

 

because

SEND(090), RECV(098), or

 

 

 

number

 

 

 

remote node

CMND(490) instruction is exe-

 

 

 

 

 

 

 

 

closed

cuted in the ladder program.

 

 

 

 

03:

 

 

 

 

 

Reopened

 

 

 

 

 

because of

 

 

 

 

 

reception

 

 

 

 

 

error

 

 

 

 

 

04:

 

 

 

 

 

Reopened

 

 

 

 

 

because of

 

 

 

 

 

transmission

 

 

 

 

 

error

 

 

 

 

 

05:

 

 

 

 

 

Reopened

 

 

 

 

 

because RST

 

 

 

 

 

received from

 

 

 

 

 

remote node

 

 

 

 

 

06:

 

 

 

 

 

Reopened

 

 

 

 

 

because of

 

 

 

 

 

no keep-alive

 

 

 

 

 

response

 

 

 

 

 

 

 

 

 

 

 

07: Illegal

Refer to Operation Manual, Con-

---

 

 

 

FINS/TCP

struction of Applications: SEC-

 

 

 

 

procedure

TION 7, and correct the remote

 

 

 

 

 

node (application on a personal

 

 

 

 

 

computer).

 

 

 

 

 

 

 

 

 

 

08: Insuffi-

There is too much load (traffic) on

---

 

 

 

cient mem-

the Ethernet Unit. Correct the sys-

 

 

 

 

ory during

tem so that traffic is not concen-

 

 

 

 

server pro-

trated.

 

 

 

 

cessing

 

 

 

 

 

09: Insuffi-

 

 

 

 

 

cient mem-

 

 

 

 

 

ory during

 

 

 

 

 

client pro-

 

 

 

 

 

cessing

 

 

 

 

 

0A: Insuffi-

 

 

 

 

 

cient mem-

 

 

 

 

 

ory during

 

 

 

 

 

node switch-

 

 

 

 

 

ing

 

 

 

 

 

 

 

 

03C3

FINS/UDP packet discarded

00

01 to FE:

The automatic generation (static)

---

 

 

 

Transmission

method was used as the IP

 

 

 

 

source node

address conversion method, so

 

 

 

 

address

remote IP address information in

 

 

 

 

 

internal memory could not be

 

 

 

 

 

changed.

 

 

 

 

 

 

 