Error Log

 

 

 

Section 8-3

 

 

 

 

 

 

 

Error

 

Meaning

Detailed error code

Correction

EE-

code

 

 

 

 

 

PROM

 

 

1st byte

2nd byte

 

 

 

 

 

 

 

 

 

 

 

 

0601

CPU Bus Unit error

Arbitrary

 

Restart the CPU Unit. If the prob-

Saved

 

 

 

 

 

lem persists, replace the Ethernet

 

 

 

 

 

 

Unit.

 

 

 

 

 

 

 

0602

CPU Bus Unit memory error

01: Read

06: Error log

Restart the CPU Unit. If the prob-

Saved

 

 

 

error

 

lem persists, replace the Ethernet

(except

 

 

 

02: Write

 

Unit.

for error

 

 

 

 

 

log)

 

 

 

error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note (1) The time information in the CPU Unit is used in the CPU Bus Units.

(2)If the time information cannot be read from the CPU Unit, the time stamp in the error log will be all zeros. This can occur due to CPU Unit startup error, unit number errors, CPU error, and model number errors. If the time is read out from a Programming Device, the time will be shown as all ze- ros in the year 2000.

(3)The battery must be installed in the CS/CJ-series CPU Unit, the power turned ON, and then the time set before the clock in the CPU Unit can be used. The time will not be set correctly in the error log unless the clock time is set correctly.

(4)An error record is not created in EEPROM when a CPU Bus Unit memory error occurs.