DM Area Allocations

Section 4-2

IP Address Display/Setting Area

m+98

m+99

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

 

(1)

 

 

(2)

 

 

 

(3)

 

 

 

(4)

 

 

(5)

 

 

(6)

 

 

 

(7)

 

 

 

(8)

 

IP address: (1)(2).(3)(4).(5)(6).(7)(8) (Hex)

If the local IP address in the CPU Bus Unit System Setup is set to a value other than 0.0.0.0, this area (words m+98 and m+99) will act as an IP Address Display Area and the local IP address set in the CPU Bus Unit System Setup will be read and stored here when the power is turned ON or the Unit restarted. If the local IP address in the CPU Bus Unit System Setup is set to

0.0.0.0(the default setting), this value is read by the Ethernet Unit when the power is turned ON or the Unit restarted and is used as the local IP address.

Note

Choose the method used to set the local IP address as follows:

 

Set the local IP address in the CPU Bus Unit System Setup when making

 

other settings in the CPU Bus Unit System Setup. The settings are made with

 

CX-Programmer.

 

 

 

Set the local IP address in the allocated words in the DM Area when using the

 

CPU Bus Unit System Setup at its default settings (i.e., for simple operation).

 

The setting is usually made with a Programming Console.

 

 

 

 

Application

Setting device

Setting area

Remarks

 

 

 

 

Simple operation (i.e., The CPU

Programming Con-

Allocated words in

The setting in the allocated words in

Unit Bus System Setup is used at

sole (CX-Program-

the DM Area

the DM Area is enabled only when the

its default settings. Only the IP

mer can also be

 

IP address in the CPU Unit Bus Sys-

address is set.)

used.)

 

tem Setup is set to 0.0.0.0.

 

 

 

If the IP address in the CPU Unit Bus

 

 

 

System Setup is set to a value other

 

 

 

than 00.00.00.00, this value is stored in

 

 

 

the allocated words in the DM Area.

 

 

 

 

Operation with the CPU Unit Bus

CX-Programmer

CPU Unit Bus Sys-

The IP address set in the CPU Unit Bus

System Setup set as desired (i.e.,

 

tem Setup

System Setup is stored in the allocated

The default settings are not used.)

 

 

words in the DM Area.

 

 

 

 

Replacing the previous CS1W-

---

---

The IP address is set using a rotary

ETN01/CS1W-ETN11 and using

 

 

switch in the previous CS1W-ETN01/

the previous settings.

 

 

CS1W-ETN11 Ethernet Units. In the

 

 

 

new Ethernet Units, the IP address set

 

 

 

with the rotary switch is displayed in the

 

 

 

DM Area. This area is backed up by the

 

 

 

battery, so the IP address can be used

 

 

 

without resetting.

 

 

 

 

Note (1) If a value other than 00.00.00.00 is set as the local IP address in the CPU Bus Unit System Setup, even if an IP address is set in the allocated words in the DM Area, it will be overwritten with the setting in the CPU Bus Unit System Setup.

(2)It is not possible to set the following IP addresses. If any of these values are set, the ERH indicator will flash.

IP addresses where all network number bits are 0 or 1.

IP addresses where all host number bits are 0 or 1.

IP addresses where all subnet number bits are 1.

IP addresses that start with 127 (7F hexadecimal, e.g., 127.35.21.16).

89

Page 114
Image 114