Omron CS1W-ETN21 TCP Send Request, Requests that data be received at a TCP socket, Etimedout

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 203
Image 203

Command/Response Reference

Section 7-3

Response Codes

 

 

 

 

 

Response code

Description

 

 

 

 

0000

Normal

 

 

 

 

0105

Local IP address setting error

 

 

 

 

0302

CPU Unit error; execution not possible.

 

 

 

 

1001

Command too large

 

 

 

 

1002

Command too small

 

 

 

 

1100

TCP socket number or number of reception bytes is out of

 

 

range.

 

 

 

 

1101

The variable type for the results storage area is out of range.

 

 

 

 

1103

Non-zero bit address specified for the results storage area.

 

 

 

 

220F

The specified socket is receiving data.

 

 

 

 

2210

No connection could be established to the specified socket.

 

 

 

 

2211

High traffic at Unit; cannot execute service.

 

 

 

Results Storage Area Response Codes

 

 

 

 

 

Response code

Description

 

 

 

 

0000

Normal

 

 

 

 

003E

Internal buffer cannot be reserved due to high receive load

 

 

(ENOBUFS).

 

 

 

 

0042 (see note)

Received ICMP data (EMSGSIZE).

 

 

 

 

0044 (see note)

Received ICMP data (ENOPROTOOPT).

 

 

 

 

0045 (see note)

A communication error occurred with the remote node

 

 

(ECONNABORTED).

 

 

 

 

004B

A communication error occurred with the remote node

 

 

(ECONNRESET).

 

 

 

 

004E (see note)

Incorrect destination IP address (ENETUNREACH).

 

 

No network number in IP router table.

 

 

Router incorrectly set.

 

 

 

 

004F (see note)

Received ICMP data (EHOSTDOWN).

 

 

 

 

0051 (see note)

Received ICMP data (EHOSTUNREACH).

 

 

Router incorrectly set.

 

 

 

 

0053

A communications error occurred with the remote node

 

 

(ETIMEDOUT).

 

 

 

 

0066

Internal memory cannot be allocated; cannot execute service.

 

 

 

 

0080

A receive request timeout error occurred.

 

 

 

 

0081

Socket was closed while receiving.

 

 

 

Note These errors occur only in large multilayered networks.

7-3-16 TCP SEND REQUEST

Requests that data be received at a TCP socket.

Command Block

27

13

 

Command

Results storage area Number of

code

bytes sent

TCP socket number

Socket option

1,984 bytes max.

Data sent

178

Page 203
Image 203
Omron CS1W-ETN21 operation manual TCP Send Request, Requests that data be received at a TCP socket, Etimedout