Omron CS1W-ETN21 operation manual Indicator Color Status Meaning

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 51
Image 51

Nomenclature and Functions

 

Section 1-6

 

 

 

 

Indicator

Color

Status

Meaning

 

 

 

 

RUN

Green

Not lit

Operation stopped

 

 

 

Hardware error

 

 

 

 

 

 

Lit

Normal operation

 

 

 

 

100M

Green

Not lit

10 Mbps (10Base-T)

(Transfer speed)

 

 

 

 

Lit

100 Mbps (100Base-TX)

 

 

 

 

ERC

Red

Not lit

Unit normal

(Ethernet Unit error)

 

 

 

 

Lit

Node address not between 1 and 254

 

 

 

A hardware (e.g., internal memory) error has occurred.

 

 

 

 

ERH

Red

Not lit

CPU Unit normal

(CPU Unit error)

 

 

 

 

Lit

An error has occurred at the CPU Unit.

 

 

 

There is an error in the I/O table, unit number, unit setup, or routing

 

 

 

table settings.

 

 

 

 

 

 

Flashing

An illegal IP address has been set. With automatic address gener-

 

 

 

ation, the rightmost two digits of the IP address do not match the

 

 

 

node address.

 

 

 

 

SD

Yellow

Not lit

Not sending data (ready to send)

(Send Data)

 

 

 

 

Lit

Sending data

 

 

 

 

RD

Yellow

Not lit

Not receiving data (ready to receive)

(Receive Data)

 

 

 

 

Lit

Receiving data

 

 

 

 

LNK

Yellow

Not lit

Link not established between hubs.

(Link status)

 

 

 

 

Lit

Link established between hubs.

 

 

 

 

TCP

Yellow

Not lit

None of the eight TCP sockets provided for socket services is in

(TCP socket in use)

 

 

use.

 

 

 

 

 

Lit

At least one of the eight TCP sockets provided for socket services

 

 

 

is in use.

 

 

 

 

FTP

Yellow

Not lit

FTP server on standby.

(FTP Server Service)

 

 

 

 

Lit

FTP server operating (one user connected).

 

 

 

 

HOST

Yellow

Not lit

Server (DNS, SMTP, POP3, or SNTP) not being used.

(Server connection sta-

 

 

 

 

Flashing

An error has occurred in the server connection.

tus)

 

 

 

 

Lit

The server connection is normal.

 

 

 

 

 

 

26