Setup

Section 3-1

3-1 Setup

Item

Contents

Default

 

 

 

Broadcast

Set the method for specifying IP addresses for broadcasting in FINS/

All 1 (4.3BSD)

 

UDP.

 

 

• All 1 (4.3BSD): Broadcast with host number set to all ones.

 

 

• All 0 (4.2BSD): Broadcast with host number set to all zeros.

 

 

Normally the default setting should be used.

 

 

 

 

IP Address

Set the local IP address for the Ethernet Unit.

0.0.0.0 (FINS node

 

 

address

 

 

192.168.250.)

 

 

 

Sub-net Mask

Set the subnet mask for the Ethernet Unit.

0.0.0.0

 

This is required if a method other than the IP address table method is

(default net mask

 

used for address conversion.

for IP address set-

 

 

ting)

 

 

 

FINS/UDP Port

Specify the local UDP port number to be used for the FINS communica-

9,600

 

tions service. The UDP port number is the number used for UDP identi-

 

 

fication of the application layer (i.e., the FINS communications service in

 

 

this case).

 

 

• Default (9,600)

 

 

• User defined (Setting range: 1 to 65,535)

 

 

Note: Make the settings so that UDP port number 123 for SNTP does

 

 

not overlap with UDP port number 53 for DNS.

 

 

 

 

FINS/TCP Port

Specify the local TCP port number to be used for the FINS communica-

9,600

 

tions service. The TCP port number is the number used for TCP identifi-

 

 

cation of the application layer (i.e., the FINS communications service in

 

 

this case).

 

 

• Default (9,600)

 

 

• User defined (Setting range: 1 to 65,535)

 

 

Note: Make the settings so that TCP port numbers 20 and 21 for the

 

 

FTP server, TCP port number 25 for SMTP, TCP port number 110 for

 

 

POP3, and TCP port number 53 for DNS do not overlap.

 

 

 

 

Conversion

Select any of the following as the method for finding and converting IP

Auto (dynamic)

 

addresses from FINS node addresses. (Enabled for FINS/UDP only.)

 

 

• Automatic generation (dynamic): Auto (dynamic)

 

 

• Automatic generation (static): Auto (Static)

 

 

• IP address table method: Table used

 

 

• Combined method: Mixed

 

 

 

 