Omron CS1W-ETN21 operation manual Reception Problems, Read Controller Status

Models: CS1W-ETN21

1 285
Download 285 pages 16.7 Kb
Page 237
Image 237

Troubleshooting Procedures

Section 8-4

Reception Problems

Reception Problems occurred.

Is reception

Is the remote

processing

finishing?

Y

N

node not processing to

N

Adjust the remote node to process send data.

 

 

 

 

 

 

 

 

 

send data?

 

 

 

 

 

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Read controller status using the FINS command

READ CONTROLLER STATUS.

 

 

 

 

 

 

 

There may be noise affecting the network.

Have any reception

Y

Increase the number of retries or take

measures against noise as described in 2-4

errors occurred?

 

 

 

 

Network Installation.

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Read memory status using the FINS command

READ MEMORY STATUS.

Is the network memory being used more Y

than 80%?

N

Read protocol status using the FINS command READ PROTOCOL STATUS.

There may be too much load on the Ethernet Unit. If the memory exhaustion records show counts, UDP data may be corrupted. Check your applications.

Are any of

Y

The UDP protocol of the remote node may not

the first three items in the

be compatible with that of the Ethernet Unit.

 

 

 

status being counted?

 

 

 

Use another communications service.

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Return to the procedure for general problems.

Check the remote node for transmission problems using the next procedure. If nothing is uncovered, go to Network Connection Problems.