Basic Settings

Section 2-9

Default Setting

The Ethernet Unit operates using the default IP address when the Unit is mounted to the PLC and initially registered in the I/O tables (i.e., when the Unit settings have not been made and the IP Address Display/Setting in the CPU Bus Unit Words Allocated in the DM Area is still all zeros).

The default IP address is determined as follows:

Default IP address = 192.168.250.FINS node address

The FINS node address is set by the rotary switch on the front of the Ethernet Unit. If the defaults are used for the IP address and the Unit settings, the set- tings will be as shown below.

Item

Operation status

IP address

192.168.250.FINS node address

 

 

Subnet mask

255.255.255.0 (Class C mask)

 

 

Broadcast settings

4.3BSD

 

 

Baud rate

Auto

 

 

TCP/IP keep-alive

120 min.

 

 

IP router table

None (IP router not enabled)

Setting the IP Address in the CPU Bus Unit Words Allocated in the DM

Area

This method sets the IP address in the IP Address Display/Setting Area in the CPU Bus Unit Words Allocated in the DM Area, when the IP address is not set in the Unit Setup. When the IP address is set in the Unit Setup, the IP Address Display/Setting Area becomes the area for displaying the settings.

To make settings in the IP Address Display/Setting Area, use the CX-Pro- grammer or Programming Console to write the values. In order for the new settings to go into effect, either the Ethernet Unit must be restarted or the power must be turned ON again to the PLC.

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

m+98

 

(1)

 

 

(2)

 

 

 

(3)

 

 

 

 

(4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m+99

 

(5)

 

 

(6)

 

 

 

(7)

 

 

 

 

(8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IP address: (1)(2).(3)(4).(5)(6).(7)(8) (hexadecimal)

If only the IP address is set, according to the IP Address Display/Setting Area, and the defaults are used for all other Unit settings, the settings will be as shown below.

Item

Status

 

 

IP address

Words allocated for CPU Bus Unit (m+98 to m+99)

 

 

Subnet mask

Uses value corresponding to IP address class.

 

 

Broadcast settings

4.3BSD specifications

 

 

Baud rate

Auto

 

 

TCP/IP keep-alive

120 minutes

 

 

IP router table

Not set. (IP routing not supported.)

 

 

Unit Setup

This method sets the IP address by first selecting the Ethernet Unit from the CX-Programmer's I/O Table Window while connected online, and then setting the IP address from the Unit Setup.