Using FINS Applications

 

Section 6-5

• Local Network Table

 

 

 

 

 

 

 

Unit number

Local network number

 

 

 

 

 

 

0

1

 

 

 

 

 

 

1

2

 

 

 

 

 

•Relay Network Table None

Example: PLC 2 and PLC 3 Routing Table Settings

•Local Network Table

Unit number

Local network number

 

 

0

2

 

 

•Relay Network Table

In order to relay from PLC2/3 to the final network number 1, it is necessary to relay via node address 1 (i.e., the Controller Link Unit) on relay network number 2.

Final network number

Relay network number

Relay node address

 

 

 

1

2

1

 

 

 

2.Save the routing table file (File - Save local routing table file).

3.Select New from the Project Menu, and save with a file name. Then select Add Device from the Project Menu. For each PLC, register a PLC with a direct serial connection (node address: 0), and select it.

4.With CX-Integrator, select Open from the PLC Menu.

5.Select Routing table − Setup, read the saved file, and select Options − Transfer to PLC. Click Yes to transfer the routing tables to the connected PLCs.

6-5-2 FinsGateway

FinsGateway Ver. 2003 must be used to communicate using FINS/TCP between applications serving as communications drivers and CS1W-ETN21 or CJ1W-ETN21 Ethernet Units.

FinsGateway Ver. 3.@ or lower versions can be used, however, when commu- nicating by the FINS/UDP method only.

■Overview of Setup Methods

1. Starting FinsGateway Settings

Select FinsGateway − FinsGateway Setup to start the FinsGateway Setup.

2. ETN_UNIT Driver Setup

1.Double-click on ETN_UNIT in the settings for the network and Unit. The fol- lowing ETN_UNIT Properties Window will be displayed.

130

Page 155
Image 155
Omron CS1W-ETN21 Local Network Table, Overview of Setup Methods Starting FinsGateway Settings, Etnunit Driver Setup